Lumineux 421309 Woodhead Emergency Downlight Open Area and Corridor Instruction Manual

June 11, 2024
Lumineux

Lumineux 421309 Woodhead Emergency Downlight Open Area and Corridor

Lumineux-421309-Woodhead-Emergency-Downlight-Open-Area-and-Corridor-
product

Product Information

Woodhead Emergency Downlight Open Area and Corridor

  • IP20 6000K
  • 35mm
  • Self-Test
  • 2-year Battery Warranty
  • 5-year Warranty

The Woodhead Emergency Downlight is a lighting fixture designed for open areas and corridors. It has an IP20 rating and emits a 6000K light. It comes with a self-test feature and a 2-year battery warranty, as well as a 5-year warranty for the fixture itself. The dimensions of the downlight are 40mm x 40mm x 21mm and it weighs 0.3kg.

Product Usage Instructions

IMPORTANT: This product must be installed by a qualified electrician or competent person, and in accordance with current building and IET wiring regulations.

Box Contents and Tools Required

Before commencing with the installation, carefully inspect the luminaire to confirm there is no damage. DO NOT INSTALL if any damage has occurred to the fixture or any of its components.

  • Electrical connection wiring
  • Mains input
  • N – NEUTRAL = Blue
  • L – SWITCHED LIVE = Brown

Terminal block not supplied.

Product Installation Instructions

  1. Disconnect mains supply.
  2. Connect battery and LED pin spot to emergency pack.
  3. Connect Live (L) and Neutral (N) from emergency pack to mains input as shown (4).
  4. Place battery and emergency pack into ceiling and using fixing levers fit LED pin spot into desired hole.
  5. Reconnect mains supply when deemed safe.

Disposal

Disassembly instructions for end of life disposal are available on the website.

Product Warranty

This luminaire is warranted for a period of 5 years from the date of purchase. The backup battery pack in the emergency version is warranted for a period of 24 months. The warranty could be invalidated should the light fitting not be installed according to these instructions, outside the scope of the specification or the product has been altered or tampered with in any way. Please see website for terms and conditions.

Product Temp Specification

Revision 2 – September 2022

Wiring Instructions for Units Equipped with EMERGENCY Function

Emergency lighting luminaries must be installed and maintained in accordance with the emergency lighting standard BS 5266-1. For the emergency unit to work correctly, please ensure that an uninterrupted permanent live feed is present and is connected directly to the ‘Permanent Live’ terminal of the mains terminal block. Please ensure there are no switches, PIRs etc within the permanent live feed, constant switching of the emergency pack could result in premature battery failure.

READ THESE INSTRUCTIONS THOROUGHLY BEFORE INSTALLATION KEEP THESE INSTRUCTIONS FOR FUTURE REFERENCE.
IMPORTANT:
This product must be installed by a qualifi ed electrician or competent person, and in accordance with current building and IET wiring regulations.

BOX CONTENTS

This lighting fi xture has been properly packed to avoid damage during transit. Before commencing with the installation carefully inspect the luminaire to confi rm there is no damage. DO NOT INSTALL if any damage has occurred to the fi xture or any of its components.

  • Woodhead Emergency
  • Instruction Manual

TOOLS REQUIRED

  1. Hole Saw
  2. Screwdriver
  3. Cable

INSTALLATION INSTRUCTIONS

Lumineux-421309-Woodhead-Emergency-Downlight-
Open-Area-and-Corridor-fig 1 Lumineux-421309-Woodhead-Emergency-Downlight-
Open-Area-and-Corridor-fig 2

PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLATION.

WARNING: Risk of electric shock! Isolate the mains power before proceeding.

  • Turn off the mains power before performing inspections, installation, or removal
  • Verify that the supply voltage is correct by comparing it with the luminaire label information
  • It is the installers responsibility to ensure installation is suitable for the total load of the luminaire(s). The supply cable, fuses/circuit brakers must be correctly rated for the electrical load and considering for any transient inrush currents that may occur
  • Do not perform insulation strength or resistance tests on installed luminarie(s) connected
  1. Disconnect mains supply
  2. Using Ø35mm hole saw, cut hole in required ceiling location
  3. Connect battery and led pin spot to emergency pack
  4. Connect Live (L) and Neutral (N) from emergency pack to mains input as shown (4). Terminal block not supplied
  5. Place battery and emergency pack into ceiling and using fi xing levers fi t LED pin spot into desired hole
  6. Reconnect mains supply when deemed safe

DISPOSAL

Disassembly instructions for end of life disposal available on website.
Disposal of Electronic Equipment WEEE Directive 2002/96/EC This product falls within the scope of the Waste Electrical & Electronic Equipment Directive (WEEE), which means the product should not be disposed of as normal household waste. Please recycle where facilities exist or check with your Local Authority. RoHS – All components and materials used in this product are RoHS 2002/95/EC compliant.
Specifications may change from time to time. The information contained in this leaflet is for guidance only and should not be considered as always accurate and should be treated as not representative.

WARRANTY

This luminaire is warranted for a period of 5 years from the date of purchase**. The backup battery pack in the emergency version is warranted for a period of 24 months. The warranty could be invalidated should the light fitting not be installed according to these instructions, outside the scope of the specification or the product has been altered or tampered with in any way. Please see website for terms and conditions.

PRODUCT TEMP SPECIFICATION

Emergency 0 to +30ºC

WOODHEAD EMERGENCY DIMENSIONS

Part No. Description Watts L (mm) W (mm) H (mm) Weight

421307

| Woodhead Emergency Downlight Open Area – White|

3W

|

40

|

40

|

21

|

0.3Kg

421308

| Woodhead Emergency Downlight Open Area Self-Test – White|

3W

|

40

|

40

|

21

|

0.3Kg

421309

| Woodhead Emergency Downlight Corridor – White|

3W

|

40

|

40

|

21

|

0.3Kg

421310

| Woodhead Emergency Downlight Corridor Self-Test – White|

3W

|

40

|

40

|

21

|

0.3Kg

Wiring instructions

Wiring instructions for units equipped an with EMERGENCY function

Emergency lighting luminaries must be installed and maintained in accordance with the emergency lighting standard BS 5266-1

  1. For the emergency unit to work correctly, please ensure that an uninterrupted permanent live feed is present and is connected directly to the ‘Permanent Live’ terminal of the mains terminal block. Please ensure there are no switches, PIRs etc within the permanent live feed, constant switching of the emergency pack could result in premature battery failure.
  2. Following power up the green LED indicator should illuminate to indicate charging. If power to the unit is disrupted or isolated, the unit indicating green LED will switch off, triggering the emergency LEDs to illuminate.

Installation Engineers Contact Details:| Luminaire Reference / Location
---|---
Name:| Tel:|
Luminaire Details:| Full Recharge Duration 24 Hours| Emergency Duration 3 Hours| Lamp Type LED
---|---|---|---
ROUTINE TEST RECORD

Type Test| Year 1| Year 2| Year 3| Year 4| Year 5
| Signed| Date| Signed| Date| Signed| Date| Signed| Date| Signed| Date
Functional 1| | | | | | | | | |
Functional 2| | | | | | | | | |
Functional 3| | | | | | | | | |
Functional 4| | | | | | | | | |
Functional 5| | | | | | | | | |
Functional 6| | | | | | | | | |
Functional 7| | | | | | | | | |
Functional 8| | | | | | | | | |
Functional 9| | | | | | | | | |
Functional 10| | | | | | | | | |
Functional 11| | | | | | | | | |
3hr Duration 12| | | | | | | | | |

** Please see our website for more detailed information on warranty.

Self-Test EMERGENCY function

The self-test version of emergency is fitted with control gear that will carry out periodic functional tests every 1 month and full duration test every 12 months.

LED Status LED Status

Mains On / No Fault

|
| Slow Flash| Function test for 2 minutes
Fast Flash| 3 hour duration test
| 1 Flash| Battery Fault
2 Flash| Lamp Fault
3 Flash| Duration Test Fault

Technical Helpline: +44 (0)1507 328031