SCHIER GB-500 100 GPM Grease Interceptor Instruction Manual
- June 16, 2024
- SCHIER
Table of Contents
- SPECIAL PRECAUTIONS
- Installation Instructions
- BURIED INSTALLATION
- Test tank for water tightness
- Set Up Outlet Diffuser and Install Cleanout Plugs
- Install Flow Control
- Connect Piping
- Wet or Air Test Piping Per Local Code
- Bring Covers Flush-to-Grade
- Backfill and Finished Grade
- ON THE FLOOR INSTALLATION
- Test tank for water tightness
- Set Up Outlet Diffuser and Install Cleanout Plugs
- Install Flow Control
- UNITS WITH 4″ DIFFUSERS
- Connect Piping
- Install AGS2 Above Grade Support Kit (sold separately)
- Wet or Air Test Piping Per Local Code
- INSTALLATION OPTIONS
- Series Installations
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
**SCHIER GB-500 100 GPM Grease Interceptor Instruction Manual
**
SPECIAL PRECAUTIONS
For Schier Grease Interceptor Installations – Failure to follow this guidance
voids your warranty
WARNING! DO NOT AIR TEST UNIT OR RISER SYSTEM! Doing so may result in
property damage, personal injury or death.
CAUTION! Do not install this unit in any manner except as described in
these instructions.
Installation Instructions
Installation instructions and additional components are included with the interceptor. Read all instructions prior to installation. This interceptor is intended to be installed by a licensed plumber in conformance with all local codes.
**When Installing Interceptor Inside
** If your dishwashing sink(s) discharges into a floor drain/sink (drain), you
must regulate the flow into the drain to avoid an overflow of water onto the
kitchen floor. This can be done by installing a valve or flow restriction cap
on the sink piping that discharges into the drain.
See drawing for guidance. For detailed guidance on indirect connections, go to
:
webtools.schierproducts.com/Technical_Data/Indirect_Connections.pdf
Hydrostatic Slabs (or Pressure Slabs)
When installed under a hydrostatic slab (slab designed to withstand upward
lift, usually caused by hydrostatic pressure) interceptor must be enclosed in
a watertight concrete vault.
**High Temperature Kitchen Water
** If water is entering the interceptor at excessive temperature (over 150º F), a drain water tempering valve (DTV) and approved backflow prevention assembly must be installed. Most state and local plumbing codes prohibit water above 150º F being discharged into the sanitary sewer. Water above 150º F will weaken or deform PVC Schedule 40 pipe, poly drainage fixtures like interceptors and erode the coating of cast iron (leading to eventual failure).
Below Grade Installation Slab Requirements
A concrete slab to finished grade with rebar is required when installing
interceptor below grade.
High Water Table Installations
Interceptors and risers are not designed to withstand water table height in
excess of the top of the unit when buried (see figure). If it is possible for
this to occur, install the interceptor and risers in a water-tight concrete
vault or backfill with concrete or flowable fill (wet concrete and flowable
backfill should be poured in stages to avoid crushing the interceptor).
At risk areas include but are not limited to tidal surge areas, floodplains
and areas that receive storm water. Great Basin™ models that are direct buried
in high water table scenarios must be installed with an anchor kit. Model
GB-500 uses model AK1 anchor kit
**Above Grade Installation Support (for Model GB-500 Only
** The wet weight of the interceptor combined with high temperature kitchen water creates the potential for tank deformation when installed above grade. Model GB-500 installed above grade must be installed with Above Grade Support Kit model AGS2 to maintain structural integrity
Fully Support Base of Unit
Install unit on solid, level surface in contact with the entire footprint of
unit base; for suspended installations design trapeze to support the wet
weight of the unit.
Do not partially support unit or suspend unit using metal U-channel to create
a trapeze.
**Support Inlet and Outlet Piping
** For above grade installations ensure heavy inlet and outlet piping (such as cast iron or long runs) is properly supported or suspended during the entire installation process to prevent connection failure or damage to bulkhead fittings.
DO NOT COMPACT BACKFILL
GETTING TO KNOW THE GB-500
- Pickable Cast Iron Cover (standard)
- Cover Gasket
- Safety Star (x2)
- Safety Star Tether (x2)
- Cover Adapter (x2)
- Cover Adapter Gasket Assembly(x2) with Upper and Lower Stainless
- Steel Band Clamps
- Bulkhead Connection Retaining Nut
- Bulkhead Connection Gasket
- 4″ Cleanout Plug (x2)
- Flow Control Cartridge (>13′ below kitchen only)
- Inlet Diffuser
- Inlet Diffuser Retaining Nut
- Inlet Diffuser Foot Retaining Nut
- Inlet Diffuser (Foot)
- Inlet Bulkhead Connection (standard) 4″ FPT
- 4″ Plain End Fitting (x2)
- 3″ Plain End Fitting (x2) (optional)
- Composite Cover Bolts and Washers (x8)
- Bolted Composite Cover (optional)
- Air Relief/Visual Access
- Outlet Diffuser Retaining Nut
- Outlet Diffuser
- Outlet Bulkhead Connection (optional) 4″ FPT (x2)
- Outlet Bulkhead Connection (standard) 4″ FPT
- 7/16″ Nut Driver Bit
BURIED INSTALLATION
Special Precautions
-
Install interceptor as close as possible to fixtures being served
-
Provide at least 16″ clearance above unit for routine maintenance.
-
-
- Max Water Level
Risers are not designed to retain water
- Max Water Level
-
Test tank for water tightness
Cap all connection points with 4″ cleanout plugs using pipe thread sealant or tape approved for use with plastics.
Remove covers. For base unit testing fill with water to just above the highest
connection.
Inspect unit, connections and gaskets for leaks. Check water level at specific
time intervals per local code.
Leak?
Call customer care at 913-951-3300 8a –
5p M – F CST
Set Up Outlet Diffuser and Install Cleanout Plugs
Remove safety star insert, leave tethered to unit.
Unscrew diffuser retaining nut and remove outlet diffuser.
Rotate diffuser toward chosen outlet, insert and hand tighten retaining nut.
Cap all unused connection points with 4″ cleanout plugs using pipe thread sealant or tape approved for use with plastics.
Install Flow Control
Note to Plumbing Inspector
This interceptor includes certified internal flow control and does not require
a dedicated “Flow Control Vent” (air intake).
Flow control is not pre-installed on this unit.
- If dimension “A” is 13 feet or less no flow control is needed, go to Step 5, Excavate Burial Pit.
- If dimension “A” in Figure 1 is more than 13 feet, or a high flow/increased head pressure condition exists, follow Steps below.
UNITS WITH 4″ DIFFUSERS
Remove safety star insert and remove flow control cartridge from the parts bag
200 GPM Installation Only: Cut off bottom of flow control cartridge at marked line.
Slide flow control cartridge into top of inlet diffuser and rotate clockwise
until cartridge drops onto flow control retainer pins.
Continue rotating clockwise until pins are fully seated.
OPTIONAL: For easy flow control removal in deep burial installations, 1-1/2″ PVC SCH. 40 pipe may used as an extension handle. Before risers have been installed, cut pipe to length and attach to top of flow control cartridge using PVC primer/cement.
OR 35 UNITS WITH 6″ DIFFUSERS
Install flow control plate on the inlet bulkhead fitting prior to
connecting piping and burial. Fasten plate to bulkhead fitting using supplied
screws. Holes in plate must line up with pre-drilled holes in bulkhead fitting
and grooved side of plate must face the unit.
Excavate Burial Pit
Excavate hole at least 18″ larger than interceptor on all sides and 12″ deeper
than tank bottom.
Lay a level bed of well-packed, crushed aggregate (approximately 3/4″ size rock or sand, with no fines) in the base of hole.
Connect Piping
Screw plain end fittings (included) into bulkhead fittings using pipe thread sealant or tape approved for use with plastics. 6″ connection types come pre- installed from the factory.
Lower unit into pit and set level. Mechanically couple inlet and outlet drainage lines to unit. Do not solvent weld. Ensure all upstream fixtures are trapped. Vent per local code. Installation of 2-way cleanout tees to grade (by others) is recommended.
Wet or Air Test Piping Per Local Code
WARNING! DO NOT AIR TEST UNIT OR RISER SYSTEM! Doing so may result in property damage, personal injury or death. Leak? Call customer care at 913-951-3300 8a5p M-F CST
Bring Covers Flush-to-Grade
The GB-500 is ready for burial depth of 49-1/2″ from finished grade to bottom
of tank (or 10-1/2″ to centerline of inlet).
Deeper burials will require extending the Cover Adapters and possibly adding
risers.Measure dimension X to determine riser height needed.
Riser Height Needed | Risers Required |
---|---|
0″ – 4″ | None (use adapter |
>4″ – 34″ | FCR2 (x2) |
>34″ – 64″ | FCR2 (x4) |
>64″ – 94″ | FCR2 (x6) |
Install risers if required (see instructions included with FCR2).
Loosen the Cover Adapter Upper Band Clamp using 7/16″ Nut Driver Bit.
Adjust Cover Adapter heights as needed.
Maintain a minimum 2-1/2″ insertion depth.
Tighten Upper Band Clamp to 5 -8 ft. lbs. of torque using 7/16″ Nut Driver
Bit.
If required, Cover Adapters may now be tilted up to 10º in any direction using
gasket flexibility
Backfill and Finished Grade
Fill unit with water for stabilization and float-out prevention.
Backfill evenly around tank using crushed aggregate (approximately 3/4″ size
rock or sand with no fines)or flowable fill. Do not compact backfill
around unit.
Pour concrete slab to finished grade
8c1
Vehicular Traffic Areas:
Minimum 8″ thick concrete slab with rebar required. Thickness of concrete
around covers to be determined by specifying engineer. If traffic loading is
required the concrete slab dimensions shown are for guideline purposes only.
Concrete to be 28 day compressive strength to 4,000 PSI. Use No. 4 rebar (ø
1/2″) grade 60 steel per ASTM A615: connected with tie wire. Rebar to be
2-1/2″ from edge of concrete and spaced in a 12″ grid with 4″ spacing around
access openings.
Pedestrian Traffic or Greenspace Areas:
Minimum 4″ thick concrete slab with rebar required.
ON THE FLOOR INSTALLATION
Special Precautions
-
ODOR ALERT!
Do not install air gap on outlet side of interceptor -
ODOR ALERT!
Interceptor is not a sewer gas trap.
All upstream fixtures must be trapped -
Install interceptor as close as possible to fixtures being served
-
Provide at least 16″ clearance above unit for routine maintenance.
Test tank for water tightness
Cap all connection points with 4″ cleanout plugs using pipe thread sealant or tape approved for use with plastics.
Remove covers. For base unit testing fill with water to just above the highest
connection.
Inspect unit, connections and gaskets for leaks. Check water level at specific
time intervals per local code.
Leak?
Call customer care at 913-951-3300 8a –
5p M – F CST
Set Up Outlet Diffuser and Install Cleanout Plugs
Choose outlet location.
Remove safety star insert, leave tethered to unit.
Unscrew diffuser retaining nut and remove outlet diffuser.
Rotate diffuser toward chosen outlet, insert and hand tighten retaining nut
Cap all unused connection points with 4″ cleanout plugs using pipe thread sealant or tape approved for use with plastics.
Install Flow Control
Note to Plumbing Inspector
This interceptor includes certified internal flow control and does not require
a dedicated “Flow Control Vent” (air intake).
Flow control is not pre-installed on this unit.
- If dimension “A” is 13 feet or less no flow control is needed, go to Step 5, Connect Piping.
- If dimension “A” in Figure 1 is greater than 13 feet, or a high flow/increased head pressure condition exists, follow Steps below.
UNITS WITH 4″ DIFFUSERS
Remove safety star insert and remove flow control cartridge from the parts bag
200 GPM Installation Only: Cut off bottom of flow control cartridge at
marked line.
Slide flow control cartridge into top of inlet diffuser and rotate clockwise
until cartridge drops onto flow control retainer pins.
Continue rotating clockwise until pins are fully seated.
UNITS WITH 6″ DIFFUSERS
Install flow control plate on the inlet bulkhead fitting prior to connecting piping and burial. Fasten plate to bulkhead fitting using supplied screws. Holes in plate must line up with pre-drilled holes in bulkhead fitting and grooved side of plate must face the unit.
Connect Piping
4″ Plain End
Screw plain end fittings (included) into bulkhead fittings using pipe thread
sealant or tape approved for use with plastics. 6″ connection types come pre-
installed from the factory.
Floor Below Installation Detail
Mechanically couple inlet and outlet drainage lines to unit. Do not
solvent weld. Ensure all upstream fixtures are trapped. Vent per local code.
Install AGS2 Above Grade Support Kit (sold separately)
The wet weight of the interceptor combined with high temperature kitchen water creates the potential for tank deformation when installed above grade. Model GB-500 installed above grade must be installed with Above Grade Support Kit model AGS2 to maintain structural integrity. Refer to installation instructions included with AGS2.
Wet or Air Test Piping Per Local Code
WARNING! DO NOT AIR TEST UNIT OR RISER SYSTEM!
Doing so may result in property damage, personal injury or death.
Leak? Call customer care at
913-951-3300
8a – 5p M – F CST
INSTALLATION OPTIONS
High Water Table Installations, See Anchor Kit Model AK2
Deadmen Anchoring:
If the installation location is in a high water table area or at risk are
(including but not limited to tidal surge areas, floodplains and areas that
receive storm water) the GB-500 must be secured to concrete deaden anchors (by
others) using Schier model AK2 anchor kit.
Series Installations
For lower flow rates and higher grease storage requirements. Piping between
units and two-way cleanout tees by others.
Below grade installations: All units must be level in the excavation pit.
Note that downstream units must be buried 2″ deeper than the adjacent,
upstream fixture. Two-way cleanout tees extended to finished grade should be
installed before the first unit inlet, after the last unit outlet and in
between units (if there is a long run of pipe between units) for line cleaning
purposes.
NOTE: When the flow control cartridge is required, it should only be
installed on the first unit in the series.
Top View of 4 GB-500 Units Piped in Series
Side View of 3 GB-500 Units Piped in Series
No. of Units in Series | Removal Efficiency |
---|
100 GPM
95.3%
2| 6,096 lbs
3| 9,144 lbs.
4| 12,192 lbs.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>