GE Appliances RAK Series Power Supply Kit for Sub-base Instruction Manual

June 10, 2024
GE Appliances

GE Appliances LOGO Installation Instructions for your new
RAK315SP, RAK320SP, RAK330SP
Power Supply Kit for Sub-base

RAK Series Power Supply Kit for Sub-base

Before you begin – Read these instructions completely and carefully.
IMPORTANT – OBSERVE ALL GOVERNING CODES AND ORDINANCES.

Tools Needed

  • Phillips Head Screw Driver

This kit is for use with 230/208 volt replacement GE Zonetime units only with previously installed subbases.
NOTE: Use only with sub-base kits RAK204D15, RAK204D20, or RAK204D30*.

230/208 VOLT ELECTRICAL SUPPLY
A power supply kit must be used to supply power to the Zonetime unit. The appropriate kit is determined by the voltage, the means of electrical connection, and the amperage of the branch circuit. See the POWER CONNECTION CHART to corm the appropriate kit.

GE Appliances RAK Series Power Supply Kit for Sub base

All wiring, including installation of the receptacle, must be in accordance with the NEC, local codes, ordinances, and regulations.

GE Appliances RAK Series Power Supply Kit for Sub base -
FIG

WARNING
RISK OF ELECTRIC SHOCK.
Disconnect the electrical power supply before wiring connections.

IMPORTANT NOTES

  • This unit must be properly connected to a grounded circuit.
  • The electrical rating marked on the power supply kit must be the same as the supply branch circuit.
  • Aluminum building wiring may present special problems—consult a qualified electrician.
  • All wiring, including installation of the receptacle, must be in accordance with the NEC, local codes, ordinances, and regulations.
  • Use ONLY the wiring size recommended for single outlet branch circuit.
  • Proper current protection is the responsibility of the owner.

Recommended branch circuit wire sizes*

Nameplate maximum circuit breaker size| AWG wire size**
15A
20A
30A| 14
12
10
AWG —American Wire Gauge

  • Single circuit breaker from main box
    ** Based on copper wire, single-insulated conductor at 60°C

NOTE: Use copper conductors only.

POWER CONNECTION CHART

GE 230/208 Volt Power Supply Kit| Receptacle Configuration| Circuit Protective Device
RAK315SP| Tandem| 15-Amp Time-Delay Fuse or Breaker
RAK320SP| Perpendicular| 20-Amp Time-Delay Fuse or Breaker
RAK330SP| Large Tandem| 30-Amp Time-Delay Fuse or Breaker

Installation Instructions

FOR 230/208 VOLT ZONELINE POWER CORD CONNECTIONS ONLY
For GE Zonetime AZ45 & AZ65 Series Units
This kit must be used in conjunction with a GE junction box kit and sub base with causeway.

1. REMOVE ROOM FRONT
Remove the room cabinet by pulling it out at the bottom to release it (1); then lift it up to clear the rail along the unit top (2).

2. REMOVE JUNCTION BOX COVER
Remove the junction box cover by removing the screw holding it to the assembly.

GE Appliances RAK Series Power Supply Kit for Sub base - FIG
3

3. CONCEAL POWER SUPPLY KIT SUB-BASE AND CHASEWAY

  1. Remove the rectangular knockout at the bottom of the junction box. Remove the rectangular knockout at the right end of the sub-base.
  2. Power Supply kit is placed between the two halves of the causeway. Observe the orientation of the causeway.GE Appliances RAK Series Power Supply Kit for Sub base - FIG 5
  3. Align the screw holes and secure the halves together using two type A screws.
  • Slide the upper end of chaseway with wiring protruding into rectangular knockout opening in the junction box.Be sure chaseway “ears” are on the inside of the box.
  • Drive one type A screw through the junction box bottom into the chaseway “ear” hole.
  • Insert lower end of chaseway into rectangular hole in sub-base and slide to right into the rectangular knockout making sure chaseway “ears” are inside the sub-base.
  • Route wire toward the center of the sub-base.
  • Drive one type A screw through the sub-base slotted hole into chaseway “ear” hole.

ZONELINE SERIES – POWER SUPPLY KIT

4. INSTALL JUNCTION BOX
Install the junction box by engaging the tabs of the junction box with the slots on the control housing, align the screw hole at the top and drive the supplied screw until  secure.

GE Appliances RAK Series Power Supply Kit for Sub base - FIG
6

5. CONNECT THE CORDSET
Plug in the connectors on the power supply kit into the corresponding mating connectors on the Zonetime. Be sure to locking tabs at the sides are engaged.
Insert the plug into the receptacle inside the subbase.

NOTE: Power Supply Kit – Appearance may vary RAK315SP will only have one power connector.

6. INSTALL JUNCTION BOX COVER

  1. Replace and secure all front covers on the sub base. Do not pinch any wires.
  2. Place the junction box cover in place. Replace the two screws removed earlier and tighten securely.
  3. Replace the Zonetime front cabinet.

GE Appliances LOGO

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

GE Appliances User Manuals

Related Manuals