SCHIER GB1 20/25 GPM Grease Interceptor for Indoor Use Installation Guide

June 11, 2024
SCHIER

GB1 20/25 GPM Grease Interceptor for Indoor Use
Installation Guide

GB1 20/25 GPM Grease Interceptor for Indoor Use

SCHIER GB1 20 25 GPM Grease Interceptor for Indoor Use SPECIAL PRECAUTIONS
For Schier Grease Interceptor Installations – Failure to follow this guidance voids your warranty
WARNING   DO NOT AIR TEST UNIT OR RISER SYSTEM!
Doing so may result in property damage, personal injury or death.
Caution
Do not install this unit in any manner except as described in these instructions.

Installation Instructions

Installation instructions and additional components are included with the interceptor. Read all instructions prior to installation. This interceptor is intended to be installed by a licensed plumber in conformance with all local codes. When Installing Interceptor Inside
If your dishwashing sink(s) discharges into a floor drain/sink (drain), you must regulate the flow into the drain to avoid an overflow of water onto the kitchen floor. This can
be done by installing a valve or flow restriction cap on the sink piping that discharges into the drain. See drawing for guidance. For detailed guidance on indirect connections, go to: webtools.schierproducts.com/Technical_Data/Indirect_Connections.pdf Hydrostatic Slabs (or Pressure Slabs)
When installed under a hydrostatic slab (slab designed to withstand upward lift, usually caused by hydrostatic pressure) interceptor must be enclosed in a watertight concrete vault. High Temperature Kitchen Water
If water is entering the interceptor at excessive temperature (over 150º F), a drain water tempering valve (DTV) and approved backflow prevention assembly must be installed. Most state and local plumbing codes prohibit water above 150º F being discharged into the sanitary sewer. Water above 150º F will weaken or deform PVC Schedule 40 pipe, poly drainage fixtures like interceptors and erode the coating of cast iron (leading to eventual failure).
ODOR ALERT!
Do not install air  gap on outlet side of interceptor.SCHIER GB1 20 25 GPM
Grease Interceptor for Indoor Use - Kitchen Water SPECIAL PRECAUTIONS
For Schier Grease Interceptor Installations – Failure to follow this guidance voids your warranty
High Water Table Installations
Interceptors and risers are not designed to withstand water table height in excess of the top of the unit when buried (see figure). If it is possible for this to occur, install the interceptor and risers in a water-tight concrete vault or backfill with concrete or flowable fill (wet concrete and flowable backfill should be poured in stages to avoid crushing the interceptor). At risk areas include but are not limited to tidal surge areas, floodplains and areas that receive storm water. Great Basin™ models that are direct buried in high water table scenarios must be installed with an anchor kit. Models GB-50, GB-75, and GB-250 use model AK1 anchor kit. Model GB-500 uses model AK2 anchor kit for use with deaden anchors. Models GB-1000, GGI-750 and GGI-1500 use model AK3 anchor kit for use with deaden anchors.
Flush-to-Grade Burials
Flush-to-Grade buried installations (without a riser) are not recommended for heavy foot traffic areas without the use of an internal gusset support kit SGK2 (for GB2) or SGK3 (for GB3). Fully Support Base of Unit
Install unit on solid, level surface in contact with the entire footprint of unit base; for suspended installations design trapeze to support the wet weight of the unit. Do not partially support unit or suspend unit using metal U-channel to create a trapeze. Support Inlet and Outlet Piping
For above grade installations ensure heavy inlet and outlet piping (such as cast iron or long runs) is properly supported or suspended during the entire installation process to prevent connection failure or damage to bulkhead fittings.SCHIER GB1 20 25 GPM Grease Interceptor for Indoor Use -
COMPACT GETTING TO KNOW THE GB1SCHIER GB1 20 25 GPM Grease Interceptor for Indoor Use - GETTING TO
KNOW

1. Cover 8. Optional Side Outlets 4″ FPT (x2) 16. Cover Bolts (x4)
2. Standard Installation Flow 9. Connection Fitting Gaskets (x4) 17.

Cover Gasket
4. 25 GPM Flow Control Extension (>5′ below kitchen only)| 10. Bulkhead Connection Retaining Nuts (x4)| 18. Air Relief/Visual Access
5. Inlet Diffuser (Top)| 11. Inlet 4″ FPT Connection| 19. Outlet 4″ FPT Connection
6. Diffuser Retaining Nuts (x2)| 12. 2″ Plain End Fittings (x2)| 20. Outlet Diffuser (Top)
7. 4″ Cleanout Plugs (x2)| 14. Diffuser Foot Retaining Nuts (x2)| 21. Outlet Diffuser (Foot)
13. 3″ Plain End Fittings (x2)| 15. Inlet Diffuser (Foot)|

ON THE FLOOR INSTALLATION

Special Precautions

  1. ODOR ALERT! Do not install air gap on outlet side of interceptor.
  2. Install interceptor as close as possible to fixtures being served
  3. ODOR ALERT! Interceptor is not a sewer gas trap. All upstream fixtures must be trapped
  4. Provide at least 5-1/2″ clearance above unit for routine maintenance.

Test Tank for Water Tightness
Cap all connection points with 4″ cleanout plugs using pipe thread sealant or tape approved for use with plastics. Remove cover and fill with water to just above the highest connection. For riser system testing (if required) fill to finished grade level.
CAUTION: Support risers before filling to prevent tipping. Inspect unit, connections and gaskets for leaks. Check water level at specific time intervals per local code. Leak?
Call customer care at 913-951-3300 8a – 5p M – F CST
Set Up Outlet Diffuser and Install Cleanout Plugs
Choose outlet location.
Side outlet Straight-through Unscrew diffuser retaining nut and remove outlet diffuser. Unscrew diffuser foot retaining nut and remove outlet diffuser foot. Rotate diffuser  toward chosen outlet, replace foot ensuring it will point to the back wall of the unit and hand tighten foot retaining nut.
Insert diffuser into chosen outlet and hand tighten retaining nut. Cap all unused connection points with 4″ cleanout plugs using pipe thread sealant or tape approved for use with plastics.

ON THE FLOOR INSTALLATION

Calibrate Flow Control
SCHIER GB1 20 25 GPM Grease Interceptor for Indoor Use - Calibrate Flow
ControlNote to Plumbing Inspector This interceptor includes certified internal flow control and does not require a dedicated “Flow Control Vent” (air intake).SCHIER GB1 20
25 GPM Grease Interceptor for Indoor Use - Depending oRotate flow control cartidge counter-clockwise to release and remove from inlet diffuser
Depending on which flow rate is desired, attach either the 20 or 25 GPM Flow Control Cartridge Extension using PVC primer/cement. Make sure extension is fully inserted into the cartridge and hold both components firmly together (until cement grabs) to prevent push-out.SCHIER GB1 20 25 GPM Grease
Interceptor for Indoor Use - flow control retainerSlide flow control cartridge into top of inlet diffuser and rotate clockwise until cartridge drops onto flow control retainer pins. Continue rotating clockwise until pins are fully seated.
Connect Piping Choose inlet and outlet fittings (included) based on pipe size.
Connect piping using pipe thread sealant or tape approved for use with plastics. Ensure all upstream fixtures are trapped. Vent per local code. SCHIER GB1 20 25 GPM Grease Interceptor for Indoor Use -
VentWet or Air Test Piping Per Local Code
Warning
DO NOT AIR TEST UNIT OR RISER SYSTEM!
Doing so may result in property damage, personal injury or death.
Leak? Call customer care at 913-951-3300 8a – 5p M – F CST

BURIED INSTALLATION

Special Precautions

  1. Install interceptor as close  as possible to fixtures being served
  2. Risers (25″) Max
  3. Max Water Level Risers are not designed to retain water

Test Tank for Water Tightness
Cap all connection  points with 4″ cleanout plugs using pipe thread sealant or tape approved for use with plastics. Remove cover and fill with water to just above the highest connection. For riser system testing (if required) fill to finished grade level.
CAUTION: Support risers before filling to prevent tipping. Inspect unit, connections and gaskets for leaks. Check water level at specific time intervals per local code. Side outletLeak?
Call customer  care at 913-951-3300 8a – 5p M – F CST
Set Up Outlet Diffuser and Install Cleanout Plugs
Choose outlet location. Side outlet Straight-throughSCHIER GB1 20
25 GPM Grease Interceptor for Indoor Use - Cleanout
Plugs Unscrew diffuser retaining nut and remove outlet diffuser.
Unscrew diffuser foot retaining nut and remove outlet diffuser foot. Rotate diffuser toward chosen outlet, replace foot ensuring it will point to the back wall of the unit and hand tighten foot retaining nut. Insert diffuser into chosen outlet and hand tighten retaining nut. Cap all unused connection points with 4″ cleanout plugs using pipe thread sealant or tape approved for use with plastics.
Calibrate Flow Control
SCHIER GB1 20 25 GPM Grease Interceptor for Indoor Use - Calibrate Flow
Control Note to Plumbing Inspector This interceptor includes certified internal flow control and does not require a dedicated “Flow Control Vent” (air intake). Rotate flow control cartidge counter-clockwise to release and remove from inlet diffuser
Depending on which flow rate is desired, attach either the 20 or 25 GPM Flow Control Cartridge Extension using PVC primer/cement. Make sure extension is fully inserted into the cartridge and hold both components firmly together (until cement grabs) to prevent  push-out. Slide flow control cartridge into top of inlet diffuser and rotate clockwise until cartridge drops onto flow control retainer pins. Continue rotating clockwise until pins are fully seated. OPTIONAL: For easy flow control removal in deep burial installations, 1-1/2″ PVC SCH. 40 pipe may used as an extension handle. Before risers have been installed, cut pipe to length and attach to top of flow control cartridge using PVC primer/cement.
ExcavationSCHIER GB1 20 25 GPM Grease Interceptor for Indoor Use -
ExcavationExcavate hole 6″ larger than interceptor on all sides.
Add crushed aggregate (approximately 3/4″ size rock or sand, with no fines) to base of hole.
Connect Piping
Floor Sink Installation

If your dishwashing sink(s) discharges into a floor drain/sink (drain), you must regulate the flow into the drain to avoid an overflow of water onto the kitchen floor. This can be done by installing a valve or flow restriction cap on the sink piping that discharges into the drain. Choose inlet and outlet fittings (included) based on pipe size. Set interceptor and connect piping using pipe thread sealant or tape approved for use with plastics. Vent per local code. Fill tank with water so that it remains in place during backfill.
Wet or Air Test Piping Per Local Code
Warning:
DO NOT AIR TEST UNIT OR RISER SYSTEM! Doing so may result in property damage, personal injury or death.
Leak? Call customer care at 913-951-3300 8a – 5p M – F CST
Backfill and Finished GradeSCHIER GB1 20 25 GPM Grease Interceptor for
Indoor Use - Backfill and Finished Grade Below Grade with  Riser (preferred): See instructions included with FCR1 riser. Backfill evenly around tank using crushed aggregate  (approximately 3/4″ size rock or sand, with no fines), finish with a minimum 4″ thick concrete pad.
Flush-to-Grade Burials: Not recommended for heavy foot traffic areas. Backfill evenly around tank using crushed aggregate (approximately 3/4″ size rock or sand, with no fines), finish with a minimum 4″ thick concrete pad.

LIFETIME GUARANTEED GREASE INTERCEPTORS
913-951-3300
schierproducts.com
© Copyright 2023 Schier Products Company, 01/01/23