MARATHON 5KCP33KNB267AS AC Induction Motors User Manual

June 9, 2024
MARATHON

**MARATHON 5KCP33KNB267AS AC Induction Motors

**

SAFETY INSTRUCTIONS

This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.

WARNING
Before installing, using, or servicing this product, carefully read and fully understand the instructions including all warnings, cautions, & safety notice statements. To reduce risk of personal injury, death and/or property damage, follow all instructions for proper motor installation, operation and maintenance.

These instructions are not intended as a complete listing of all details for installation, operation, and maintenance. If you have any questions concerning any of the procedures, STOP, and call the appropriate Regal-Beloit motor company.

INSTALLER/OWNER/OPERATOR RESPONSIBILITY:

ELECTRICAL SAFETY

WARNING: ELECTRICAL SHOCK HAZARD
Electrical connections shall be made by a qualified electrical personnel in accordance with all applicable codes, ordinances and sound practices.
Failure to follow these instructions could result in serious personal injury, death and/or property damage. Only qualified personnel who are familiar with the applicable National Code (USA = NEC) and local codes should install or repair electrical motors and their accessories.

WARNING: ELECTRICAL LIVE CIRCUIT HAZARD
Do not touch electrically live parts. Disconnect, lockout and tag input power supply before installing or servicing motor (includes accessory devices). Use a voltmeter to verify that power is off before contacting conductors.

WARNING: ELECTRICAL GROUNDING HAZARD
Failure to properly ground motors, per the National Electrical Code (NEC)
Article 430 and local codes may cause serious injury or death to personnel. For general information on grounding refer to NEC Article 250. (Also see “Ground Connections section 3.4.4“).

WARNING: AUTOMATIC RESET PROTECTOR HAZARD
Do not use automatic reset protectors if automatically restarting the motor will place personnel or equipment at risk. . Failure to follow this instruction could result in serious personal injury, death and/or property damage

WARNING: MANUAL RESET PROTECTOR HAZARD
If a tripped manual reset thermal protector is exposed to a temperature less than –7°C (20°F) it may reset and restart the motor automatically. If an application requires a motor with a manual reset thermal protector that will be operated at temperatures less than –7°C (20°F) contact the manufacturer to review the application / motor requirements. Failure to follow this instruction could result in serious personal injury, death and/or property damage

MECHANICAL SAFETY

WARNING: LOOSE PARTS HAZARD
Before starting the motor, remove all unused shaft keys and loose rotating parts to prevent them from flying off. Failure to follow these instructions could result in serious personal injury, death and/or property damage.

WARNING: ROTATING PARTS HAZARD
Keep extremities, hair, jewelry and clothing away from moving parts.
Failure to follow these instructions could result in serious personal injury, death and/or property damage.

ENVIRONMENTAL SAFETY

WARNING: HAZARDOUS LOCATIONS

  1. The NEC and the local authority having jurisdiction must be consulted concerning the installation and suitability of motors for use in Hazardous Locations. The local authority having jurisdiction must make the final determination of what type of motor is required. The application and operation is beyond the control of the motor manufacturer.
  2. Division 1 Hazardous Locations motors can only be modified or reworked by the manufacturer or a facility that is Listed under UL’s category “Motors and Generators, Rebuilt for use in Hazardous Locations”. Failure to follow these instructions could result in serious personal injury, death and/or property damage.
  3. Do not use a Hazardous Locations motor with a Variable Frequency Drive (VFD) unless the motor nameplate specifically states that the motor is suitable for use on Pulse Width Modulated (PWM) type VFD power. In addition, the nameplate must be marked with the inverter rating; for example, “2:1 CT”, “2 to 1 Constant Torque”, etc.

RECEIVING AND INSPECTION

INITIAL INSPECTIONS

  1. CHECK PACKING LIST AND INSPECT the packaging to make certain no damage has occurred in shipment. If there is visible damage to the packaging, unpack and inspect the motor immediately. Claims for any damage done in shipment must be made by the purchaser against the transportation company.
  2. TURN MOTOR SHAFT by hand to be certain that it rotates freely. Note: Shaft seals and bearing seals may add drag.
  3. CHECK NAMEPLATE for conformance with purchase order requirements and compliance with power supply and control equipment requirements.

HANDLING:

WARNING: FALLING OBJECT HAZARD
Eyebolts or lifting lugs, where provided, are intended for lifting only the motor and accessories mounted by the motor manufacturer (unless specifically stated otherwise on the motor).
Utilizing the motor lifting provision to lift other components such as pumps and gear boxes could result in serious personal injury, death and/or property damage.

WARNING: FALLING OBJECT HAZARD
Before using the lifting provision, check the eyebolts and/or other lifting means to assure they are not bent or damaged and are completely threaded, seated & secured to the motor. Equipment to lift motor must have adequate lifting capacity. While lifting the motor DO NOT stand under or in the vicinity of the motor. Failure to follow these instructions could result in serious personal injury, death and/or property damage.

**LIFTING ANGLE LIMITATIONS

**

STORAGE:

Motors, not put into service immediately, must be stored indoors in a clean, dry location. Avoid locations with large temperature swings that will result in condensation. Motors must be covered to eliminate airborne dust and dirt. If the storage location exhibits high vibration, place isolation pads under motor to minimize damage to motor bearings.

  1. BEARING LUBRICATION: Bearings are grease packed at the factory; relubrication upon receipt of motor or while in storage is not necessary. If stored more than one year, add grease per lubrication instructions (Table 4-4) before start-up.
  2. SHAFT ROTATION: It is recommended that the motor shaft be rotated 5 to 10 rotations every three months to distribute the grease in the bearings. This will reduce the chance for corrosion to form on the bearing rolling elements and raceways. Note: Shaft seals and bearing seals may add drag.
  3. DAMP OR HUMID STORAGE LOCATIONS: Treat unpainted flanges, shafts, and fittings with a rust inhibitor. Apply appropriate power to the motor’s space heaters (if so equipped)

INSTALLATION AND OPERATION

WARNING: Only qualified personnel who are familiar with the appropriate national code, local codes and sound practices should install or repair electrical motors and their accessories. Installation should conform to the appropriate national code as well as local codes and sound practices. Failure to follow these instructions could result in serious personal injury, death and/or property damage.

WARNING: ELECTRICAL LIVE CIRCUIT HAZARD
Do not touch electrically live parts. Disconnect, Lockout and Tag input power supply before installing or servicing motor (includes accessory devices). Use a voltmeter to verify that power is off before contacting conductors.

LOCATION

SELECTING A LOCATION: Consideration should be given to environment and ventilation. Motors should be installed in an area that is protected from direct sunlight, corrosives, harmful gases or liquids, dust, metallic particles, and vibration. A motor with the proper enclosure for the expected operating condition should be selected. Provide accessible clearance for cleaning, repair, service, and inspections (See section 3.1.3 for construction clearances).
The location should be considered for possible future motor removal / handling. The free flow of air around the motor should not be obstructed.

AMBIENT TEMPERATURE LIMITS: The ambient temperatures of the air inlet to the motor should not exceed 40°C (104°F) or be less than -30°C (-22°F) unless the motor nameplate specifically states an ambient temperature outside of these limits.
The ambient inside an enclosure built around the motor shall not exceed the nameplate ambient. For ambient temperatures outside of these limits consult the motor manufacturer.

CAUTION: INSULATION DEGRADATION WARNING Insulation at high temperatures ages at an accelerated rate. Each 10°C increase in temperature reduces the insulation life by one half.

WARNING: HAZARDOUS LOCATIONS AMBIENT LIMIT:
Division 1 Hazardous Locations motors shall NOT be operated below –25°C (-13°F) ambient. (Low temperatures reduce the component mechanical properties.)

CONSTRUCTION SELECTION per LOCATION:

  1. DRIPPROOF (OPEN) MOTORS are intended for use indoors where the atmosphere is relatively clean, dry, and non-corrosive. Recommended a minimum clearance of ½ the shaft height between vent openings and the nearest obstruction.

  2. TOTALLY ENCLOSED MOTORS are suitable for indoor or outdoor standard service applications.
    TEAO or AOM (Totally Enclosed Air Over) motors must be mounted in the air stream.
    When the motor nameplate states a minimum airflow the motor must be mounted in an air stream meeting this minimum value.
    TEFC (Totally Enclosed Fan Cooled) motors must meet a minimum distance of ½ the shaft height between the fan guard grill openings and the nearest obstruction.

  3. HAZARDOUS LOCATIONS MOTORS: Hazardous Locations motors are intended for installations in accordance with NEC Article 500. For all installations involving Hazardous Locations motors, consult the applicable national codes, local codes, and the authority having jurisdiction.
    Division 1 Installations – includes Class I & II: Use only motors that are UL Listed and CSA Certified or UL Listed and UL Certified for Canada. These motors bear a separate nameplate that includes the UL Listing Mark and CSA Certification Mark or includes the UL Listing Mark and the UL Mark for Canada. This plate also bears the phrase: “ Electric motor for Hazardous Locations” and is marked with the Class, Group and Operating Temperature Code.
    Division 2 Installations – Class I only: Use only motors that are CSA Certified and bear the CSA Certification Mark.
    These motors include a phrase on the main motor nameplate that indicates the motor is CSA Certified for Class I, Division 2 / Zone 2 locations.
    Division 2 Installation – Class II only: Use only Class II motors as described above under “Division I Installations”.

WARNING: EXPLOSION HAZARD
A motor should never be placed in an area with a hazardous process or where flammable gases or combustible materials may be present unless it is specifically designed and nameplated for this type of service. Hazardous Locations motors are intended for installations in accordance with NEC Article 500. For all installations involving Hazardous Locations motors, consult the NEC, local codes, and the authority having jurisdiction. Failure to follow these instructions could result in serious personal injury, death and/or property damage. (For other limitations see section 1.3)

MOUNTING MOTOR:

RIGID BASE (FOOTED): The motor must be securely installed to a rigid foundation or a mounting surface to minimize vibration and maintain alignment between the motor shaft and the load’s shaft. The mounting surfaces of the four mounting pads must be flat within 0.01 inches for 210 frame & smaller; 0.015 inches for 250 frame & larger. [IEC 0.25 mm for 130 frame & smaller, 0.38 mm for 160 frame & larger]. This may be accomplished by shims under the motor feet. For special isolation mounting, contact manufacturer for assistance

RIGID BASE HOLE SELECTION -6 OR 8 HOLES
RIGID BASE HOLE SELECTION -6 OR 8 HOLES

VERTICAL MOUNTING:

CAUTION: ENCLOSURE PROTECTION CAUTION: Most Drip proof rigid base (footed) motors do NOT meet “Dripproof” requirements when mounted vertically. If the motor is located in unprotected environments, the addition of a drip cover may be available. Drip covers not available for cast iron rigid base motors.

WARNING: FALLING OBJECT HAZARD
The lifting provision on standard horizontal footed motors is not designed for lifting the motor in a vertical shaft up or shaft down position. (see 2.2.1 lifting angles). Lifting method / provisions for mounting a rigid base (footed) motor vertically is the responsibility of the installer.

VERTICAL SHAFT DOWN: Most standard horizontal motors thru 449 Fr. (excluding brake motors) can be mounted in a vertical shaft down orientation. For vertical brake motors see section 3.3.6.2.

VERTICAL SHAFT UP:
WARNING: HAZARDOUS LOCATIONS VERTICAL MOUNT: Hazardous locations motors must NOT be mounted vertically shaft up without approval by the motor manufacturer.
Without proper retaining provisions the rotor may move axially and contact components, creating a spark hazard.
Belted or Radial Load when mounted vertically: The following frame sizes / constructions with applied (axial) down loads within the limit stated are acceptable when mounted vertical shaft up.

Table 3-1 Belted or Radial Load Applications (All speeds)

Frame Size Enclosure Construction Shaft Up OK Max Applied Down Load3
56 TEFC & ODP Steel Yes 25 lbs
140 TEFC Steel & Cast

Iron

| Yes| 25 lbs
ODP| Steel| Yes| 25 lbs
180| TEFC| All| Yes| 35 lbs
ODP| Steel| Yes| 35 lbs
210| TEFC| All| Yes| 40 lbs
ODP| Steel| Yes| 40 lbs
250| TEFC| All| Yes| 40 lbs
ODP| Steel| Yes| 40 lbs
Cast Iron| N 2

o

| N/A

280-320

| 320 TTFC models| Cast Iron| En 1

g

| N/A
All Other TEFC| Cast Iron & Aluminum| Yes| 30 lbs
ODP| Cast Iron| N 2

o

| N/A
TEFC & ODP| Steel| Build Up

Only4

| N/A
360 & Up| TEFC| Cast Iron| Build Up Only4| N/A
ODP| Cast Iron| No2| N/A
TEFC & ODP| Steel| Build Up Only4| N/A

Notes:

  1. For TEFC model numbers beginning with 324TTFC or 326TTFC consult the motor manufacturer to determine if a build up motor is required.
  2. The max applied down load is any applied load external to the motor, including such things as sheave weight, fan loads, axial belt force, pump load, etc. If the application is direct drive with no applied radial load, consult the motor manufacturer.
  3. ”Build-up only”, refers to motors that are specifically ordered and built for shaft up applications. It does not imply that all buildup motors are suitable for shaft up applications.

APPLICATION ASSEMBLY TO MOTOR:

CAUTION: EQUIPMENT DAMAGE:
Do not connect or couple motor to load until correct rotational direction is established.

GENERAL: PROPER ALIGNMENT of the motor and driven equipment minimizes vibration levels, maximizes bearing life, and extends the overall life of the machinery. Consult the drive or equipment manufacturer for more information.

CAUTION: BEARING FAILURE
During assembly do NOT force components onto the shaft. Striking or hammering the component may result in bearing damage.

DIRECT COUPLING: Use flexible couplings if possible.
For applications that apply radial, axial or moment loading on the motor shaft see section 3.3.3.

CAUTION: BEARING FAILURE
Unless approved by the motor manufacturer do NOT direct couple a vertical shaft up or roller bearing motor. Direct coupling a vertical shaft up motor or a motor with a roller bearing may result in bearing damage.

DIRECT CONNECTED: Radial loading for direct connected equipment (gears, fans etc.) must be approved by the motor manufacturer unless within the maximum overhung load limits (Table 3-2). Combined loading (axial, radial and/or moments) must be approved by motor manufacturer. For belted loads see section 3.3.4.

Table 3-2 Maximum Radial Load (lbf) @ Middle of the Shaft Extension Length

Frame Number Motor Rated RPM
3600 1800
143T 106
145T 109
182T 187
184T 193
213T 319
215T 327
254T 500
256T 510
284T
286T
324T
326T
364T
365T
404T
405T
444T
445T
447T
449T

Values based on 26,280 hrs B-10 Life
For “End of Shaft” Load multiply value by 0.88
To convert from lbf to N multiply value by 4.4482.

BELTED:
The goal of any belted system is to efficiently transmit the required torque while minimizing the loads on the bearings and shafts of the motor and driven equipment. This can be accomplished by following four basic guidelines:

  1. Use the largest practical sheave diameter.
  2. Use the fewest number of belts possible.
  3. Keep sheaves as close as possible to support bearings.
  4. Tension the belts to the lowest tension that will still transmit the required torque without slipping. It is normal for V-belts to squeal initially when line starting a motor

Sheave Diameter Guidelines:
In general, smaller sheaves produce greater shaft stress and shaft deflection due to increased belt tension. See Table 3-3 for recommended minimum sheave diameters. Using larger sheaves increases the contact with belts which reduces the number of belts required. It also increases the belt speed, resulting in higher system efficiencies. When selecting sheaves, do not exceed the manufacturer’s recommended maximum belt speed, typically 6,500 feet per minute for cast iron sheaves. Determine belt speed by the following formula:
Sheave Diameter Guidelines

Number of Belts
In general, use the fewest number of belts that will transmit the required torque without slipping. See Table 3-3 for recommended maximum number of belts. Each belt adds to the tension in the system, which increases load on the shafts and bearings. Belts are most efficient when operated at or near their rated horsepower.
If the sheaves have more grooves than the number of belts required, use the grooves closest to the motor.

Sheave Location
Install sheaves as close to the housing as possible to increase the bearing life of the motor and driven equipment

Belt Tension
CAUTION: Equipment Failure Caution
Belt tensioning by feel is NOT acceptable. Tensioning by “feel” can be very misleading, and can damage motor and equipment.
It is normal for V-belts to squeal initially when line starting a motor.
In general, belt tensions should be kept as loose as possible while still transmitting the required torque without slipping. Belt tensions must be measured with a belt tension gage. These inexpensive gages may be obtained through belt manufacturers, or distributors.
Proper belt tension is determined by measuring the force required to deflect the center of the belt a given distance. The proper deflection (in inches) is determined by dividing the belt span in inches by 64.
Calculate the proper deflection and then see Table 3-3 for the required “Deflected Force” to achieve that deflection.
After tensioning the belt, rotate the sheaves for several rotations or operate the system for a few minutes to seat belts into the grooves, then re-tension the belts. New belts will stretch during use, and should be retensioned after the first eight hours of use.

Table 3-3 Recommended Minimum Sheave Diameters, Belt Type, Number of Belts and Deflected Force

Motor Hp 1200 rpm 1800 rpm 3600 rpm
Min Sheave Dia (in) Belt Type Max # of Belts Avg. Deflected Force (lbs)
Min Sheave Dia (in) Belt Type Max # of Belts Avg. Deflected Force (lbs)
Min Sheave Dia (in) Belt Type Max # of Belts Avg. Deflected Force (lbs)
       
1 2.4 3VX 1
1.5 2.4 3VX 2
2 2.4 3VX 3
3 3.0 3VX 2
5 3.0 3VX 3
7.5 3.8 3VX 4
10 4.4 3VX 4
15 4.4 3VX 5
20 5.2 3VX 6
25 6.0 3VX 7
30 6.8 3VX 7

Contact Motor Manufacturer when Belting 3600 rpm Motors Greater than 25 HP

40| 6.8| 5VX| 4| 11.6| 6.0| 3VX| 7| 6.0
50| 8.2| 5VX| 4| 14.6| 6.8| 3VX| 8| 5.9
60| 8.2| 5VX| 5| 14.1| 7.4| 5VX| 4| 13.3
75| 10.0| 5VX| 5| 14.5| 8.6| 5VX| 4| 14.3
100| 10.0| 5VX| 6| 16.0| 8.6| 5VX| 6| 13
125| 12.0| 5V| 7| 14.1| 10.5| 5V| 6| 13.1
150| 13.2| 5V| 7| 15.4| 10.5| 5V| 7| 13.4
200| 15.0| 5V| 8| 16.0| 13.2| 5V| 8| 13.1
250| 15.0| 8V| 6| 27.6| 14.0| 5V| 9| 13.8
300| 16.0| 8V| 7| 27.1| 14.0| 5V/8V| 11 / 7| 23.4
350| 16.5| 8V| 7| 30.3| 14.5| 5V/8V| 12 / 7| 26.0
400| 17.5| 8V| 8| 29.1| 15.0| 5V/8V| 13 / 8| 25.7
450| 18| 8V| 8| 31.6| 16.0| 5V/8V| 14 / 9| 25.2
500| 18.5| 8V| 9| 30.7| 16.5| 5V/8V| 15 / 9| 26.9
600|  |  |  |  | 17.5| 8V| 11| 26.3
700|  |  |  |  | 19.0| 8V| 12| 27.3
800|  |  |  |  | 20.0| 8V| 13| 28.2

Notes:

  1. Horsepower is the nameplate motor horsepower, and RPM is the motor (driver) speed.
  2. Minimum sheave diameters are from NEMA standards where applicable.
  3. For variable speed applications or values outside these recommendations, consult motor manufacturer.
  4. Selections are based on a 1.4 service factor, 5 to 1 speed ratio and various Power Transmission Manufacturers’ catalogs.
  5. These selections are for Narrow V-belt sections only. Consult manufacturer for details on conventional V-belt sections (A, B, C, D and E), or other belt types.
  6. “Average Deflected Force is per section 3.3.4.4 of this document and is the force required to deflect the center of a belt 1/64 of the belt span distance. Tolerance on this force is ±1 lbf for forces ≤10 lbs, and ±2 lbs for forces >10 lbs as measured utilizing a belt tension gage.
  7. When more than one belt is required the belts must be a matched set (matched for length).
  8. If possible, the lower side of the belt should be the driving side to increase the length of wrap on the sheave).
  9. For belted loads do not exceed 125% of 60 Hz operating RPM.

VFD (Variable Frequency Drives) OPERATION:

WARNING: VFD Motors with Reset Thermal Protectors
UL Recognition, UL Listing, or CSA certification does not apply to motors that are equipped with a manual or automatic reset thermal protector when the motor is operated on VFD power.

WARNING: Power Factor Correction Capacitors:
Power factor correction capacitors should never be installed between the drive and the motor.

CAUTION: VFD / Motor Setup:
It is the responsibility of the startup personnel during set up of the VFD / motor system to properly tune the drive to the motor for the specific application per the VFD user manual. The correct voltage boost and volts per hertz settings are application dependent and unique to each motor design. Failure to connect over temperature devices (when provided) will void the warranty.

Overspeed Capability:
Belted loads: Do not exceed 125% of 60 Hz operating RPM.
Table 3-4 Maximum Safe Continuous Speed (RPM)
For Coupled and Direct Connected Loads

NEMA / [IEC] Frame Size 2-Pole 4, 6, or 8 Pole
56-180     [80-110] 7200 * 5400 *
210-250 [130-160] 5400 * 4200*
280          [180] 5400 * 3600
320          [200] 4500 * 3600
360          [225] 4500 * 2700
400-440 [250-280] 3600 2700
>440        [>280] 3600 1800
  • = Fan cooled motors (Totally Enclosed & Hazardous Locations Motors) are limited to a maximum safe continuous speed of 4000 RPM For higher speeds or shortened duty cycle contact motor manufacturer

Cable Lengths: For optimum insulation life, limit VFD to motor cable lengths of general purpose motors to Table 3-5 values. Definite purpose VFD motors may accommodate longer cable lengths. For additional information contact motor manufacturer.
Table 3-5 Max Cable Lengths General Purpose Motors
These values are based on 3 kHz carrier frequency. Add suitable VFD output- side filters when exceeding the listed values

Frame Size 230V 460 V 575 V
NEMA 56-320 600 ft. 125 ft. 40 ft.
NEMA 360-5011 1000 ft. 225 ft. 60 ft.
IEC 80-200 180 m. 40 m. 12 m.
IEC 225-280. 300 m. 70 m. 18 m.
  1. VFD Grounding: Equipment grounding conductors may be run in the same conduit as the AC motor power leads.
    This wire must be used as the equipment ground for the motor and not as the fourth current carrying wire of a “WYE” motor circuit.
    The grounded metal conduit carrying the output power conductors can provide EMI shielding, but the conduit does not provide an adequate ground for the motor; a separate grounding conductor must be used. Grounding the motor neutral (WYE) of a VFD powered motor may result in a VFD ground fault trip. Improper grounding of an inverter fed motor may result in frame voltages in excess of 500 Volts. Refer to Grounding section 3.4.4

  2. VFD – Single Phase:
    CAUTION: SINGLE PHASE MOTOR FAILURE:
    Single Phase motors are NOT suitable for use on VFD power.
    Connecting a Single Phase Motor to a VFD voids the warranty.

  3. Stray Voltage on Accessory Leads:
    VFD’s will couple stray (common-mode) voltage to motor mounted RTDs, thermistors, thermostats and space heaters. The leads of these elements must be properly insulated and control input circuits must be designed to withstand this common-mode voltage.

ACCESSORIES / PROVISIONS:

  1. General: Carefully read and understand the accessory manufacturer’s instructions, supplied with motor. Contact the manufacturer for additional information.

  2. Brake Motors:
    CAUTION: Vertical Motor Premature Brake Failure
    Motors with brakes that are designed for vertical applications are equipped with springs to support the brake pressure plate.
    Mounting a horizontal brake motor vertically shaft up or down may require a pressure plate spring modification. Failure to modify the brake for the vertical application may result in premature brake failure. If in question, consult brake literature or brake manufacturer.
    Brake Solenoid Wiring: Do NOT connect the brake solenoid to the output of a VFD. The brake solenoids must be wired to 50/60 Hz line power

  3. Space Heaters:
    Motors provided with space heaters have two leads that are brought into the conduit box or into an auxiliary box. These leads are marked ”H1”, “H2” (”H3”, “H4” if a second space heater is supplied). See the space heater nameplate on motor for heater rating.
    WARNING: DIVISION 2 EXPLOSION HAZARD
    The space heater temperature rating when used in Class I, Division 2 motors shall NOT exceed 80% of the auto ignition temperature of the hazardous gas or vapor. See the space heater nameplate on motor for heater Temperature Code and heater rating. Failure to follow this instruction could result in serious personal injury, death and/or property damage

  4. Thermal Protection:
    General Information: When thermal protection is provided, one of the following will be stamped on the nameplate:

  5. “THERMALLY PROTECTED” This motor has built in thermal protection. Thermal protectors open the motor circuit electrically when the motor overheats or is overloaded. The protector cannot be reset until the motor cools. If the protector is automatic, it will reset itself. If the protector is manual, disconnect motor from power supply. After protector cools (five minutes or more) press the reset button and reapply power to the motor. In some cases a motor is marked “Auto” and the connection diagram on the motor will identify T’Stat leads – see “2 ” below. (See warnings on Manual and Automatic reset protectors – section 1.1)

  6. “WITH OVERHEAT PROTECTIVE DEVICE”: This motor is provided with an overheat protective device that does not directly open the motor circuit. Motors nameplated with this phrase have either thermostats, thermisters or RTD’s. The leads to these devices are routed into the motor conduit box or into an auxiliary box. The lead markings are defined on the nameplate (normally “P1”, “P2”) . The circuit controlled by the overheat protection device must be limited to a maximum of 600 volts and 360 volt-amps. See connection decal provided inside the terminal box cover. Failure to connect these over temperature devices (when provided) will void the warranty.
    WARNING: EXPLOSION HAZARD
    For Hazardous Locations motors provided with thermostats UL and the NEC require connection of thermostat leads into the control portion of a manual reset start circuit. Failure to follow this instruction could result in serious personal injury, death and/or property damage
    Resistance Temperature Detectors (RTD): When winding and/or bearing RTDs are provided the RTD lead markings are defined on the nameplate. (Normally “R1”, “R2”, “R3” etc.)

  7. RTD Alarm & Trip Settings:
    Tables 3-6 & 3-7 are suggested initial RTD alarm and trip settings.
    For motors found to operate significantly below these values the settings may be reduced accordingly.

Table 3-6 Winding RTD – Temperature Limit (°C) 40 °C Max Ambient

Motor Load| Class B Temp Rise 80 ° C| Class F Temp Rise 105 ° C
---|---|---
 | Alarm| Trip| Alarm| Trip
Up to 1.0 SF| 130| 140| 155| 165

1.0 to 1.15 SF| 140| 150| 160| 165

Table 3-7 Bearing RTD – Temperature Limit (°C) 40 °C Max Ambient

Ambient Alarm Trip
Up to 40 ° C 95 100
> 40 ° C 110 115
Bearings that are Heat Stabilized to 150 ° C

130

|

135

GUARDS:
WARNING: ROTATING PARTS HAZARD
When devices are assembled to the motor shaft, be sure to install protective devices such as belt guards, chain guards, and shaft covers. These devices must protect against accidental contact with extremities, hair, and clothing. Consider the application and provide guarding to protect personnel. Remove all unused shaft keys and loose rotating parts to prevent them from flying off and causing bodily injury. Failure to follow this warning could result in serious personal injury, death and/or property damage.

ELECTRICAL CONNECTIONS:

WARNING: ELECTRICAL HAZARDS
Before proceeding read Section 1-1 on Electrical Safety. Failure to follow the instructions in Section 1-1 could result in serious personal injury, death and/or property damage

POWER SUPPLY / BRANCH CIRCUIT

WARNING: POWER SUPPLY INCOMPATIBILITY HAZARD
Check power supply to make certain that voltage, frequency and current carrying capacity are in accordance with the motor nameplate. Failure to match motor nameplate values could result in serious personal injury, death and/or property damage

WARNING: BRANCH CIRCUIT SUPPLY HAZARD
Motor and control wiring, fusing, overload protection, disconnects, accessories and grounding must always conform to the applicable electrical codes as well as local codes and sound practices.

  1. Branch Circuit Supply to a motor should include a disconnect switch, short circuit current fuse or breaker protection, motor starter (controller) and correctly sized thermal elements or overload relay protection.

  2. Fuses, Breakers, Overload Relays
    Short Circuit Current Fuses or Breakers are for the protection of the branch circuit. Starter or motor controller overload relays are for the protection of the motor. Each of these should be properly sized and installed per the applicable electrical codes as well as local codes and practices.
    WARNING: PROTECTIVE DEVICE DISABLED HAZARD
    DO NOT bypass or disable protective devices. Protection removal could result in serious personal injury, death and/or property damage

  3. AC Power Supply Limits
    Motors are designed to operate within the following limits at the motor terminals:
    1- AC power is within +/- 10 % of rated voltage with rated frequency applied. (Verify with nameplate ratings) OR
    2- AC power is within +/- 5% of rated frequency with rated voltage OR
    3- A combined variation in voltage and frequency of +/- 10% (sum of absolute values) of rated values, provided the frequency variation does not exceed +/-5% of rated frequency.
    4- For 3 phase motors the line to line full load voltage must be balanced within 1%.
    5- If the motor is rated 208-230V, the voltage deviations must be calculated from 230V.
    CAUTION: Reduced Motor Performance
    Operation outside of these limits will degrade motor performance and increase operating temperature.

TERMINAL BOX:

  1. Conduit Opening: For ease of connections, motors are typically provided with large terminal boxes. Most motors have conduit access in 90 degree increments, the terminal box conduit opening is typically provided via knockouts, holes with covers, or the terminal box is rotate-able. Fabricated conduit boxes may have a removable plate for the installer to provide correctly sized hole(s).
  2. Hazardous Locations Motors:
    WARNING: EXPLOSION HAZARDS
    (1) Terminal Boxes mounted to motor with a pipe nipple: If a pipe nipple mounted terminal box is removed or rotated it must be reassembled with a minimum of five full threads of engagement.
    (2) Component Removal: Do not set a terminal box component on its machined surfaces. Prior to component reassembly wipe clean all machined surfaces.
    (3) Machined Surface Gap (Hazardous Locations Terminal Boxes): The gap between mating surfaces with the machined terminal box MUST BE LESS THAN 0.002 inches. This gap must be checked with a feeler gage along the entire perimeter. If there is visible damage to the mating surfaces, or if the gap between these surfaces exceeds 0.002 inches, DO NOT complete the installation and contact the motor manufacturer. Failure to follow these instructions could result in serious personal injury, death and/or property damage

LEAD CONNECTIONS

Electrical connections to be made per nameplate connection diagram or separate connection plate. In making connections follow the applicable electrical code as well as local codes and practices.

WARNING: ELECTRICAL CONNECTION HAZARD
Failure to correctly connect the motor leads and grounding conductor can result in injury or death. Motor lead connections can short and cause damage or injury if not well secured and insulated.

Wire Size (Single Phase) Requirements
The minimum wire size for Single Phase, 115 & 230 Volt Circuits must meet table 3-8 for a given distance between motor and either Fuse or Meter Box.
Table 3-8 Minimum Wire Gage Size Single Phase 115 & 230 Volt Circuits

Distance (Feet) – Motor to Fuse or Meter Box

Motor| 100 Ft.| 200 Ft.| 300 Ft.| 500 Ft.
HP| 115| 230| 115| 230| 115| 230| 115| 230
1/4| 14| 14| 10| 12| 8| 10| 6| 8
1/3| 12| 14| 10| 12| 6| 10| 4| 8
1/2| 10| 12| 8| 10| 6| 8| 4| 6
3/4| 10| 12| 6| 10| 4| 8| 2| 6
1| 8| 10| 6| 8| 4| 6|  | 4
1 1/2| 4| 10| 0| 8|  | 6|  | 4
2|  | 8|  | 6|  | 4|  | 2
3|  | 8|  | 6|  | 4|  | 2
5|  | 6|  | 4|  | 2|  | 0

Extension Cords (Single Phase Motors):
Where an extension cord(s) is utilized to provide power to the motor the extension cord(s) must be…(1) the proper gauge size per table 3-8, (2) in good working condition (3) properly grounded.

GROUND CONNECTION(S):

WARNING: ELECTRICAL GROUNDING HAZARD
For general information on grounding (USA) refer to NEC Article 250.
Improper grounding of an inverter fed motor may result in frame voltages in excess of 500 Volts. In making the ground connection, the installer must make certain that a good electrical connection is obtained between motor and grounding lead. Failure to properly ground motors, per the applicable national code (such as NEC Article 430) and local codes may cause serious injury or death to personnel.
Primary “Internal” Ground: A grounding conductor must be connected to the grounding terminal provided in the terminal housing.
This grounding terminal is either a ground screw, ground lug, or a tapped hole to be used with a separately provided ground screw. The internal grounding feature is accessible inside the terminal housing and must be used as the primary grounding connection.
Secondary “External” Ground: Some motors are provided with a supplemental grounding terminal located on the external surface of the motor frame or feet. This external terminal is for supplemental bonding connections where local codes permit or require such connection

START UP:
WARNING: ELECTRICAL SHOCK HAZARD:
Be certain that all connections are secure and the conduit box cover is fastened in place before electrical power is connected. Failure to follow these instructions could result in serious personal injury, death, and/or property damage.
WARNING: LOOSE & ROTATING PARTS HAZARD
Before proceeding read Section 1-2 on Mechanical Safety. Failure to follow the instructions in Section 1-2 could result in serious personal injury, death and/or property damage
WARNING: EXCESSIVE SURFACE TEMPERATURE HAZARD
Motors with the temperature code stated on the nameplate are designed to operate within this limit. Improper application or operation can cause the maximum surface temperature to be exceeded. A motor operated in a Hazardous Location that exceeds this surface temperature limit increases the potential of igniting hazardous materials. Therefore, motor selection, installation, operation, and maintenance must be carefully considered to ensure against the following conditions: (1) Motor load exceeds service factor value, (2) Ambient temperature above nameplate value, (3) Voltages outside of limits (3.4.1.3), (4) Loss of proper ventilation, (5) VFD operation exceeding motor nameplate rating, (6) Altitude above 3300 feet / 1000 meters, (7) Severe duty cycles, (8) Repeated starts, (9) Motor stall, (10) Motor reversing, and (10) Single phase operation. Failure to follow these instructions could result in serious personal injury, death and/or property damage.
CAUTION: HOT SURFACE
Normal motor surface temperatures may exceed 90 ° C (194° F).
Touching the motor frame may cause discomfort or injury. Surface temperatures should only be measured with suitable instruments and not estimated by hand touch.

Start Up – No Load Procedure

  1. Check Instructions: Before startup carefully read and fully understand these instructions including all warnings, cautions, and safety notice statements.

  2. Motor out of storage after more than three months:
    Check winding insulation integrity with a Megger. If winding resistance to ground is less than 1.5 Meg-ohms consult the local authorized service shop before energizing the motor.

  3. Check Installation: Mechanical – Check tightness of all bolts and nuts. Manually rotate the motor shaft to ensure motor shaft rotates freely. Note: Shaft & bearing seals will add drag.
    Electrical – Inspect all electrical connections for proper terminations, clearance, mechanical tightness and electrical continuity. Be sure to verify connections are made per the nameplate connection diagram or separate connection plate.
    Replace all panels and covers that were removed during installation before energizing the motor.

  4. Energize Motor: Check Rotation
    If practical check motor rotation before coupling to the load.
    Unlock the electrical system. Momentarily provide power to motor to verify direction of rotation. If opposite rotation is required, lock out power before reconnecting motor. If motor has a rotational arrow only operate the motor in the rotation identified. Reapply power to ensure proper operation.

  5. Record No Load Amps, Watts & Voltage:
    Recommend – To establish a baseline value check and record the no load amps, watts, and voltage.

Start Up – Load Connected Procedure

  1. Check Instructions: Before startup carefully read and fully understand these instructions including all warnings, cautions, & safety notice statements.
  2. Coupling Installation: Check that the connected equipment is properly aligned and not binding. Check that all guards and protective devices are properly installed.
  3. Energize Motor: When all personnel are clear of the machine, apply power and verify that the load is not transmitting excessive vibration back to the motor though the shaft or the foundation. Verify that motor amps are within nameplate rating.
    For repeated starts see 3.4.5.3. The equipment can now be fully loaded and operated within specified limits as stated on the nameplate.

Jogging and/or Repeated Starts
Do not start more than twice in succession under full load.
Repeated starts and/or jogs of induction motors can cause overheating and immediate failure. Contact the motor manufacturer if it is necessary to repeatedly start or jog the motor.

MAINTENANCE

WARNING: Hazardous Locations Motor Repair HAZARD:
Division 1 Hazardous Locations motors can only be modified or repaired by the manufacturer or a facility that is Listed under UL’s category “Motors and Generators, Rebuilt for use in Hazardous Locations”. Failure to follow these instructions could result in serious personal injury, death and/or property damage.
WARNING: ELECTRICAL SHOCK HAZARD
Electrical connections are to be made by qualified electrical personnel in accordance with all applicable codes, ordinances and sound practices.
Failure to follow these instructions could result in serious personal injury, death and/or property damage. Only qualified personnel who are familiar with the applicable national codes, local codes and sound practices should install or repair electric motors and their accessories.
WARNING: ELECTRICAL LIVE CIRCUIT HAZARD
Do not touch electrically live parts. Disconnect, lockout and tag input power supply before installing or servicing motor (includes accessory devices).

GENERAL INSPECTION

Inspect the motor approximately every 500 hours of operation or every three months, whichever occurs first. Keep the motor clean and the ventilation and fin openings clear. The following steps should be performed at each inspection:

  1. VENTILATION: Check that the ventilation openings and/or exterior of the motor is free of dirt, oil, grease, water, etc, which can accumulate and block motor ventilation. If the motor is not properly ventilated, overheating can occur and cause early motor failure.
  2. INSULATION: Use a “Megger” periodically to ensure that the integrity of the winding insulation has been maintained. Record the Megger readings. If winding resistance to ground is less than 1.5 Meg-ohms consult the local authorized service shop before reenergizing the motor.
  3. ELECTRICAL CONNECTIONS: Check all electrical connectors to be sure that they are tight.

LUBRICATION & BEARINGS:

The lubricating ability of grease (over time) depends primarily on the type of grease, the size of the bearing, the speed at which the bearing operates and the severity of the operating conditions. Longer bearing life can be obtained if the listed recommendations are followed:
NOTE: If lubrication instructions are provided on the motor nameplate, the nameplate instructions will supersede these instructions. Motors marked “Permanently Lubricated” do not require additional service.

CAUTION: BEARING / MOTOR DAMAGE WARNING
Lubricant should be added at a steady moderate pressure. If added under heavy pressure bearing shield(s) may collapse. Over greasing bearings greatly increases bearing friction and can cause premature bearing and/or motor failure.

GREASE TYPE (unless nameplate states otherwise):
Nameplate Ambient Temperature between -30°C (-22°F) to 65°C (150°F) inclusive: Recommended grease for standard service conditions is Mobil Polyrex ® EM. Equivalent and compatible greases include: Texaco Polystar RB, Rykon Premium

2, Pennzoil Pen 2 Lube, Chevron SRI & Mobil SHC 100.

Nameplate Ambient Temperature below -30°C (-22°F): Special low temperature grease is recommended, such as Aeroshell 7 or Beacon 325 for ball bearings and Mobil SHC 100 for roller bearings.

Nameplate Ambient Temperature above 65°C (150°F): Dow Corning DC44 or equivalent, a special high temperature grease is required. Note that Dow Corning DC44 grease does not mix with other grease types.

BEARING OPERATING TEMPERATURE:
CAUTION: HOT SURFACE
The external surface temperature of the end shield (bracket) bearing hub may reach 100° C (212° F) during normal operation. Touching this surface may cause discomfort or injury. Surface temperatures should only be measured with suitable instruments and not estimated by hand touch.

For RTD settings see Table 3-7.

LUBRICATION INTERVALS: (For motors with regreasing provisions)

Eq. 4.2 Lubrication Interval = [(Table 4-1) hrs] x [Interval Multiplier (Table 4-2)] x [Construction Multiplier (Table 4-3)] Table 4-1 Lubrication Intervals (Hours) These values are based on average use.

NEMA / [IEC] Frame Size| Operating Speed – RPM (See Table 3.4 for Maximum Operating Speed)
---|---
<7200| <5400| <4500| <3600| <1800| <1200
56-180     [80-110]| 2500 Hrs.| 4000 Hrs| 5000 Hrs| 6000 Hrs.| 17000 Hrs.| 20000 Hrs.
210-250 [130-160]|  | 2500 Hrs| 4000 Hrs| 5000 Hrs.| 12000 Hrs.| 16000 Hrs.
280          [180]|  | 2000 Hrs| 3000 Hrs| 4000 Hrs.| 10000 Hrs.| 14000 Hrs.
320          [200]|  |  | 2000 Hrs| 3000 Hrs.| 9000 Hrs.| 12000 Hrs.
360          [225]|  |  | 1500 Hrs| 2000 Hrs.| 8000 Hrs.| 10000 Hrs.
400-440 [250 – 280]|  |  |  | 1500 Hrs.| 4000 Hrs.| 7000 Hrs.

440       [>280]|  |  |  | 1000 Hrs.| 3000 Hrs.| 5000 Hrs.

Seasonal Service: If motor remains idle for more than six months, Lubricate at the beginning of the season, then follow lubrication interval.
Do not exceed maximum safe operating speed Table 3-4 without manufacturer’s approval

Table 4-2 Service Conditions
Use highest level Multiplier: Maximum Ambient Temperature and Contamination are independent factors

Severity of Service| Maximum Ambient Temperature| Atmospheric Contamination| Multiplier
---|---|---|---
Standard| Less than 40° C (104° F)| Clean, Slight Corrosion, indoors, less than 16 hrs per day|

1.0

Severe| Above 40° C (104° F) to 50° C| Moderate dirt or Corrosion or outdoors or more than 16 hrs per day|

0.5

Extreme| Greater than 50° C     or Class H Insulation| Severe dirt or Abrasive dust or Corrosion|

0.2

Table 4-3 Construction Multiplier

Construction Multiplier
Angular Contact or Roller Bearing 0.5
Vertical Motor 0.5
All others 1.0

Table 4-4 Relubrication Amounts

Frame Size Volume
NEMA IEC
48-56 80
143-145 90
182-184 110
213-215 130
254-256 160
284-286 180
324-326 200
364-365 225
404-405 250
444-449 280
>449 >280

For regreasing while operating multiply volume by 125%.

LUBRICATION PROCEDURE:
(For Motors with Regreasing Provisions)

CAUTION: BEARING DAMAGE WARNING
Added grease must be compatible with the original equipment’s grease. If a grease other than those stated in 4.2.1 is to be utilized contact the motor manufacturer. Nameplate information supersedes section 4.2.1 (GREASE TYPE). New grease must be free of dirt. Failure to follow these instructions and procedure below may result in bearing and/or motor damage.

For an extremely dirty environment, contact the motor manufacturer for additional information.

LUBRICATION PROCEDURE:

  1. Clean the grease inlet plug or zerk fittings prior to regreasing.

  2. (If present) Remove grease drain plug and clear outlet hole blockage.
    CAUTION: GREASE DRAIN PLUGGED:
    Old grease may completely block the drain opening and must be mechanically removed prior to regreasing. Forcing a blocked drain open by increased greasing pressure may collapse bearing shields and / or force excess grease through the bearings and into the motor.

  3. Add grease per Table 4-4

  4. Re-install grease inlet and drain plugs (if removed).
    WARNING: EXPLOSION HAZARD
    Do NOT energize a Hazardous Locations motor without all grease fittings properly installed.

EXAMPLE: LUBRICATION
Assume – NEMA 286T (IEC 180), 1750 RPM Vertical motor driving an exhaust fan in an ambient temperature of 43° C and the atmosphere is moderately corrosive.

  1. Table 4-1 list 10,000 hours for standard conditions.
  2. Table 4-2 classifies severity of service as “Severe” with a multiplier of 0.5.
  3. Table 4-3 lists a multiplier value of 0.5 for “Vertical”
  4. (Eq. 4.2) Interval = 10,000 hrs x 0.5 x 0.5 = 2500 hrs
    Table 4-4 shows that 1.5 in 3 of grease is to be added.
    Relubricate every 2,500 hrs of service with 1.5 in 3 of recommended grease.
TROUBLE-SHOOTING

WARNING: READ INSTRUCTIONS:
Before trouble-shooting a motor, carefully read and fully understand the warnings, cautions, & safety notice statements in this manual.

WARNING: Hazardous Locations Motor Repair:
Motors nameplated for use in Division 1 Hazardous Locations can only be disassembled, modified or repaired by the plant of manufacturer or a facility that is Listed under UL’s category “Motors and Generators, Rebuilt for use in Hazardous Locations”. Failure to follow these instructions could result in serious personal injury, death and/or property damage

CAUTION: DISASSEMBLY APPROVAL REQUIRED:
Motor disassembly must be performed by a party approved by the motor manufacturer. To disassemble the motor without approval voids the warranty.

GENERAL TROUBLE-SHOOTING WARNINGS

  1. DISCONNECT POWER TO THE MOTOR BEFORE PERFORMING SERVICE OR MAINTENANCE.
  2. Discharge all capacitors before servicing motor.
  3. Always keep hands and clothing away from moving parts.
  4. Be sure required safety guards are in place before starting equipment.
  5. If the problem persists contact the manufacturer.

Motor Trouble-shooting Cause / Corrective Action – Table 4-5

  Issue: Likely Cause: Corrective Action:
  Motor fails to start upon initial installation:
    A.) Supply voltage is too low or is severely unbalanced (one phase is
low or missing). (1) Check power supply fuses (2) Match motor lead wiring to

nameplate connection diagram and supply voltage (3) Ensure that steady state supply voltage at motor terminals is within limits (see section 3.4.1.3). Correct as needed (4) Obtain correct motor to match actual supply voltage.
 |  | B.)| Motor leads are miswired at conduit box.
 |  | C.)| Driven load exceeds motor capacity| (1) Verify that motor & load turn freely (2) Disconnect motor from load & ensure motor turns freely. Note: Roller bearings make noise when motor is uncoupled and shaft is rotated (3) Verify that motor starts when disconnected from load (4)

Remove excessive / binding load if present.

 |  | D.)| Load is jammed.
 |  | E.)| Fan guard is bent and making contact with fan| Replace fan guard & fan (if blades are damaged)
 |  | F.)| VFD with power factor capacitors installed| Remove power factor correction capacitors if equipped
 |  | G.)| VFD with motor neutral lead grounded| Ensure that motor neutral lead is ungrounded
 |  |

H.)

|

VFD programmed incorrectly

| (1) Repeat checks listed above (2) Verify that VFD current limit and starting boost are set correctly (5) Double-check motor and feedback parameter settings and VFD permissives (6) Repeat autotune (for vector drives) procedure (7) Consult

VFD supplier.

 | Motor has been running, then slow down, stalls, or fails to restart:
 |  | A.)| Supply voltage has drooped or has become severely unbalanced| (1) Replace fuse or reset circuit breaker. Allow motor to cool down before resetting manual protector on motor. Warnings – See section 1.1 for automatic and manual reset protector warnings (2) Verify that rated and balanced supply voltage has been restored before restarting motor. Measure voltage during restart. Ensure that steady state supply voltage at motor terminals is within limits (see section 3.4.1.3).
 |  | B.)| Motor is overloaded| (1) Verify that motor & load turn freely. Repair binding components as needed (2) Reduce driven load to match motor capacity or increase motor size to match load requirements.
 |  | C.)| Motor bearings are seized
 |  | D.)| Load Is jammed.
 |  | E.)| VFD will not restart motor after tripping| (1) Check fault codes on VFD and follow VFD troubleshooting procedures (2) Verify that VFD input voltage is balanced and within limits (3) Remove excessive mechanical load if present.
 |  | F.)| Capacitor failure on single phase motor (if equipped)| Warning: Potential Shock Hazard: Contact service shop to check capacitor.
 | Motor takes too long to accelerate:
 |  | A.)| Motor leads are not connected correctly| Match motor lead wiring to nameplate diagram.
 |  | B.)| Supply voltage has drooped or become severely unbalanced.| (1) Ensure that steady state supply voltage at motor terminals is within limits (see section 3.4.1.3). Correct as needed (2) Obtain correct motor to match actual supply voltage.
 |  | C.)| Load exceeds motor capability| Determine correct motor size and contact motor representative to obtain replacement motor.
 |  | D.)| Faulty start capacitor (Single Phase)| Motor may be too small for load. Record acceleration time. Start capacitors may fail if acceleration time exceeds 3 seconds.
 |  | E.)| Mechanical Failure| (1) Check to make sure motor & load turn freely (2) Disconnect motor from load & ensure motor turns freely
 | Motor rotates in the wrong direction:
 |  | A.)| Incorrect wiring connection at motor| [Single Phase] Reconnect motor according to wiring schematic provided.      Note: Some motors are non- reversible
 | [Three Phase] Interchange any two power supply (phase) leads.
 | Motor overheats or overload protector repeatedly trips
 |  | A.)| Driven Load is excessive| (1) If motor current exceeds nameplate value, ensure that driven load has not increased. Correct as needed. (2) If new motor is a replacement, verify that the rating is the same as the old motor. If previous motor was a special design, a general purpose motor may not have the correct performance.
 |  | B.)| Ambient temperature too high| Most motors are designed to operate in an ambient up to 40 °C. (See section 4.2.2 Hot Surface Caution)
 |  | C.)| Motor cooling fins and/or vent openings blocked| Remove foreign materials – clear vent openings, fan guard air inlets and frame fins (TEFC motors)
 |  | D.)| Insufficient Air Flow| TEAO (Totally Enclosed Air Over) motors: Measure airflow next to motor surface and obtain minimum requirements from motor manufacturer.
 |  | E.)| Motor is started too frequently| See section 3.4.5.3
 |  | F.)| Supply voltage too low, too high, or unbalanced| (1) Ensure that steady state supply voltage at motor terminals is within limits (see section 3.4.1.3) Correct as needed (2) Reconnect motor per input voltage (3) Obtain correct motor to match power supply.
Motor Vibrates|
 | A.)| Motor misaligned to load.| Realign load|
 | B.)| Load out of balance (Direct drive application)| (1) Ensure that load is dynamically balanced: (2) Remove motor from load and inspect motor by itself. Verify that motor shaft is not bent. Rule of thumb is 0.002”

runout for shafts extension lengths up to 3.00”. Add 0.0005” per every additional inch of shaft length beyond 3.00”.

|
 | C.)| Uneven tension on multiple belts| Mixing new with used belts. Replace multiple belt applications with a complete set of matched belts.|
 | D.)| Driven load operating at resonant point / natural frequency.| (1) De- energize motor and record vibration as load coasts from 100% speed to 0 RPM. If vibration drops immediately, vibration source is electrical. If levels do not drop immediately, source is mechanical (2) Redesign system to operate below the resonant point (3) On VFD-driven loads, program skip frequencies to bypass resonant points (4) Increase carrier frequency to obtain <3% THD current (5) On variable torque loads reduce volts/hertz below base speed.|
 | E.)| VFD torque pulsations| (1) Adjust VFD to obtain <3% THD current @ rated motor current (2) Adjust VFD stability for smooth operation. Vector drives may be unstable at light load.|
 | F.)| Motor miswired at terminal box| Match motor lead wiring to nameplate connection diagram.|
 | G.)| Uneven, weak or loose mounting support.| Shim, strengthen or tighten where required.|
 | H.)| Motor bearings defective| Test motor by itself. If bearings are bad, you will hear noise or feel roughness. Roller bearings are normally noisy when operated without load. If sleeve bearing, add oil per nameplate instructions. For motors with regreasing provisions, add grease per relubricating instructions (see section 4.2.3). If noise persists contact

warranty service.

|
 | I.)| Motor out of balance| Disconnect from load. Set motor on rubber pads on solid floor. Secure a ½ height key in shaft keyway and energize from balanced power supply @ rated voltage. Record vibration levels and compare with appropriate standards. If excessive vibration persists contact motor manufacturer.|
Bearings repeatedly fail.

 |

A.)

|

Load to motor may be excessive or unbalanced

| (1) If belt drive check system per section 3.3.4. (2) Other than belting, check loading on motor shaft. An unbalanced load will also cause the bearings to fail. (3) Check runouts of mating components, such as a C-face and pump flange.
 | B.)| Bearings contaminated.| Motor enclosure not suitable for environment. Replace with correct enclosure construction
 | C.)| Incorrect grease or bearings for ambient extremes.| See section 4.2.1
 | D.)| VFD bearing damage| Ground brush, common mode filter, or insulated bearings must be added. Contact motor manufacturer.
Motor, at start up, makes a loud rubbing, grinding, or squealing noise.
 | A.)| Contact between rotating and stationary components| Belt squeal during across the line starting is normal: (1) Verify that supply voltage is within limits (see section 3.4.1.3). (2) Ensure that motor lead wiring matches nameplate connection diagram: (3) Isolate motor from load. (4) To locate point of contact turn motor shaft by hand. (5) If point of contact is not located contact

motor service shop.

Start capacitors repeatedly fail.
 | A.)| The motor acceleration time is too long| Motor may be too small for load. Record acceleration time. Start capacitors may fail if acceleration time exceeds 3 seconds.
 | B.)| Motor is being started too frequently| Excessive starting will damage motor capacitors. Contact motor manufacturer if

motor is started more than 20 times/hour or if acceleration time exceeds 3 seconds.

 | C.)| Motor voltage low| Verify that voltage at the motor terminals is within limits (see section 3.4.1.3).
 | D.)| Defective start switch inside motor| Motor internal switch failure overheats start capacitor. Contact service shop or motor manufacturer.
Run capacitor fails.
 | A.)| High ambient temperature| Verify that the ambient does not exceed motor’s nameplate value
 | B.)| Input voltage exceeds limit| Verify that voltage to the motor terminals is within limits (see section 3.4.1.3).
 | C.)| Power surge to motor (caused by lightning strike or other high transient voltage).| If a common problem, install surge protector.

Customer Service

MARATHON ELECTRIC
Contact Motor Customer Service at:
Phone: 715-675-3311
www.marathonelectric.com

MARATHON logo

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

MARATHON User Manuals

Related Manuals