tyco TY4235 Pendent Quick Response Dry-Type Sprinkler
General Description
TYCO Series DS-1 5.6K Pendent, Upright, and Horizontal Sidewall, Stan-dard Response (5 mm bulb), Standard Coverage Dry-type Sprinklers are dec-orative glass bulb automatic sprinklers typically used where:
- pendent sprinklers are required on dry pipe systems that are exposed to freezing temperatures (for example, sprinkler drops from unheated portions of buildings)
- sprinklers and/or a portion of the connecting piping may be exposed to freezing temperatures (for example, sprinkler drops from wet systems into freezers, or horizontal piping extensions through a wall to protect unheated areas of a building such as loading docks, overhangs, and building exteriors)
- sprinklers are used on systems that are seasonably drained to avoid freezing (for example, vacation resort areas)
NOTICE
Series DS-1 Dry-type Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applica-ble standards of the NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), in addition to the standards of any other authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for maintaining their fire protection system and devices in proper operating con- dition. Contact the installing contrac-tor or product manufacturer with any questions. Series DS-1 Dry-type Sprinklers must only be installed in fittings that meet the requirements of the Design Crite-ria section.
Sprinkler Identification Numbers (SINs)
- TY3255 – Pendent
- TY3155 – Upright
- TY3355 – Horizontal Sidewall
Technical Data
Approvals
- UL and C-UL Listed
- FM Approved
- NYC Approved
- under MEA 352-01-E LPCB Approved
- Reference No. 094a/11 CE Certified
- Certificate of Conformity No.2831-CPR-S2015
See Tables A and B for details.
Maximum Working Pressure
- 175 psi (12,1 bar)
Inlet Thread Connections
- 1 in. NPT
- ISO 7-R 1
Discharge Coefficient
K=5.6 gpm/psi½ (80,6 lpm/bar½)
Temperature Ratings
See Tables A and B.
Finishes
Sprinkler: See Table D.
Escutcheon: See Table D.
Physical Characteristics
- Inlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Copper
- Plug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Copper
- Yoke ………………….. Stainless Steel
- Casing …………. Galvanized Carbon Steel
- Bulb Seat Stainless Steel
- Bulb (5 mm dia.) Glass
- Compression Screw Bronze
- Deflector Bronze
- Frame Bronze
- Guide Tube Stainless Steel
- Water Tube Stainless Steel
- Spring. . . . . . . . . . . . . . . . . . . . . .Stainless Steel
- Sealing Assembly. . Beryllium Nickel w/TEFLON
- Escutcheon. . . . Carbon Steel or Stainless Steel
TFP500
SPRINKLER TYPE
| ****
ESCUTCHEON TYPE
| ****
TEMPERATURE RATING
| ****
BULB COLOR CODE
| SPRINKLER FINISH
---|---|---|---|---
NATURAL BRASS| CHROME PLATED| **POLYESTER***
PENDENT (TY3255)
| ****
STANDARD
| 135°F (57°C)| Orange| ****
1, 2, 3, 4, 5
| ****
1, 2, 4, 5
155°F (68°C)| Red
175°F (79°C)| Yellow
200°F (93°C)| Green
286°F (141°C)| Blue
360°F (182°C)| Mauve| 1, 2, 3| 1, 2
RECESSED
| 135°F (57°C)| Orange| ****
1, 2, 3, 5
| ****
1, 2, 5
155°F (68°C)| Red
175°F (79°C)| Yellow
200°F (93°C)| Green
286°F (141°C)| Blue| 1, 2
360°F (182°C)| Mauve| N/A
DEEP
| 135°F (57°C)| Orange| ****
1, 2, 3, 4, 5
| ****
1, 2, 4, 5
155°F (68°C)| Red
175°F (79°C)| Yellow
200°F (93°C)| Green
286°F (141°C)| Blue
360°F (182°C)| Mauve
WITHOUT
| 135°F (57°C)| Orange
155°F (68°C)| Red
175°F (79°C)| Yellow
200°F (93°C)| Green
286°F (141°C)| Blue
360°F (182°C)| Mauve| 1, 2, 3| 1, 2
UPRIGHT (TY3155)
| ****
WITHOUT
| 135°F (57°C)| Orange| ****
1, 2, 3, 4, 5
| ****
1, 2, 4, 5
155°F (68°C)| Red
175°F (79°C)| Yellow
200°F (93°C)| Green
286°F (141°C)| Blue
360°F (182°C)| Mauve| 1, 2, 3| 1, 2
Notes:
1. Listed by Underwriters Laboratories, Inc. (UL), maximum order length of 48 in.
2. Listed by Underwriters Laboratories for use in Canada (C-UL), maximum order length of 48 in.
3. Approved by FM Global (FM Approvals), maximum order length of 48 in.
4. Loss Prevention Certification Board (LPCB) and CE conformity apply to these temperature ratings only
5. Approved by the City of New York under MEA 352-01-E
- Frame and deflector only N/A – Not Applicable
TABLE A
SERIES DS-1 PENDENT & UPRIGHT DRY-TYPE SPRINKLERS, 5.6K, STANDARD RESPONSE LABORATORY LISTINGS AND APPROVALS
SPRINKLER TYPE
| ****
ESCUTCHEON TYPE
| ****
TEMPERATURE RATING
| ****
BULB COLOR CODE
| SPRINKLER FINISH
---|---|---|---|---
NATURAL BRASS| CHROME PLATED| **POLYESTER*****
*HSW (TY3355)**
| ****
STANDARD
| 135°F (57°C)| Orange| ****
1, 2, 3***, 4, 5
| ****
1, 2, 4, 5
155°F (68°C)| Red
175°F (79°C)| Yellow
200°F (93°C)| Green
286°F (141°C)| Blue
360°F (182°C)| Mauve
DEEP
| 135°F (57°C)| Orange
155°F (68°C)| Red
175°F (79°C)| Yellow
200°F (93°C)| Green
286°F (141°C)| Blue
360°F (182°C)| Mauve
WITHOUT
| 135°F (57°C)| Orange
155°F (68°C)| Red
175°F (79°C)| Yellow
200°F (93°C)| Green
286°F (141°C)| Blue
360°F (182°C)| Mauve| 1, 2, 5| 1, 2
Notes:
1. Listed by Underwriters Laboratories, Inc. (UL), maximum order length of 48 in.
2. Listed by Underwriters Laboratories for use in Canada (C-UL), maximum order length of 48 in.
3. Approved by FM Global (FM Approvals), maximum order length of 48 in.
4. Loss Prevention Certification Board (LPCB) and CE conformity apply to these temperature ratings only
5. Approved by the City of New York under MEA 352-01-E
* Horizontal sidewall with top of deflector-to-ceiling distance of 4 to 12 in. (100 to 300 mm)
** Light and ordinary hazard occupancies only
*** Light hazard occupancies only
**** Frame and deflector only
TABLE B
SERIES DS-1 HORIZONTAL SIDEWALL (HSW) DRY-TYPE SPRINKLER, 5.6K, STANDARD RESPONSE LABORATORY LISTINGS AND APPROVALS
TFP500
Ambient Temperature Exposed to
Discharge End of Sprinkler
| Temperatures for Heated Area (1)
---|---
40°F (4°C)| 50°F (10°C)| 60°F (16°C)
Minimum Exposed Barrel Length (2) , in.
(mm)
40°F (4°C)| 0| 0| 0
30°F (-1°C)| 0| 0| 0
20°F (-7°C)| 4
(100)
| 0| 0
10°F (-12°C)| 8
(200)
| 1
(25)
| 0
0°F
(-18°C)
| 12
(305)
| 3
(75)
| 0
-10°F (-23°C)| 14
(355)
| 4
(100)
| 1
(25)
-20°F (-29°C)| 14
(355)
| 6
(150)
| 3
(75)
-30°F (-34°C)| 16
(405)
| 8
(200)
| 4
(100)
-40°F (-40°C)| 18
(455)
| 8
(200)
| 4
(100)
-50°F (-46°C)| 20
(510)
| 10
(255)
| 6
(150)
-60°F (-51°C)| 20
(510)
| 10
(255)
| 6
(150)
Notes:
1. For protected area temperatures that occur between values listed above, use the next cooler temperature.
2. These lengths are inclusive of wind velocities up to 30 mph (18,6 kph).
TABLE C
EXPOSED SPRINKLER BARRELS IN WET PIPE SYSTEMS MINIMUM RECOMMENDED LENGTHS
Operation
When TYCO Series DS-1 5.6K Pendent, Upright, and Horizontal Sidewall, Standard Response, Standard Coverage Dry-type Sprinklers are in service, water is prevented from entering the assembly by the Plug with Sealing Assembly (see Figure 1) in the Inlet of the sprinkler. The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, and the Bulb Seat is released. The compressed Spring is then able to expand and push the Water Tube as well as the Guide Tube outward. This action simultaneously pulls inward on the Yoke, withdrawing the Plug with Sealing Assembly from the Inlet, allow-ing the sprinkler to activate and flow water.
Design Criteria
TYCO Series DS-1 5.6K Pendent, Upright, and Horizontal Sidewall, Standard Response, Standard Coverage Dry-type Sprinklers are intended for use in fire sprinkler systems designed in accordance with the standard install-location rules recognized by the applicable listing or approval agency (for example, UL Listing is based on NFPA 13 requirements). For more information on LPCB Approval, contact Johnson Controls at the following office:
- Kopersteden 1
- 7547 TJ Enschede
- The Netherlands
- Tel: +31-(0)53-428-4444 Fax: +31-(0)53-428-3377
Sprinkler Fittings
Install 1 in. NPT Series DS-1 Dry-type Sprinklers in the 1 in. NPT outlet or
run of the following fittings:
- malleable or ductile iron threaded tee fittings that meet the dimensional requirements of ANSI B16.3 (Class 150)
- cast iron threaded tee fittings that meet the dimensional requirements of ANSI B16.4 (Class 125)
Do not install Series DS-1 Dry-type Sprinklers into elbow fittings. The Inlet of the sprinkler can contact the interior of the elbow. The unused outlet of the threaded tee is plugged as shown in Figure 12.
TFP500
You can also install Series DS-1 Dry-type Sprinklers in the 1 in. NPT outlet of a GRINNELL Figure 730 Mechanical Tee and GRINNELL G-FIRE Figure 522; however, the use of the Figure 730 Tee and Figure 522 for this arrangement is limited to wet pipe systems. The configuration shown in Figure 13 is only applicable for wet pipe systems where the sprinkler fitting and water-filled pipe above the sprinkler fitting are not subject to freezing and where the length of the dry-type sprinkler has the minimum exposure length depicted in Figure 11. See the Exposure Length section. For wet pipe system installations of 1 in. NPT Series DS-1 Dry-Type Sprinklers connected to CPVC piping, use only the following TYCO CPVC fittings:
- 1 in. x 1 in. NPT Female Adapter (P/N 80145)
- 1 in. x 1 in. x 1 in. NPT Sprinkler Head Adapter Tee (P/N 80249)
For dry pipe system installations, use only the side outlet of a maximum 2 1/2 in. reducing tee when locating Series DS-1 Dry-type Sprinklers directly below the branch line; otherwise, use the configuration shown in Figure 12 to assure complete water drainage from above Series DS-1 Dry-type Sprinklers and the branch-line. Failure to do so may result in pipe freezing and water damage.
NOTICE
Do not install Series DS-1 Dry-type Sprinklers into any other type fitting. Failure to use the appropriate fitting may result in one of the following:
- failure of the sprinkler to operate properly due to the formation of ice over the Inlet Plug or binding of the Inlet Plug
- insufficient engagement of the Inlet pipe threads with consequent leakage
Drainage
In accordance with the minimum requirements of the NATIONAL FIRE PROTECTION
ASSOCIATION for dry pipe sprinkler systems, branch, cross, and feed-main
piping connected to Dry Sprinklers and subject to freezing temperatures must
be pitched for proper drainage.
Exposure Length
When using Dry Sprinklers in wet pipe sprinkler systems to protect areas
subject to freezing temperatures, use Table C to determine a sprinkler’s
appropriate exposed barrel length to prevent water from freezing in the
connecting pipes due to conduction. The exposed barrel length measurement must
be taken from the face of the sprinkler fitting to the surface of the
structure or insulation that is exposed to the heated area. See Figure 11 for
an example. For protected area temperatures between those given above, the
minimum recommended length from the face of the fitting to the outside of the
protected area may be determined by interpolating between the indicated
values.
Clearance Space
In accordance with NFPA 13, when connecting an area subject to freezing and an
area containing a wet pipe sprinkler system, the clearance space around the
sprinkler barrel of dry-type sprinklers must be sealed. Due to temperature
differences between the two areas, the potential for the formation of
condensation in the sprinkler and subsequent ice build-up is increased. If
this condensation is not controlled, ice build-up can occur that might damage
the dry-type sprinkler and/or prevent proper operation in a fire situation.
Use of the Model DSB-2 Dry Sprinkler Boot, described in technical data sheet
TFP591 and shown in Figures 14 and 15, can provide the recommended seal
.
Installation
TYCO Series DS-1 5.6K Pendent, Upright, and Horizontal Sidewall, Standard Response, Standard Coverage Dry-type Sprinklers must be installed in accordance with this section.
General Instructions
Series DS-1 Dry-type Sprinklers must only be installed in fittings that meet
the requirements of the Design Criteria section. See the Design Criteria
section for other important requirements regarding piping design and sealing
of the clearance space around the Sprinkler Casing. Do not install any bulb-
type sprinkler if the bulb is cracked or there is a loss of liquid from the
bulb. With the sprinkler held horizontally, a small air bubble should be
present. The diameter of the air bubble is approximately 1/16 in. (1,6 mm) for
the 135°F (57°C) rating to 1/8 in. (3,2 mm) for the 360°F (182°C) rating.
Obtain a leak-tight 1 in. NPT sprinkler joint by applying a minimum-to-maxi-
mum torque of 20 to 30 lb-ft (26,8 to 40,2 N·m). Higher levels of torque may
distort the sprinkler Inlet with consequent leakage or impairment of the
sprinkler. Do not attempt to compensate for insufficient adjustment in an
Escutch-eon Plate by under or over-tightening the Sprinkler. Re-adjust the
position of the sprinkler fitting to suit.
Notes:
- Install pendant sprinklers only in the pendent position; install upright sprinklers only in the upright position. The deflector of a pendent or upright sprinkler is to be parallel to the ceiling.
- Install horizontal sidewall sprinklers in the horizontal position with their centerline of waterway perpendicular to the back wall and parallel to the ceiling. Ensure the word “TOP” on the Deflector faces the ceiling.
Step 1. With a non-hardening pipe-thread sealant such as TEFLON applied
to the inlet threads, hand-tighten the sprinkler into the sprinkler fitting.
Step 2. Wrench-tighten the sprinkler using either:
- a pipe wrench on the Inlet Band or the Casing, see Figure 1
- the W-Type 7 Sprinkler Wrench on the Wrench Flat, see Figure 2 Apply the wrench recess of the W-Type 7 Sprinkler Wrench to the wrench flat.
Note: If sprinkler removal becomes necessary, remove the sprinkler using
the same wrenching method noted above. Sprinkler removal is easier when a non-
hardening sealant was used and torque guidelines were followed. After removal,
inspect the sprinkler for damage.
Step 3. After installing the ceiling or wall and applying a ceiling
finish, slide on the outer piece of the escutcheon until it comes in contact
with the ceiling/wall. Do not lift the ceiling panel out of its normal
position. When using the Deep Escutcheon, hold the outer piece in contact with
the mounting surface (ceiling or wall). Then rotate the inner piece
approximately 1/4 turn with respect to the outer piece, to hold the Deep
Escutcheon firmly together.
Care and Maintenance
TYCO Series DS-1 5.6K Pendent, Upright, and Horizontal Sidewall, Standard Response, Standard Cover-age Dry-type Sprinklers must be maintained and serviced in accordance with this section. Before closing a fire protection system’s main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection systems from the proper authorities and notify all personnel who may be affected by this action. The absence of the outer piece of an escutcheon, which is used to cover a clearance hole, may delay the time of sprinkler operation in a fire situation. A Vent Hole is provided in the Bulb Seat (see Figure 1) to indicate if the Dry Sprinkler is remaining dry. Evidence of leakage from the Vent Hole indicates potential leakage past the Inlet seal and the need to remove the sprinkler to determine the cause of leakage; for example, an improper installation or an ice plug. Close the fire protection system control valve and drain the system before removing the sprinkler. Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or otherwise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprinklers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. See the Installation section. The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the NATIONAL FIRE PROTECTION ASSOCIATION, such as NFPA 25, in addition to the standards of any other authorities having jurisdiction. Contact the installing contractor or product manufacturer with any questions. Automatic sprinkler systems are recommended to be inspected, tested, and maintained by a qualified Inspec-tion Service in accordance with local requirements and/or national codes.
Limited Warranty
For warranty terms and conditions, visit www.tyco-fire.com.
Ordering Procedure
Contact your local distributor for availability. When placing an order, indicate the full product name, including description and part number (P/N).
Dry-type Sprinklers
When ordering Series DS-1 5.6K Pendent, Upright, and Horizontal Side-wall,
Standard Response, Standard Coverage Dry-type Sprinklers, specify the
following information:
- SIN :
- TY3255 – Pendent
- TY3155 – Upright
- TY3355 – Horizontal Sidewall
- Order Length: Dry-type Sprinklers are furnished based upon Order Length as measured per Figures 3 through 10, as applicable. After the measurement is taken, round it to the nearest 1/4 in. increment.
- Inlet Connections: 1 in. NPT (Standard) ISO 7-R 1 (For information on ISO Inlet Thread Connections, contact your Johnson Controls Sales Representative.)
- Temperature Rating
- Sprinkler Finish
- Escutcheon Type and Finish, as applicable
- P/N from Table D Part numbers are for 1 in. NPT standard order sprinklers. Orders for all other sprinkler assemblies must be accompanied by a complete description.
Replacement Escutcheons
Order replacement escutcheons separately.
Note: Style 10 Recessed Escutcheons are shipped as assemblies comprised of closure rings and mounting plates. The included mounting plate is not used for Dry Type Sprinkler applications, discard accordingly. Specify: (specify type), (specify) finish, P/N (specify):
Recessed (Style 10)
- Brass Plated . . . . . . . . . . . . . . . . . 56-701-2-010
- Signal White (RAL9003) 56-701-4-010 Chrome
- Plated . . . . . . . . . . . . . . . 56-701-9-010
Standard (Push-On)
- White Color . . . . . . . . . . . . . . . . . . 91-106-0-007
- Brass Plated . . . . . . . . . . . . . . . . . 91-106-2-007
- Chrome Plated . . . . . . . . . . . . . . . 91-106-9-007
Deep
- Brass Plated . . . . . . . . . . . . . . . . . . 91-107-2-010
- White ……………………91-107-4-007
- Chrome Plated . . . . . . . . . . . . . . . 91-107-9-007
Sprinkler Wrench
Specify W-Type 7 Sprinkler Wrench, P/N 56-850-4-001
Sprinkler Boot
Specify Model DSB-2 Dry Sprinkler Boot, P/N 63-000-0-002 This part number
includes one (1) Boot, two (2) Strap Ties, and 1/3 oz of Adhesive (a
sufficient quantity for installing one boot). 1400 Pennbrook Parkway,
Lansdale, PA 19446 | Telephone
+1-215-362-0700 © 2021 Johnson
Controls. All rights reserved. All specifications and other information shown
were current as of the document revision date and are subject to change
without notice. NATIONAL FIRE PROTECTION ASSOCIATION and NFPA have registered
trademarks of the National Fire Protection Association; TEFLON is a trademark
of The Chemours Company FC, LLC