Lumineux 3CCT Rutland Bulkhead Instruction Manual

June 9, 2024
Lumineux

Lumineux LOGO

Lumineux 3CCT Rutland Bulkhead

Lumineux 3CCT Rutland Bulkhead Instruction-
PRODUCT

Rutland 3CCT Bulkhead

The Rutland 3CCT Bulkhead is an IP65 rated lighting fixture that comes with a 5-year warranty. It has a 12W power consumption and a BESA mount. The luminaire is designed to provide high-quality lighting output and has an Lm/W rating based on 4000K output.

Installation Instructions

Before installation, carefully inspect the luminaire to ensure there is no damage. Do not install if any damage has occurred to the fixture or any of its components. The product must be installed by a qualified electrician or competent person in accordance with current building and IET wiring regulations.Lumineux 3CCT Rutland Bulkhead Instruction-
FIG-1

Box Contents

The box contains the Rutland Bulkhead, Geartray, Twist-lock, Electrical connection wiring, and Grommet. This lighting fi xture has been properly packed to avoid damage during transit. Before commencing with the installation carefully inspect the luminaire to confi rm there is no damage. DO NOT INSTALL if any damage has occurred to the fi xture or any of its components.

  • Light Fitting
  • Instruction Manual

Tools Required

The tools required for installation are a drill, appropriately sized drill bits, and a screwdriver.

  • Drill
  • Screwdriver
  • Cable

Instructions

  1. Isolate the mains power before proceeding.
  2. Remove the diffuser by gently twisting anti-clockwise.
  3. Twist the locking tab to loosen and remove the geartray.
  4. Drill appropriately sized holes through your chosen mounting points in the base.
  5. Install grommet to your chosen cable entry and pierce, making a hole just large enough to make a tight fit around the incoming mains cable. Carefully thread cable through grommet.
  6. Secure the fitting in place. Note: If protection against ingress of moisture is required, the heads of screws must be covered with a silicone or similar sealant.
  7. Wire as per diagram (5).
  8. Replace the geartray and twist the locking tab to secure in place, then refit the diffuser.
  9. Reconnect the mains supply.

Disposal

The light source of this unit is not replaceable; when the light source reaches its end of life, the whole luminaire shall be replaced. Disassembly instructions for end-of-life disposal are available on the website. The light source of this unit is not replaceable; when the light source reaches its end of life the whole luminaire shall be replaced.
Disassembly instructions for end of life disposal available on website. Disposal of Electronic Equipment WEEE Directive 2002/96/EC This product falls within the scope of the Waste Electrical & Electronic Equipment Directive (WEEE), which means the product should not be disposed of as normal household waste. Please recycle where facilities exist or check with your Local Authority. RoHS – All components and materials used in this product are RoHS 2002/95/EC compliant. Specifications may change from time to time. The information contained in this leaflet is for guidance only and should not be considered as always accurate and should be treated as not representative.

Microwave Sensor Settings

Hold Time Duration: This determines the time the fitting remains at 100% illumination following motion detection. Daylight Setting: This setting holds off the 100% light output should there be sufficient daylight. Detection Range: This determines the effective range of the motion. Note that reducing the sensitivity will also narrow the detection range.

Rutland Bulkhead Dimensions

The Rutland Bulkhead has a standard product temp specification and is revision 2 – March 2022.

Warranty

This luminaire is warranted for a period of 5 years from the date of purchase**. The backup battery pack in the emergency version is warranted for a period of 12 months. The warranty could be invalidated should the light fitting not be installed according to these instructions, outside the scope of the specification or the product has been altered or tampered with in any way. Please see the website for terms and conditions. The luminaire is warranted for a period of 5 years from the date of purchase. The backup battery pack in the emergency version is warranted for a period of 12 months. The warranty could be invalidated should the light fitting not be installed according to these instructions, outside the scope of the specification or the product has been altered or tampered with in any way. Please see website for terms and conditions.

PRODUCT TEMP SPECIFICATION

  • Standard -20 to +40ºC
  • Emergency 0 to +30ºC
  • Revision 2 – March 2022

MICROWAVE SENSOR SETTINGS

Detection Range: This determines the effective range of the motion. Note that reducing the sensitivity will also narrow the detection range.
Hold Time Duration: This determines the time the fitting remains at 100% illumination following motion detection.
Daylight Setting: This setting holds off the 100% light output should there be sufficient daylight.

STANDARD ON/OFF SENSORLumineux 3CCT Rutland Bulkhead Instruction-
FIG-3

RUTLAND BULKHEAD DIMENSIONS

STEP DIM DRIVER SETTINGS

Lumineux 3CCT Rutland Bulkhead Instruction-
FIG-5

ROUTINE TEST RECORD

Lumineux 3CCT Rutland Bulkhead Instruction-
FIG-6EMERGENCY FITTINGS ONLY. EARTH CONNECTION REQUIRED.

Wiring instructions for units equipped an with EMERGENCY function

Emergency lighting luminaries must be installed and maintained in accordance with the emergency lighting standard BS 5266-1

  1. Connect incoming earth cable to ‘Earth’ terminal on connector block.

  2. Connect incoming neutral cable to ‘Neutral’ terminal on connector block.

  3. For the emergency unit to work correctly, please ensure that an uninterrupted permanent live feed is present and is connected directly to the ‘Permanent Live’ terminal of the mains terminal block. Please ensure there are no switches, PIRs etc within the permanent live feed, constant switching of the emergency pack could result in premature battery failure.

  4. Connect incoming switched live cable to the terminal marked “Switched Live”
    NOTE: If there is no switch live feed and the unit has a microwave sensor, simply bridge across from the “Permanent Live” to the Switch Live” on the mains terminal block.

  5. There should be a loose flying lead connected to the battery. This needs to be attached to the flying lead from the emergency control unit.

  6. Following power up the green LED indicator should illuminate to indicate charging. If power to the unit is disrupted or isolated, the unit indicating green LED will switch off, triggering the emergency LEDs to illuminate.

  7. Please allow 24 hours charge before first emergency test.
    EMERGENCY FITTINGS ONLY. EARTH CONNECTION REQUIRED.Lumineux 3CCT Rutland
Bulkhead Instruction-FIG-7

Self-Test EMERGENCY function
The self-test version of emergency is fitted with control gear that will carry out periodic functional tests every 1 month and full duration test every 12 months.Lumineux 3CCT Rutland Bulkhead Instruction-
FIG-8

This product contains a light source of energy efficiency Class F.

STOP: READ THESE INSTRUCTIONS THOROUGHLY BEFORE INSTALLATION KEEP THESE INSTRUCTIONS FOR FUTURE REFERENCE.

IMPORTANT:
This product must be installedby a qualifi ed electrician or competent person, and in accordance with current building and IET wiring regulations.

PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLATION.

WARNING: Risk of electric shock! Isolate the mains power before proceeding.

  • Turn off the mains power before performing inspections, installation, or removal
  • Verify that the supply voltage is correct by comparing it with the luminaire label information
  • It is the installers responsibility to ensure installation is suitable for the total load of the luminaire(s). The supply cable, fuses/circuit brakers must be correctly rated for the electrical load and considering for any transient inrush currents that may occur
  • Do not perform insulation strength or resistance tests on installed luminarie(s) connected
  1. Remove the diffuser by gently twisting anti-clockwise
  2. Twist the locking tab to loosen and remove the geartray
  3. Drill appropriately sized holes through your chosen mounting points in the base
  4. Install grommet to your chosen cable entry and pierce, making a hole just large enough to make a tight fi t around the incoming mains cable. Carefully thread cable through grommet
  5. Secure the fi tting in place. Note: If protection against ingress of moisture is required the heads of screws must be covered with a silicone or similar sealant
  6. Wire as per diagram (5)
  7. Please see overleaf for instructions on how to set all sensor versions
  8. Replace the geartray and twist the locking tab to secure in place, then refi t the diffuser
  9. Re-connect the mains supply

Technical Helpline: +44 (0)1507 328031
Manby Business Park,
Manby, Lincolnshire,
LN11 8UT Lumineux is a B&T Associates Ltd company.
www.lumineux.co.uk

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Lumineux User Manuals

Related Manuals