BLUEDIAMOND ARCTIKBLUE Collect Filter and Pump Condensate Water from Refrigeration Units Instruction Manual

June 10, 2024
BLUEDIAMOND

BLUEDIAMOND-LOGO

BLUEDIAMOND ARCTIKBLUE Collect Filter and Pump Condensate Water from

Refrigeration Units

BLUEDIAMOND-ARCTIKBLUE-Collect-Filter-and-Pump-Condensate-Water-from-
Refrigeration-Units-PRODUCT

Product Information Condensate Removal Pumps – ARCTIKBLUE

The ARCTIKBLUE Condensate Removal Pumps are designed to pump out condensate water that is generated by air conditioning units, refrigeration systems, and dehumidifiers. The pump is equipped with an alarm system that alerts the user in case of power failure, pipe blockages or any other reason that may cause property damage or personal injury. The product comes with installation instructions in multiple languages (English, French, German, Spanish, and Italian) and a warranty of 7 years. The package includes the pump, cables, tubes, and an alarm system. The product must be installed in accordance with national wiring regulations. Caution and warning instructions are provided in the manual to ensure safe usage of the product.

It is important to use the product only for its intended purpose and not to handle it while standing on a wet or damp surface. The installation of cables or tubes should not pose a trip hazard. Servicing and maintenance should be conducted by a suitably trained technician. All condensate tray peripherals must be cleaned thoroughly prior to installation. The alarm system should not be connected to a load higher than 3A, 240V AC/DC. Suitable gloves must be worn while performing servicing/maintenance. The product should not be used with flammable or explosive liquids or in explosive atmospheres. The product must be earthed and relevant mains power supply should be isolated prior to carrying out any electrical work.

Product Usage Instructions

  1. Ensure that the product is used only for its intended purpose.
  2. Do not handle the product while standing on a wet or damp surface.
  3. Install cables or tubes in a way that they do not pose a trip hazard.
  4. Conduct servicing and maintenance by a suitably trained technician.
  5. Clean all condensate tray peripherals thoroughly prior to installation.
  6. Do not connect the alarm system to a load higher than 3A, 240V AC/DC.
  7. Wear suitable gloves while performing servicing/maintenance.
  8. Do not use the product with flammable or explosive liquids or in explosive atmospheres.
  9. Earth the product and isolate relevant mains power supply prior to carrying out any electrical work.
  10. Follow the installation instructions provided in the manual and ensure that the product is installed in accordance with national wiring regulations.
  11. In case of power failure, pipe blockages or any other reason that may cause property damage or personal injury, the alarm system must be used.
  12. If the cord supply is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified person in order to avoid hazard.

The ArctikBlue® is designed to collect, filter and pump condensate water from refrigeration units during daily operation and defrost cycles. The rotary diaphragm pump provides a quiet, reliable and self priming operation.

  • Caution : Use product only for its intended purpose.
  • Caution : Do not handle while standing on a wet or damp surface.
  • Caution : Ensure the installation of cables or tubes do not pose a trip hazard.
  • Caution : Servicing and maintenance to be conducted by suitably trained technician.
  • Caution : All condensate tray peripherals (e.g. collecting elements, connecting tubes and discharge tubes) must be cleaned thoroughly prior to installation.
  • Caution : Do not connect alarm system to a load higher than 3A, 240V AC/DC.
  • Caution : If the cord supply is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified person in order to avoid hazard.
  • Warning : Suitable gloves must be worn while performing servicing/maintenance.
  • Warning : Do not use with flammable or explosive liquids or in explosive atmospheres.
  • Warning : With any installation that may cause property damage or personal injury due to power failure, pipe blockages or for any other reason, the alarm system must be used.
  • Warning : Product must be earthed.
  • Warning : Ensure relevant mains power supply is isolated prior to carrying out any electrical work. The appliance must be installed in accordance with national wiring regulations.

WARRANTY

The ArctikBlue® is manufactured under Charles Austen Pumps strict quality control system. In the unlikely event of failure within 3 years from the date of purchase under normal usage, Charles Austen Pumps will repair the item free of charge subject to the following conditions:

  • Charles Austen Pumps will decline any responsibility if the installation of the pump does not conform to these instructions and specifications.
  • Any modifications to the unit will immediately void the warranty.
  • We reserve the right to alter specifications without prior notice.

IN THE BOX

BLUEDIAMOND-ARCTIKBLUE-Collect-Filter-and-Pump-Condensate-Water-from-
Refrigeration-Units-FIG-1

  1. ArctikBlue® unit.
  2. Pump inlet.
  3. Inlet tubing.
  4. Inlet tubing nut.
  5. Inlet tubing o ring.
  6. Sensor filter.
  7. Filter housing cover.
  8. Pump housing cover.
  9. Alarm cable.
  10. Main cable.

TECHNICAL DATA

PERFORMANCE

  • Flow rate : 50 l/h
  • Pump ON/OFF : 330ml
  • Alarm ON : 3600ml
  • Max capacity : 4.1L
  • Operating temperature range : 5 – 45°C
  • Drain outlet max height : 20m

PHYSICAL

  • Size (excluding fittings) LxWxH: 454x422x64mm
  • Weight (empty): 4.6Kg
  • Inlet fitting : 40mm push fit/solvent weld fitting.
  • Outlet fitting : Ø12mm OD hose tail.

ELECTRICAL

  • Input voltage : 100-240Vac, 50-60 Hz
  • Power : 35-46 W
  • Fuse rating : T2AH250V
  • Max current draw : 0.32A
  • Alarm signal : 0 volt relay.

INSTALLATION

BLUEDIAMOND-ARCTIKBLUE-Collect-Filter-and-Pump-Condensate-Water-from-
Refrigeration-Units-FIG-2 BLUEDIAMOND-ARCTIKBLUE-Collect-Filter-and-
Pump-Condensate-Water-from-Refrigeration-Units-FIG-3

WARING DIAGRAMS

BLUEDIAMOND-ARCTIKBLUE-Collect-Filter-and-Pump-Condensate-Water-from-
Refrigeration-Units-FIG-4

WATER TEST

Following the installation of the ArctikBlue® an operational test must be conducted to ensure correct functionality. To do so, pour approximately 0.5 litres of water into the ArctikBlue® via the inlet tube in order to activate the pump. Ensure free flow of water is achieved through the discharge tube.

The alarm should be linked to a Building Management System or alternative alarm system in order to alert the user of potential hazards. Following installation of the alarm system an operational test must be conducted to ensure correct functionality. To do so, quickly pour approximately 5.0 litres of water into the ArctikBlue® via the inlet tube in order to trigger an alarm condition.

BLUEDIAMOND-ARCTIKBLUE-Collect-Filter-and-Pump-Condensate-Water-from-
Refrigeration-Units-FIG-6

SERVICING

it is the operators responsibility to ensure the ArctikBlue® is maintained to an appropriate service schedule and that the filters are kept clean and free from any blockages.

  1. Remove filter housing cover. Remove screws 1 and 2 only.
  2. Clean filter elements, dispose of waste debris and rinse as necessary.
  3. Clean filter housing using warm soapy water only.
  4. Ensure that there are no blockages or obstructions in the inlet or discharge tubes. Clean as necessary.
  5. Reinstall filter elements.
  6. Reinstall filter housing cover.
  7. Carry out an operational test to ensure correct functionality.

ArctikBlue® pump
Should spares or accessories be required, please contact Charles Austen Pumps or your local ArctikBlue® supplier