SCHIER GB2 Hydromechanical Grease Interceptor Installation Guide

June 11, 2024
SCHIER

SCHIER GB2 Hydromechanical Grease Interceptor Installation Guide

SPECIAL PRECAUTIONS

For Schier Grease Interceptor Installations – Failure to follow this guidance voids your warranty

WARNING: DO NOT AIR TEST UNIT OR RISER SYSTEM!
Doing so may result in property damage, personal injury or death.

CAUTION: Do not install this unit in any manner except as described in these instructions.

Installation Instructions

Installation instructions and additional components are included with the interceptor. Read all instructions prior to installation. This interceptor is intended to be installed by a licensed plumber in conformance with all local codes.
Installation Instructions

When Installing Interceptor Inside

If your dishwashing sink(s) discharges into a floor drain/sink (drain), you must regulate the flow into the drain to avoid an overflow of water  onto the kitchen floor. This canbe done by installing a valve or flow restriction cap on the sink piping that discharges into the drain. See drawing for guidance. For detailed guidance on indirect connections, go to: webtools.schierproducts.com/Technical_Data/Indirect_Connections.pdf
Installation Instructions

Hydrostatic Slabs (or Pressure Slabs)

When installed under a hydrostatic slab (slab designed to withstand upward lift, usually caused by hydrostatic pressure) interceptor must be enclosed in a watertight concrete vault.
Installation Instructions

High Temperature Kitchen Water

If water is entering the interceptor at excessive temperature (over 150º F), a drain water tempering valve (DTV) and approved backflow prevention assembly must be installed. Most state and local plumbing codes prohibit water above 150º F being discharged into the sanitary sewer. Water above 150º F will weaken or deform PVC Schedule 40 pipe, poly drainage fixtures like interceptors and erode the coating of cast iron (leading to eventual failure).

ODOR ALERT!

Do not install air gap on outlet side of interceptor.

Warnings

High Water Table Installations

Interceptors and risers are not designed to withstand water table height in excess of the top of the unit when buried (see figure). If it is possible for this to occur, install the interceptor and risers in a water-tight concrete vault or backfill with concrete or flowable fill (wet concrete and flowable backfill should be poured in stages to avoid crushing the interceptor). At risk areas include but are not limited to tidal surge areas, floodplains and areas that receive storm water. Great Basin™ models that are direct buried in high water table scenarios must be installed with an anchor kit. Models GB-50, GB-75, and GB-250 use model AK1 anchor kit. Model GB-500 uses model AK2 anchor kit for use with deadmen anchors. Models GB-1000, GGI-750 and GGI-1500 use model AK3 anchor kit for use with deadmen anchors.
Installation Instructions

Flush-to-Grade Burials

Flush-to-Grade buried installations (without a riser) are not recommended for heavy foot traffic areas without the use of an internal gusset support kit SGK2 (for GB2) or SGK3 (for GB3).
Flush to Grade Burials

Fully Support Base of Unit

Install unit on solid, level surface in contact with the entire footprint of unit base; for suspended installations design trapeze to support the wet weight of the unit. Do not partially support unit or suspend unit using metal U-channel to create a trapeze.
Installation Instructions

Support Inlet and Outlet Piping

For above grade installations ensure heavy inlet and outlet piping (such as cast iron or long runs) is properly supported or suspended during the entire installation process to prevent connection failure or damage to bulkhead fittings.
Inlet and Outlet Piping

Do Not Icon

GETTING TO KNOW THE GB2

  1. Cover
  2. Standard Installation Flow Control Cartridge
  3. 35 GPM Flow Control Extension (>5′ below kitchen only)
  4. 50 GPM Flow Control Extension (>5′ below kitchen only)
  5. Inlet Diffuser (Top)
  6. Diffuser Retaining Nuts (x2)
  7. 4″ Cleanout Plugs (x2)
  8. Optional Side Outlets 4″ FPT (x2)
  9. Connection Fitting Gaskets (x4)
  10. Bulkhead Connection\ Retaining Nuts (x4)
  11. Inlet 4″ FPT Connection
  12. 3″ Plain End Fittings (x2)
  13. 4″ Plain End Fittings (x2)
  14. Diffuser Foot Retaining Nuts (x2)
  15. Inlet Diffuser (Foot)
  16. Cover Bolts (x4)
  17. Cover Gasket
  18. Air Relief/Visual Access
  19. Outlet 4″ FPT Connection
  20. Outlet Diffuser (Top)
  21. Outlet Diffuser (Foot)

ON THE FLOOR INSTALLATION

Special Precautions

ODOR ALERT!

  1. Do not install air gap on outlet side of interceptor.
    On the Floor Installation

  2. Install interceptor as close as possible to fixtures being served

  3. ODOR ALERT!
    Interceptor is not a sewer gas trap. All upstream fixtures must be trapped
    On the Floor Installation

  4. Provide at least 5-1/2″ clearance above unit for routine maintenance.
    On the Floor Installation

Test Tank for Water Tightness

1a: Cap all connection points with 4″ cleanout plugs using pipe thread sealant or tape approved for use with plastics.

1b: Remove cover and fill with water to just above the highest connection. For riser system testing (if required) fill to finished grade level.

CAUTION: Support risers before filling to prevent tipping. Inspect unit, connections and gaskets for leaks. Check water level at specific time intervals per local code.

Leak?

Call customer
care at 913-951-3300
8a – 5p M – F CST

Set Up Outlet Diffuser and Install Cleanout Plugs

2a: Choose outlet location.
Set Up Outlet Diffuser

Side outlet

OR

Set Up Outlet Diffuserq

Straight-through

2b: Unscrew diffuser retaining nut and remove outlet diffus

2c: Unscrew diffuser foot retaining nut and remove outlet diffuser foot.

2d: Rotate diffuser toward chosen outlet, replace foot ensuring it will point to the back wall of the unit and hand tighten foot retaining nut.
Set Up Outlet Diffuser

2e: Insert diffuser into chosen outlet and hand tighten retaining nut.
Set Up Outlet Diffuser

2f: Cap all unused connection points with 4″ cleanout plugs using pipe thread sealant or tape approved for use with plastics.

Calibrate Flow Control

Note to Plumbing Inspector
This interceptor includes certified internal flow control and does not require a dedicated “Flow Control Vent” (air intake).

Calibrate Flow Control

If dimension
A. 5 feet or less discard red extension parts, then go to Step 4.
If dimension
greater than 5 feet follow Steps below.

Rotate flow control cartidge counter-clockwise to release and remove from inlet diffuser

Depending on which flow rate is desired, attach either the 35 or 50 GPM Flow Control Cartridge Extension using PVC primer/cement. Make sure extension is fully inserted into the cartridge and hold both components firmly together (until cement grabs) to prevent push-out.
Calibrate Flow Control

Calibrate Flow Control
Slide flow control cartridge into top of inlet diffuser and rotate clockwise until cartridge drops onto flow control retainer pins. Continue rotating clockwise until pins are fully seated.

Connect Piping

Connect Piping
Choose inlet and outlet fittings (included) based on pipe size.

4b: Connect piping using pipe thread sealant or tape approved for use with plastics. Ensure all upstream fixtures are trapped. Vent per local code.

4b1: Next to Sink
Connect Piping
4b2: Under Sink

4b3: Floor Below
Connect Piping

Wet or Air Test Piping Per Local Code

WARNING: DO NOT AIR TEST UNIT OR RISER SYSTEM!
Doing so may result in property damage, personal injury or death.

Leak? Call customer care at
913-951-3300
8a – 5p M – F CST

BURIED INSTALLATION

Special Precautions

  1. Install interceptor as close aspossible to fixtures being served

  2. Risers (25″) Max
    Special Precautions

  3. Max Water Level
    Risers are not designed to retain water
    Special Precautions

Test Tank for Water Tightness

1a: Cap all connection points with 4″ cleanout plugs using pipe thread sealant or tape approved for use with plastics.

1b: Remove cover and fill with water to just above the highest connection. For riser system testing (if required) fill to finished grade level.

CAUTION: Support risers before filling to prevent tipping. Inspect unit, connections and gaskets for leaks. Check water level at specific time intervals per local code.

Leak?
Call customer
care at 913-951-3300
8a – 5p M – F CST

Set Up Outlet Diffuser and Install Cleanout Plugs

2a: Choose outlet location.

Side outlet

OR

Set Up Outlet Diffuser
Straight-through

2b: Unscrew diffuser retaining nut and remove outlet diffuser.

2c: Unscrew diffuser foot retaining nut and remove outlet diffuser foot.

2d: Rotate diffuser toward chosen outlet, replace foot ensuring it will point to the back wall of the unit and hand tighten foot retaining nut.

2e: Insert diffuser into chosen outlet and hand tighten retaining nut.

2f: Cap all unused connection points with 4″ cleanout plugs using pipe thread sealant or tape approved for use with plastics.

Calibrate Flow Control

Note to Plumbing Inspector
This interceptor includes certified internal flow control and does not require a dedicated “Flow Control Vent” (air intake).

Calibrate Flow Control

If dimension is
A. 5 feet or less go to Step 4.
If dimension
greater than 5 feet follow Steps below.

Calibrate Flow Control
Rotate flow control cartidge counter-clockwise to release and remove from inlet diffuser

3b: Depending on which flow rate is desired, attach either the 35 or 50 GPM Flow Control Cartridge Extension using PVC primer/cement. Make sure extension is fully inserted into the cartridge and hold both components firmly together (until cement grabs) to prevent push-out.
Calibrate Flow Control

Calibrate Flow Control
Slide flow control cartridge into top of inlet diffuser and rotate clockwise until cartridge drops onto flow control retainer pins. Continue rotating clockwise until pins are fully seated.

3d: OPTIONAL: For easy flow control removal in deep burial installations, 1-1/2″ PVC SCH. 40 pipe may used as an extension handle. Before risers have been installed, cut pipe to length and attach to top of flow control cartridge using PVC primer/cement.

Excavation

Excavate hole 6″ larger than interceptor on all sides.

Add crushed aggregate (approximately 3/4″ size rock or sand, with no fines) to base of hole.

Connect Piping

Floor Sink Installation

If your dishwashing sink(s) discharges into a floor drain/sink (drain), you must regulate the flow into the drain to avoid an overflow of water onto the kitchen floor. This can be done by installing a valve or flow restriction cap on the sink piping that discharges into the drain.

Connect Piping

5a: Choose inlet and outlet fittings (included) based on pipe size.

5b: Set interceptor and connect piping using pipe thread sealant or tape approved for use with plastics. Vent per local code.
Fill tank with water so that it remains in place during backfill.
Connect Piping

Wet or Air Test Piping Per Local Code

WARNING: DO NOT AIR TEST UNIT OR RISER SYSTEM!
Doing so may result in property damage, personal injury or death.

Leak? Call customer care at
913-951-3300
8a – 5p M – F CST

Backfill and Finished Grade

Backfill and Finished Grade
Below Grade with Riser (preferred):
See instructions included with FCR1 riser. Backfill evenly around tank using crushed aggregate (approximately 3/4″ size rock or sand, with no fines), finish with a minimum 4″ thick concrete pad.

Backfill and Finished Grade
Flush-to-Grade Burials:

WARNING: Not recommended for heavy foot traffic areas without the use of an internal support system SGK2 (sold additionally). Contact Customer Care for more details. Backfill evenly around tank using crushed aggregate (approximately 3/4″ size rock or sand, with no fines), finish with a minimum 4″ thick concrete pad.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals