SMART APP ONLINE
UPS SYSTEM
INSTALLATION AND OPERATION MANUAL
BP192VL2U01
BP192VL2U01 Smart App Online UPS System
SAVE THESE INSTRUCTIONS
Please read this manual and follow the instructions for installation and
operation.
©2022 Cyber Power Systems (USA), Inc. All rights reserved. All other
trademarks are the property of their respective owners.
SAFETY INSTRUCTIONS
PRODUCT SAFETY
CAUTION
** To reduce the risk of fire, connect the EBM AC input to a branch circuit
with 20 amperes maximum overcurrent protection in accordance with the National
Electric Code, ANSI/NFPA 70.
A battery can present a risk of electric shock and high short circuit current.
The following precaution should be observed when working on batteries:
Remove watches, rings or other metal objects.
Use tools with insulated handles.
Wear rubber gloves and boots.
Do not lay tools or metal parts on top of batteries.
Disconnect the AC power prior to connecting or disconnecting terminals.
Ensure the ground terminal is disconnected during installation and maintenance
to reduce likelihood of shock. If battery is installed and grounded,
disconnected the ground terminal before working on the UPS.
RISK OF ELECTRIC SHOCK
See Installation Instructions Before Connecting To The Supply. Do Not
Disconnect Battery Connector Under Load.
Batteries replaceable by SERVICE PERSONNEL.
BATTERY
** Do not dispose of batteries in fire as the battery may explode.
Do not open or mutilate the battery, released electrolyte is harmful to the
skin and eyes.
INTRODUCTION
UPS EXTENDED BATTERY MODULES
Extended Battery Modules (EBMs) from CyberPower (BP192VL2U01) increase battery
runtimes during power outages. Each rack/tower convertible EBM uses 2U of rack
space and can be installed in a tower form factor to match the UPS
installation. The DC plug-and-play power connectors allow to daisy-chain
additional EBMs to a UPS system. EBMs compatible with Smart App Online UPS
systems also have a built-in battery charger, providing Fast Charge Technology
to quickly restore the backup power supply. Every CyberPower EBM has a three-
year warranty.
UNPACKING PROCEDURES
** Information, advice, help
The Extended Battery Module is very heavy, please handle with care. Wear
safety shoes and use a hydraulic equipment lift if one is available. At least
two people are required for all handling operations, including unpacking,
lifting, and installation in a rack system. Do not use the lifting straps to
carry the unit around; they are provided to manually unpack the unit only.
USE LIFTING STRAPS TO REMOVE THE UNIT FROM THE BOX. WHAT’S IN THE BOX**
ITEM | CONTENT | QTY |
---|---|---|
1 | EBM | 1 |
2 | Front panel | 1 |
3 | IEC320 C14 to IEC320 C13 power cord | 1 |
4 | NEMA L6-20P to IEC320 C13 power cord | 1 |
5 | BM Cable | 1 |
6 | BMP Cable | 1 |
7 | DC Power Core | 1 |
8 | Rackmount left rail | 1 |
9 | Rackmount right rail | 1 |
10 | Left hanging bracket | 1 |
11 | Right hanging bracket | 1 |
12 | Installation and Operation Manual | 1 |
13 | Registration warranty card | 1 |
14 | Rackmount ears | 2 |
15 | Flat head screws M5X7L | 8 |
16 | Pan head screws M5X8L | 12 |
17 | Pan head screws M5X6L | 6 |
18 | Plastic washers | 8 |
19 | Screw hole dust covers | 18 |
20 | Rubber pads | 12 |
21 | Stand | 2 |
22 | Tie plate | 1 |
EXTENDED BATTERY MODULE INSTALLATION
BATTERY MODULE BP192VL2U01
-
BP192VL2U01 EBM DC Input Connector
Connect to the UPS or to the other Extended battery modules -
BM Ports
Connection port for built-in battery management module on UPS and Extended Battery Module. -
BMP Connectors
BMP connector for built-in battery management module on UPS and Extended Battery Module. -
DC Breaker
Use the DC breaker to disconnect battery output. -
AC Fast Charge outlet (IEC320 C13)
Use this outlet to connect to the Fast Charge AC input of a downstream EBM. -
AC Fast Charge Input (IEC320 C14)
Connect to a 208V, 20A, AC power source, or connect to the AC Fast Charge output from an upstream EBM. -
AC Circuit Breaker
Provides overload and fault protection.
CONNECTION WITH UPS
Scenario #1: UPS with one Extended Battery Module (EBM) Step 1: Turn off the DC breaker on the EBM.
Step 2: Loosen the two screws to remove the battery cable retention
bracket of the UPS.
Step 3: Use the output cable of the EBM to connect the EBM to the UPS.
Step 4: Rotate the battery cable
retention bracket and tighten the two screws to fix battery cable.
Step 5: Connect the BM/ENV port from UPS rear panel to BM port marked
“IN” on the rear panel of the Extended Battery Module using the provided BM
cable. Refer to illustration below.
Step 6: Connect the BMP connector from UPS rear panel to left side BMP
connector on the rear
panel of the Extended Battery Module using the provided BMP cable. Refer to
illustration below.
Step 7: Use a NEMA L6-20P to IEC-320-C13 power cord to plug AC input
inlet of the battery module into a wall receptacle.
Step 8: Turn on the DC breaker of the EBM.
Scenario #2: UPS with multiple Extended
Battery Modules (EBMs) Step 1: Turn off the DC breaker on
the EBM.
Step 2: Loosen the two screws to remove the battery cable retention
bracket of the UPS.
Step 3: Use the output cable of the EBM to connect the EBM to the
UPS. Step 4: Rotate the battery cable
retention bracket and tighten the two screws to fix battery cable.
Step 5: Connect the BM/ENV port from UPS rear panel to BM port marked
“IN” on the rear panel of the Extended Battery Module using the provided BM
cable, and then connect another BM cable between BM port marked “OUT” and BM
port marked “IN” of another Extended Battery Module. Refer to illustration
below.
Step 6: Connect the BMP connector from UPS rear panel to left side BMP
connector on the rear panel of the Extended Battery Module using the provided
PMP cable, and then connect another BMP cable, between BMP connector and right
side BMP connector of next Extended Battery Module.Refer to illustration
below.
Step 7: Use a NEMA L6-20P to IEC-320-C13 power cord to plug AC input
inlet of the battery module into a wall receptacle.
Step 8: Turn on the DC breaker of the EBM. Step 9: Turn on the DC breaker of the 2nd EBM.
Step 10: Set the EBM number to the respective setting to match the number
of installed units. To do this via the LCD control panel, go to the
Configuration Menu, then scroll to the EBM Number setting, select the
appropriate number and Save the configuration. This operation can also be done
via the RMCARD web UI or via PowerPanel® Business software. Please see their
respective User Manual for instructions.
EXTENDED BATTERY MODULES CONFIGURATION
Extended Battery Modules can be configured by the user to display correct
estimated battery runtimes.
-
Select “Main Menu” and press the “ENTER” button to activate the “Main Menu”.
-
Press the “UP” and “DOWN” buttons to select the “SET UP” ICON.
-
Press the “ENTER” button to enter the “SET UP” function.
-
Press the “UP” and “DOWN” buttons to scroll to the “External Batt” option.
-
Press the “ENTER” button to enter the “External Batt” option.
-
Press the “UP” and “DOWN” buttons to select the “Auto” or “Manual” option.
-
(a) Select “Auto” and press the “ENTER” buttons to activate the Auto detect function.
(b) Select “Manual” and press the “UP” and “Down” buttons to select the number of EBM installed then press the “ENTER” button to set. -
You may be prompted “Save Change?” to save the selection, if so press the “ENTER” button to save the setting.
-
Press the “ESC” button to cancel or return to the previous SET UP menu.
SET UP ITEMS| AVAILABLE SETTINGS| DEFAULT
SETTINGS
---|---|---
External Batt| Auto| If UPS has EOM function, the UPS will Auto detect the
external batt number.| None
Manual| = [0] [1] [2] [3] [4] [5] [6] [7] [8] [9] [10] Sets the actual EBM
(extended battery modules) number to get the correct estimated runtime.| 0
HARDWARE INSTALLATION
CyberPower Extended Battery Module (EBM) can be installed in a rackmount or
vertical/tower orientation. This versatility is especially important to
growing organizations with changing needs that value having the option to
position an EBM on the floor or in a rackmount system. Note that the included
rack mounting hardware is only compatible with square hole racks. Please
follow the instructions below for the respective mounting methods.
RACKMOUNT INSTALLATION FOR 4-POST RACK
Caution: Important Instructions
To prevent the risk of fire or electric shock, only use the supplied hardware
to attach the mounting brackets.
Step 1: Remove the dust covers
Remove ten dust covers from the screw holes as shown below.
Step 2: Rackmount ear & hanging bracket installation
Attach two rackmount ears to the EBM using eight black M5X7L flat head screws
and tighten two hanging brackets using six silver M5X6L pan head
screws. Step 3: Rackmount rail
Installation
The mounting depth of the included rackmount rails can adjust from 20.5 in to
36 in (52 cm to 91.5 cm). Select the proper holes in the rack for positioning
the EBM in the rack. The EBM takes up 2 rack units: rack hole positions 1
through 6.
Position the guide screws on the back of the rackmount rails into the rear
rack square holes to temporarily support the rails in place.
Step 4: Adjust rackmount rails to fit your rack
Adjust the rail depth to match your rack depth. Attach each rackmount rail to
your rack with two black M5X8L pan head screws and two plastic washers at the
front of the rack (square holes 1 and 4 as shown below). Secure each rail to
the rear of the rack with two black M5X8L pan head screws and two plastic
washers Step 5: Place and secure the EBM on
the rails
Slide the hanging brackets on the EBM on to the rails mounted in the rack with
the front of the unit facing toward you. Secure the EBM to your rack with four
black M5X8L pan head screws at the front of the rack (square holes 2 and 5 as
shown above).
NOTE: To slide the EBM out from the rack
The EBM will be secured by a safety locking mechanism midway of pulling it out
of the rack. Use both hands to hold the EBM and press the safety locking tab
to pull the EBM out. RACKMOUNT INSTALLATION FOR 2-POST
RACK
CAUTION! Due to the weight of this unit, it is strongly recommended to
install it at the bottom of the rack.
CAUTION! Prior to installing the unit, remove internal batteries to
reduce the weight of the unit. Refer to the battery replacement section in
this user manual for instructions.
CAUTION! It is strongly recommend having 2-3 people assist during the
installation process.
CAUTION! It is strongly recommended that the 2 post rack be bolted to the
floor prior to the installation of the EBM.
Step 1: Remove side dust covers
Remove seven dust covers from screw holes as shown below.
Step 2: Rackmount ears installation
Attach the included rackmount ears to the center holes on the sides of the EBM
using eight black M5X7L screws as shown below.
Step 3: Secure the EBM to the rack
Secure the EBM to your rack with four black M5X8L screws at the front of the
rack (square holes 2 and 5 as shown below)
VERTICAL/TOWER INSTALLATION
Step 1: Adhere rubber pads
Adhere four circular rubber pads to the left hand side of the extended battery
module. This will become the bottom side. Insert the dust covers into the open
screw holes on bottom.
Step 2: Attach the base stands and attach the dust covers
Stand the EBM on its side with the rubber pads facing down. If installing the
EBM together with a UPS, remove the four dust covers first and secure the tie
plate between the UPS and the EBM using four silver M5X6L pan head screws.
Adhere four circular rubber pads to each tower stand and screw on to the EBM
and UPS for added stability a shown below. Insert the dust covers into the
open screw holes on top.
MAINTENANCE
Storage
To store your EBM for an extended period of time, cover and store it with the
battery fully charged. Recharge the battery every three months to ensure
battery life.
Battery Replacement
Please read and follow the Safety Instructions before servicing the battery.
Battery replacement should be performed by trained personnel who are familiar
with the procedures and safety precautions. Make a note of the Replacement
Battery part number.
Safety Precautions
Warning: High voltage – Risk of Electric Shock
Only use replacement batteries that are certified by Cyber Power Systems. Use
of incorrect battery type is an electrical hazard that could lead to
explosion, fire, electric shock, or short circuit.
Batteries contain an electrical charge that can cause severe burns. Before
servicing batteries, please remove any conductive materials such as jewelry,
chains, wrist watches, and rings.
Do not open or mutilate the batteries. Electrolyte fluid is harmful to the
skin/eyes and may be toxic.
To avoid electric shock, turn off and unplug the EBM from the wall receptacle
before servicing the battery.
Only use tools with insulated handles. Do not lay tools or metal parts on top
of the EBM or battery terminals.
Replacement Batteries
Please refer to the front side of the EBM for the model number of the correct
replacement batteries. For battery procurement, go to
www.CyberPowerSystems.com, or contact your
local dealer.
When the UPS LCD displays Service Battery, use PowerPanel® Business software
or log on to the RMCARD to perform a runtime calibration to verify battery
capacity is sufficient and acceptable.
Battery Disposal
Do Not Discard
Batteries are considered hazardous waste and must be disposed of properly.
Contact your local government for more information about proper disposal and
recycling of batteries. Do not dispose of batteries in fire.
Cyber Power Systems encourages environmentally sound methods for disposal and
recycling of its UPS products.
Please dispose and/or recycle your UPS and batteries in accordance with local
regulations.
Step 1: Remove the front panel.
Step 2: Unscrew and open the battery access door. Loosen the two screws
on the battery connectors.
Step 3: Disconnect the battery connector and then disconnect battery
management module connector. Step 4: Unscrew the
battery retention bracket and then open it
Step 5: Pull the battery trays out slowly and then put the new battery
trays into the compartment.
Step 6 : Assemble battery retention cover. Connect battery management
module connector and then connect the battery connector. Ensure that they are
seated properly (connector will click into place). Tighten the battery access
door.
Step 7: Install the front panels. Execute a battery test via the LCD
control panel. To do this go to the Main Menu and select the Diagnostics Icon,
then select Battery Test and Activate. After Battery test, go back to the Main
Menu then select the Set UP icon, then select Batt Install Date to set the
battery installation date. This operation can also be done via PowerPanel®
Business or the RMCARD web interface. Please see their respective User Manuals
for detailed instructions.![CyberPower BP192VL2U01 Smart App Online UPS System
- fig 18](https://manuals.plus/wp-content/uploads/2023/04/CyberPower- BP192VL2U01-Smart-App-Online-UPS-System-fig-18.jpg)
TECHNICAL SPECIFICATIONS
MODELS | BP192VL2U01 |
---|
CONFIGURATION
AC Input Voltage| 200-240 V
DC Output Voltage| 192 Vdc
DC Output Current| 60 A
PHYSICAL
Dimensions| L x W x H = 28.3 X 17.05 x 3.4 in (72 x 43.3 x 8.65 cm)
Net Weight| 101.4 lb (46Kg)
BATTERY
Specifications| (16) 12 V/6 Ah
Replacement Battery Cartridge| RB1260X8A (1) (Left) + RB1260X8B (1) (Right)
Recharge Time 0-90% (Typical)| 4 hours
Hot-Swappable| Yes
Built-in Charger| Yes
ENVIRONMENT
Operating Temperature| 32 °F to 104 °F ( 0 °C to 40 °C)
Operating Relative Humidity| 0 to 90% Non-Condensing
SAFETY
Conformance Approvals| CE, UL1778, FCC part 15 Class A
RoHS| RoHS Compliant
TROUBLESHOOTING
PROBLEM | POSSIBLE CAUSE | SOLUTION |
---|
WARNING
BAT Disconnected| No battery power is being detected by the UPS.
Check the battery connector and the battery breaker.
Battery Failure| UPS has failed a Battery Test.| Check the battery connector
and the battery breaker.
Contact technical support to replace battery if under the warranty
period..
Replace Battery| Battery will soon need to be replaced due to insufficient
runtime.| Install new batteries, execute battery test, and reset the replace
battery date.
Service Battery| The Battery Replacement Date has reached the recommended 3
year maintenance period.| Perform a runtime calibration to verify battery
capacity is sufficient and acceptable.
If batteries have been recently replaced, then reset the Battery Replacement
Date using
PowerPanel’ Business software, RMCARD web interface or through the LCD control
panel on the UPS (See LCD Configuration Settings).
FAULT
Over Charge| Battery is overcharged.| Remove the battery connector and check
charger voltage.
Contact CyberPower for repair.
Charger Failure| Charger has failed.
PRODUCT REGISTRATION
CyberPower requests that you complete and return the Warranty Registration Card enclosed with the Product or register the Product at its website (www.cyberpowersystems.com/registration) to establish that you are the Initial Customer of the Product, and therefore entitled coverage under the Limited Warranty and the Connected Equipment Guarantee. (Registration is not required for coverage, but note: if you do not register your purchase, you will be required to provide proof of purchase.)
LIMITED WARRANTY
Read the following terms and conditions carefully before using the CyberPower
BP192VL2U01. By using the Product you consent to be bound by and become a
party to the terms and conditions of this Limited Warranty (together referred
to as the “Warranty”). If you do not agree to the terms and conditions of this
Warranty, you should return the Product for a full refund prior to using it.
Who is Providing this Warranty?
CyberPower Systems (USA), Inc. (“CyberPower”) provides this Limited Warranty.
What Does This Warranty Cover?
This warranty covers defects in materials and workmanship in the Product under
normal use and conditions.
What is the Period of Coverage?
This warranty covers the Product for three years.
Who Is Covered?
This warranty only covers the original purchaser. Coverage ends if you sell or
otherwise transfer the Product.
How Do You Get Warranty Service?
- Before contacting CyberPower, identify Your Product model number, and the Purchase Date.
- Email us at tech@cpsww.com or Call us at 877-297-6937.
- If your product requires warranty service you must provide a copy of your dated purchase receipt or invoice.
How Do You Open A Warranty Claim?
- Call us at 877-297-6937 or write to us at Cyber Power Systems (USA), Inc., 4241 12th Ave. E., STE 400, Shakopee, MN 55379, or send us an e-mail message to claims@cpsww.com for instructions, within 10 days of the occurrence.
- When you contact CyberPower, identify the Product, the Purchase Date, and Request a Claim Number.
- You must provide a dated purchase receipt (or other proof of the original purchase) for the Cyber Power unit.
- Pack and ship the product to CyberPower and all claim forms that CyberPower provides to you. Show the Claim Number on the shipping label or include it with the product. You must prepay all shipping costs, you are responsible for packaging and shipment, and you must pay the cost of the repair estimate.
How Long Do I Have To Make A Claim?
All claims must be made within ten days of the occurrence.
What Will We Do To Correct Problems?
CyberPower will inspect and examine the Product.
If the Product is defective in material or workmanship, CyberPower will repair
or replace it at CyberPower’s expense, or, if CyberPower is unable to or
decides not to repair or replace the Product (if defective) within a
reasonable time, CyberPower will refund to you the full purchase price you
paid for the Product (purchase receipt showing price paid is required).
Who Pays For Shipping?
We pay when we send items to you; you pay when you send items to us.
What Are Some Examples Of What This Warranty Does Not Cover?
- This Warranty does not cover any software that was damaged or needs to be replaced due to the failure of the Product or any data that is lost as a result of the failure or the restoration of data or records, or the reinstallation of software.
- This Warranty does not cover or apply to: misuse, modification, operation or storage outside environmental limits of the Product or the equipment connected to it, nor for damage while in transit or in storage, nor if there has been improper operation or maintenance, or use with items not designed or intended for use with the Product, such as laser printers, appliances, aquariums, medical or life support devices, etc.
What Other Limitations Apply?
The sole and exclusive remedies of the Initial Customer are those provided by
this Warranty.
- This Warranty does not apply unless the Product and the equipment that was connected to it were connected to properly wired and grounded outlets (including compliance with electrical and safety codes of the most current electrical code), without the use of any adapters or other connectors.
- The Product must have been plugged directly into the power source and the equipment connected to the Product must be directly connected to the Product and not “daisy-chained” together in serial fashion with any extension cords, another Product or device similar to the Product, surge suppressor, or power tap. Any such installation voids the Limited Warranty.
- The Product must have been used properly in a suitable and proper environment and in conformance with any license, instruction manual, or warnings provided with the Product and the equipment connected to it.
- The Product must have been used at all times within the limitations on the Product’s VA capacity.
The Product was designed to eliminate disrupting and damaging effects of momentary (less than 1ms) voltage spikes or impulses from lightning or other power transients. If it can be shown that a voltage spike lasting longer than 1ms has occurred, the occurrence will be deemed outside the rated capabilities of the Product and the Limited Warranty is void. CyberPower Does Not Cover or Undertake Any Liability in Any Event for Any of the Following:
-
Loss of or damage to data, records, or software or the restoration of data or records, or the reinstallation of software.
What Other Limitations Apply? Cont. -
Damage from causes other than AC Power Line Transients, spikes, or surges on properly installed, grounded and code-compliant 120 volt power lines in the United States and Canada; transients, surges or spikes on standard telephone land lines, PBX telephone equipment lines or Base 10T Ethernetlines, when properly installed and connected. (This exclusion applies, for example, to fluctuations in data transmission or reception, by CATV or RF transmission or fluctuations, or by transients in such transmission.)
-
Damage from any circumstance described as excluded above with respect to the Product.
-
Damages from fire, flood, wind, rain, rising water, leakage or breakage of plumbing, abuse, misuse or alteration of the product.
-
CyberPower excludes any liability for personal injury under the Limited Warranty. CyberPower excludes any liability for direct, indirect, special, incidental or consequential damages, whether for damage to or loss of property [EXCEPT FOR (AND ONLY FOR) the specific limited agreement of CyberPower to provide certain warranty benefits, loss of profits, business interruption, or loss of information or data. NOTE: Some States or Provinces do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation may not apply to you.
-
The Product is not for use in high-risk activities or with aquariums. The Product is not designed or intended for use in hazardous environments requiring fail-safe performance, or for use in any circumstance in which the failure of the Product could lead directly to death, personal injury, or severe physical or property damage, or that would affect operation or safety of any medical or life support device (collectively, “High Risk Activities”). CyberPower expressly disclaims any express or implied warranty of fitness for High Risk Activities or with aquariums. CyberPower does not authorize use of any Product in any High Risk Activities or with Aquariums. ANY SUCH USE IS IMPROPER AND IS A MISUSE OF THE PRODUCT.
Where Can I Get More Information?
The application of the United Nations Convention of Contracts for the
International Sale of Goods is expressly excluded.
CyberPower is the warrantor under this Limited Warranty.
For further information please feel free to contact CyberPower at
Cyber Power Systems (USA), Inc.
4241 12th Ave E., STE 400, Shakopee, MN 55379
877-297-6937
claims@cpsww.com
CONFORMANCE APPROVAL
FCC NOTICE
This device complies with part 15 of the FCC Rules. Operation is subject to
the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference that may cause
undesired operation.
WARNING!! This equipment has been tested and found to comply with the
limits for a Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful
interference when the equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, may cause
harmful interference to radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his own expense. Shielded
signal cables must be used with this product to ensure compliance with the
Class A FCC limits.
The Class A digital apparatus meets all requirements of the Canadian
Interference-Causing Equipment Regulation.
Cet appareil numerique de la class A respecte toutes les exigencies du
Reglement sur le materiel brouilleur du Canada.
This document is believed to be accurate, but CyberPower reserves the right to
change or correct the contents and does not assume any responsibility for
omissions or errors.
Need Additional Help?
See Operation and Installation Manual provided and also available to download
at
www.CyberPowerSystems.com Still Need Help?
Please contact our Tech Support department with installation, troubleshooting,
or general product questions.
CyberPower Technical Support
Phone: 1-877-297-6937
Email: tech@cpsww.com
Web: www.CyberPowerSystems.com
Address: 4241 12th Avenue E., Suite 400, Shakopee, MN 55379, USA
Hours of Operation:
Monday – Friday, 7:00am – 6:00pm (CST)
Cyber Power Systems, Inc.
www.CyberPowerSystems.com
For USA and Canada
4241 12th Ave East, Suite 400, Shakopee, MN 55379
Toll-free: 877.297.6937
For all other regions
Please visit our website for local contact information.
Copyright © 2022 Cyber Power Systems, Inc. All rights reserved.