Schneider Electric CDXAE12016 MCCB 16 Amp Triple Pole 3 Phase 16A CDX Range Instruction Manual

June 11, 2024
Schneider Electric

CDXAE12016 MCCB 16 Amp
Triple Pole 3 Phase 16A CDX Range
Instruction Manual

CDXAE12016 MCCB 16 Amp Triple Pole 3 Phase 16A CDX Range

Before Installing I-Line MCCB’s disconnect all power to the panel board

  1. Align I-Line MCCB with busbar ensuring the guide boss on the MCCB aligns with the groove on the busbar shroud
  2. Place screwdriver through rectangular hole (see picture) in the mounting bracket; using the slots in the panelboard mounting pan firmly ratchet the MCCB into place
  3. Tighten clamping screw do not over tighten such that mounting is deformed. Recommended torque 1.5Nm.

Schneider Electric CDXAE12016 MCCB 16 Amp Triple Pole 3 Phase 16A CDX
Range I-Line MCCB Removal
Reverse the fitting procedure taking care to ensure the clamping bolt is clear of the plan assembly.
If a new MCCB is not being fitted the space should be filled with HNM-1BL or HNM-4BL banking plates.

Safety

The equipment must be installed and maintained by competent personnel in accordance with the appropriate statutory regulations and codes of practice e.g. Electricity at Work Regulations, IEE.
Wiring regulations (BS7671) Etc.
Ensure the source is isolated elsewhere, locked off and labelled prior to work being carried out on the board.
It is the responsibility of the installer to ensure that all electrical connections are tight and satisfactory earth continuity has been achieved.
Following completion of installation these instructions should be left with the equipment/end user.
Warning

  • Do not adjust plug on jaws or remove the joint compound for them.
  • Mount main circuit breaker adjacent to main lugs
  • Clearly identify when used as an incomer on Size 1 Panelboard

I-Line MCCB Product Selector Table

Outgoing Device 1 Pole

16-100 Icu= 25 kA @ 240 V AC Single Pole 1 Mod
L1
16A CDXAE12016
20A CDXAE12020
25A CDXAE12025
30A CDXAE12030
40A CDXAE12040
50A CDXAE12050
63A CDXAE12063
80A CDXAE12080
100A CDXAE12100
Triple Pole (3 Mods) Additional tunnel terminals

cable**
---|---|---
| 25kA| 36kA| 50kA| |
16A| CDXAE34016| CNXAE34016| CHXAE34016| LV429242| 1.5 – 95MM
25A| CDXAE34025| CNXAE34025| CHXAE34025
32A| CDXAE34032| CNXAE34032| CHXAE34032
40A| CDXAE34040| CNXAE34040| CHXAE34040
50A| CDXAE34050| CNXAE34050| CHXAE34050
63A| CDXAE34063| CNXAE34063| CHXAE34063
80A| CDXAE34080| CNXAE34080| CHXAE34080
100A| CDXAE34100| CNXAE34100| CHXAE34100
125A| | CNXAE34125| CHXAE34125
160A| CNXAE34160| CHXAE34160
200A| CNXAE32400| CHXAE34200| LV429259| 95 – 185MM
250A| CNXAE34250| CHXAE34250| LV429259
| | | |
| | |
| | |
160A (elec)| | CNXAE34160E20| | LV429242| 1.5 – 95mm
250A (elec)| CNXAE34250E20| LV429259| 95 – 185mm
| | |

Health and Safety at Work, etc Act 1974
To ensure that the equipment described is safe for both personnel and property it should be installed, commissioned and maintained by or under the supervision of qualified persons. Regard should be taken of BS7671, Codes of practice, statutory requirements and specific
Instructions issued by Schneider Electric. Any operating or installation queries relating to these products should be communicated directly to Schneider Electric.

Schneider Electric Limited
Stafford Park 5
Telford
TF3 3BL
Tel: 0870 608 8 608
Fax: 0870 608 8 606
www.schneider-electric.co.uk

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Schneider Electric User Manuals

Related Manuals