Tyco Electronics TY-FRB Fire Sprinkler Heads Instruction Manual
- June 8, 2024
- Tyco Electronics
Table of Contents
Tyco Electronics TY-FRB Fire Sprinkler Heads
IMPORTANT
Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory
and health information.
Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that
provides cautions with respect to handling and installation of sprinkler
systems and components. Improper handling and installation can permanently
damage a sprinkler system or its components and cause the sprinkler to fail to
operate in a fire situation or cause it to operate prematurely.
Scan the QR code or enter the URL in a web browser to access the most up-to-
date electronic version of this document. Data rates may apply.docs.jci.com/tycofire/series-ty-
frb-5-6K
General Description
The TYCO Series TY-FRB, 5.6 K-factor, Upright (TY313) and Pendent (TY323)
Sprinklers described in this data sheet are quick response, standard coverage,
decorative 3 mm glass bulb-type spray sprinklers designed for use in light or
ordinary hazard, commercial occupancies such as banks, hotels, and shop-ping
malls.
The recessed version of the Series TY-FRB Pendent Sprinkler, where applicable,
is intended for use in areas with a finished ceiling. This recessed pendent
sprinkler uses one of the following:
- A two-piece Style 15 Recessed Escutcheon with recessed adjust-ment up to 5/8 in. (15,9 mm) from the flush pendent position.
- A two-piece Style 20 Recessed Escutcheon with recessed adjustment up to 1/2 in. (12,7 mm) from the flush pendent position.
The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the fixed pipe drops to the sprinklers must be cut. Intermediate level versions of Series TY-FRB Sprinklers are described in Technical Data Sheet TFP357. Sprinkler guards and shields are described in Technical Data Sheet TFP780.
NOTICE
The TYCO Series TY-FRB Sprinklers described herein must be installed and
maintained in compliance with this document, as well as with the applicable
standards of the National Fire Protection Association, in addition to the
standards of any other authori-ties having jurisdiction. Failure to do so may
impair the performance of these devices.
The owner is responsible for main-taining their fire protection system and
devices in proper operating con-dition. Contact the installing contrac-tor or
product manufacturer with any questions.
Sprinkler Identification Number (SIN)
TY313 . . . . Upright 5.6K, 1/2 in. NPT
TY323 . . . .Pendent 5.6K, 1/2 in. NPT
Technical Data
Approvals
Refer to Table A
Maximum Working Pressure
- 175 psi (12.1 bar)
- 250 psi (17.2 bar)*
- The maximum working pressure of 250 psi (17.2 bar) only applies to the listing by Underwriters Laboratories, Inc. (UL).
Discharge Coefficient
K=5.6 GPM/psi½ (80,6 LPM/bar½)
Temperature Rating
Refer to Table A
Finishes
Sprinkler: Refer to Table B
Recessed Escutcheon: White Coated, Black Coated, Chrome Plated, or Brass
Plated
Physical Characteristics
- Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
- Button . . . . . . . . . . . . . . . . . . . . . . Brass/Copper
- Sealing Assembly …Stainless Steel w/TEFLON
- Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Glass
- Compression Screw . . . . . . . . . . . . . . . . .Bronze
- Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Notes:
- Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers.
- Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers.
- Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
- Approved by the City of New York under MEA 354-01-E.
- VdS Approved (For details, contact Johnson Controls, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-54-428-3377.)
- Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
- Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers.
- Installed with Style 15 (1/2 in. NPT) 5/8 in. Total Adjustment Recessed Escutcheon, as applicable.
- Installed with Style 20 (1/2 in. NPT) 1/2 in. Total Adjustment Recessed Escutcheon, as applicable.
- Frame and Deflector only. Listings and approvals apply to color (Special Order).
TABLE A
LABORATORY LISTINGS AND APPROVALS FOR 5.6 K-FACTOR SPRINKLERS
Operation
The glass bulb contains a fluid which expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and water to flow.
Design Criteria
The TYCO Series TY-FRB, 5.6 K-factor, Upright (TY313) and Pendent (TY323)
Sprinklers are intended for fire protec-tion systems designed in accordance
with the standard installation rules recognized by the applicable Listing or
Approval agency (such as, UL Listing is based on the requirements of NFPA 13,
and FM Approval is based on the requirements of FM’s Loss Prevention Data
Sheets). Only the Style 15 or Style 20 Recessed Escutcheon is to be used for
recessed pendent installations.
Installation
The TYCO Series TY-FRB, 5.6 K-factor, Upright (TY313) and Pendent (TY323) Sprinklers must be installed in accordance with this section.
General Instructions
Do not install any bulb-type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 in. (1,6 mm) for the 135°F (57°C) and 3/32 in. (2,4 mm) for the 286°F (141°C) temperature ratings. A leak-tight 1/2 in. NPT sprinkler joint should be obtained by applying a minimum to maximum torque of 7 to 14 lb-ft (9,5 to 19,0 N·m). Higher levels of torque can distort the sprinkler Inlet with consequent leakage or impairment of the sprinkler. Do not attempt to compensate for insufficient adjustment in the Escutch-eon Plate by under- or over-tightening the sprinkler. Re-adjust the position of the sprinkler fitting to suit. Upright and Pendent Sprinklers The Series TY-FRB Upright and Pendent Sprinklers must be installed in accordance with the following instructions.
- Step 1. Install Pendent sprinklers in the pendent position. Install upright sprin-klers in the upright position.
- Step 2. With pipe-thread sealant applied to the pipe threads, hand-tighten the sprinkler into the sprinkler fitting.
- Step 3. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench . With reference to , apply the W-Type 6 Sprinkler Wrench to the wrench flats. Torque sprinklers 7 to 14 lb-ft (9,5 to 19,0 N·m).
Recessed Pendent Sprinklers
The Series TY-FRB Recessed Pendent Sprinklers must be installed in accor-dance
with the following instructions.
-
Step A. After installing the Style 15 or Style 20 Mounting Plate over the sprinkler threads, and with pipe-thread sealant applied to the pipe threads, hand-tighten the sprinkler into the sprinkler fitting.
-
Step B. Tighten the sprinkler into the sprinkler fitting using only the W-Type 7 Recessed Sprinkler Wrench .
With reference to Figure 1, apply the W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats. Torque sprinklers 7 to 14 lb-ft (9,5 to 19,0 N·m). -
Step C. After ceiling installation and finishing, slide on the Style 15 or Style 20 Closure over the Series TY-FRB Sprinkler and push the Closure over the Mounting Plate until its flange comes in contact with the ceiling.
Care and Maintenance
The TYCO Series TY-FRB, 5.6 K-factor, Upright (TY313) and Pendent (TY323) Sprinklers must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection systems from the proper authorities and notify all personnel who may be affected by this action. Absence of the outer piece of an escutcheon, which is used to cover a clearance hole, can delay sprinkler operation in a fire situation. The owner must assure that the sprinklers are not used for hanging any objects and that the sprinklers are only cleaned by means of gently dusting with a feather duster; otherwise, non-operation in the event of a fire or inadvertent operation may result. Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or other-wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprinklers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installation Section.) The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Association (e.g., NFPA 25), in addition to the standards of any other authorities having jurisdiction. Contact the installing contractor or product manufacturer with any questions. Automatic sprinkler systems are recommended to be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes.
Limited Warranty
For warranty terms and conditions, visit www.tyco- fire.com.
Ordering Procedure
Contact your local distributor for avail-ability. When placing an order,
indicate the full product name and Part Number (P/N).
Sprinkler Assemblies with NPT Thread Connections
Specify: Series TY-FRB Upright or Pendent (specify) Sprinkler, SIN (specify),
K=5.6, Quick Response, (specify) temperature rating, (specify) finish, P/N
(specify, refer to Table A).
Recessed Escutcheon
Specify: Style 15 Recessed Escutch-eon with (specify) finish, P/N (specify)
Specify: Style 20 Recessed Escutch-eon with (specify) finish, P/N (specify)
- Refer to Technical Data Sheet TFP770
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001
1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone
+1-215-362-0700
© 2018 Johnson Controls. All rights reserved. All specifications and other
information shown were current as of document revision date and are subject to
change without notice.