legrand DPX31600 Electronic Circuit Breaker Instruction Manual
- June 12, 2024
- Legrand
Table of Contents
DPX³ 1600 S10
Instruction Manual
DPX31600 Electronic Circuit Breaker
- Indications led for protection status
- Navigation button
- Setting button
- Mechanical trip button
- Battery compartment
- Display LCD
- Mini USB port (type B)
- Logic selectivity port (4 210 78)
- Serial communication port RS485/EMS and auxiliary power supply (4 210 75 – 4 238 90 – 4 210 83)
- External neutral connexion port (for 3P breakers without measurement function)
BATTERIES INSERTION
If battery powered the display switch off after 10 s if not used. In case of low battery it add this report. At the end of life cycle, process the included batteries according to the EU directive 2006/66 CE about the batteries, accumulators and relative wastes.
PROTECTIONS SETTING
Factory settings
r| tr| MemT| sd| tsd| i| g| tg| N
1ln| 3s| OFF| 10Ir| 400ms (t=k)| OFF| 1ln| 80ms| 100%
SETTING WITH BUTTONS
Isd=xln if Ir=OFF
150% not possible if Ir>66,7% In or Ir=OFF
50% not possible if Ir<0,4% In or Ir=OFF
****200% not possible if Ir>50% In or Ir=OFF
For additional functions, as diagnostic test, advanced protection setting,
intervention curve visualization and report download, it’s necessary connect
via USB with PC (download software Power Control Station from e-catalog) or
with dongle-key bluetooth (0 283 10).
SERVICE SIGNALS
“Wait”:
It appears every time you change a threshold for intervention. The writing
is flashing and disappears after 4s last time you pressed a button control (+
/ -).
” Ok “:
It appears every time you store a new threshold for intervention. Setting and
navigation possible. Only navigation possible. The mechanical seal on
transparent cover does not prevent the setting by Software/app.
SETTINGS BY USB
|
---|---
r| tr| MemT| sd| tsd| i| g| tg| N
| ON/OFF| ON/OFF| ON/OFF| ON/OFF| ON/OFF| ON/OFF
| min| 0,2ln| 40ms| –| 1.5Ir| 40ms| 2In| 0,2ln| OFF| 50% (Ir,Isd,Ii)
max| ln| 30s| –| 10Ir| 480ms| 15In| ln| 1s| 200% (Ir,Isd,Ii)
| 1A| 40ms (@6Ir)| ON/OFF| 1A| | 1A| 1A| | OFF; 50%: Ir 0,4 In
(**); 100%;
150%: Ir 66.7% In
(*);
200%: Ir 50% In
(**);
Isd=xln if Ir=OFF
150% not possible if Ir>66,7% In or Ir=OFF
50% not possible if Ir<0,4% In or Ir=OFF
****200% not possible if Ir>50% In or Ir=OFF The protections could be enabled
by Software PCS (refer to the user guide). Once the parameters have been set,
password is required. Parameters setting by Software or app disable a further
modification by buttons.
A further setting it’s allowed only by SW or app using the password.
In case of password loss, it’s possibile reset the protections to the factory
configuration following the user guide procedure.
Protection unit trip test
DISPLAY BACKLIGHT
In service – Self-feeding with TA Out of service – Power supply with battery With external power supply USB (PC, dongle, powerbank) DESCRIPTIONS OF PROTECTIONS AND ADDITIONAL FUNCTIONS RELATED TO THE PROTECTION UNIT SUPPLY STATUS. IN CASE OF SELF-SUPPLY, ALL PROTECTION FUNCTIONS ARE ACTIVE EVEN IF THE GREEN LED IS OFF.
| Function| Power supply| External supply
---|---|---|---
Protection| Ir- tr| |
Isd – tsd| |
Ii| |
Ig – tg| |
N| |
Mem T| |
Measure function| |1|2|3|N| |
U1 U2 U3| |
V1N V2N V3N| |
THDV- THDI- 123- 132| |
Freq.| |
EP-Eq| |
P tot| |
Q tot| |
PF| |
Communication function and logic selectivity| SEL LOG| |
COM EMS/RS485| |
Mem T: Thermal memory
SEL LOG: Logic selectivity
✔ Active function
✘ Function not guaranteed
Function in stand-by if I<35%In, activates for higher currents
INDICATIONS LED
| Double color led
---|---
Indication| Event| Priority
Green led blinking| Setting in process| 1
Red led blinking| I > 1,05 Ir| 2
Red led on| I > 0,9 Ir| 3
Green and Red alternately blinking| T > 90°C| 4
**** Green led on| Protection unit switched on| 5
If more events were at the same time, the signal would be the one with highest
priority. The highest priority is 1.
DESCRIPTION OF EMBEDDED MEASUREMENT FUNCTIONS
I1 I2 I3 | A | Current phase L1 / L2 / L3 |
---|---|---|
IN (4P) | A | Current of neutral |
IG | A | Earth fault current |
U12 U23 U31 (3P) | V | Phase to Phase Voltage |
V1N V2N V3N (4P) | V | Phase voltages |
Freq | Hz | Frequency |
PTot | kW | Three-phase active power (Ptot>0 if A → B) by default (you can reset |
the direction via sw)
QTot| kvar| Three-phase reactive power
PF| | Power Factor
Ep| kWh| Energie Active A → B
Ep| kWh| Energie Active B → A
Eq| kvar h| Reactive Energy A → B
Eq| kvar h| Reactive Energy B → A
THDU12 THDU23 (3P) THDU31| %| Chained Voltage THD
THDV1N THDV2N (4P) THDV3N| %| THD Phase Voltages
THDI THDI2 THDI3 THDIN| %| Current THD
MEM| A – °C| Cause of the last intervention and its value. (Tst indicates that
the last intervention took place for Diagnostic test)
Conformity IEC 61557-12 Edition 2 (10/2018)
PMD Characteristics
Type of characteristic| Example of possible characteristic value|
Other complementary characteristics andere aanvullende functies
Classification of PMD according to 4.3| PMD-x (*)| –
Classification of PMD according to 4.4| DD|
Temperature| K 55| –
Humidity + altitude| Standard conditions| –
Active power or active energy function (if function available) performance
class| 1| –
(*)PMD-III without S and Eap PMD: Power Metering and Monitoring Devices
Characteristics of functions
Function symbols| Function performance class according to IEC
61557-12 (2013-11)| Measurement range| Other complementary
characteristics Andere kenmerken
DPX 3 1600A| I max PMD
In| | 630A| 800A| 1000A| 1250A| 1600A|
630A| 800A| 1000A| 1250A| 1600A
P| 1| 0.5kW
900kW
| 0.5kW
1.15MW
| 0.5kW
1.4MW
| 0.5kW
1.8MW
| 0.5kW
2.3MW
| 750A| 960A| 1200A| 1500A| 1920A
Ib=400A, Un=400V, fn=50Hz
Q V| 2| 0.5kvar 900kvar| 0.5kvar 1.15Mvar| 0.5kvar 1.4Mvar| 0.5kvar
1.8Mvar| 0.5kvar 2.3Mvar| 750A| 960A| 1200A| 1500A| 1920A
Ib=400A, Un=400V, fn=50Hz
S A| –| –| –
E a| 1| 0…9999 GW/h| 750A| 960A| 1200A| 1500A| 1920A
Ib=400A, Un=400V, fn=50Hz
E rV| 2| 0…9999 Gvar/h| 750A| 960A| 1200A| 1500A| 1920A
Ib=400A, Un=400V, fn=50Hz
E apA , E apV| –| –| –
f| 0.02| 50…60 Hz| –
I| 1| 20A
750A| 20A
950A| 20A
1200A| 20A
1500A| 20A
1950A| 750A| 960A| 1200A| 1500A| 1920A
Ib=400A, Un=400V, fn=50Hz
I N| 1| 20A
750A| 20A
950A| 20A
1200A| 20A
1500A| 20A
1950A| 750A| 960A| 1200A| 1500A| 1920A
Ib=400A, Un=400V, fn=50Hz
U(3P), V(4P)| 0.5| U 88…690V| –
P FA| 0.5| | 750A| 960A| 1200A| 1500A| 1920A
Ib=400A, Un=400V, fn=50Hz
P st| –| –| –
P lt| –| –| –
U dip , **V dip| –| –| –
U swl , V swl| –| –| –
U tr , V tr| –| –| –
U int , V int| –| –| –
U nba , V nba| –| –| –
U nb| –| –| –
U h , V h| –| –| –
THD u (3P), THD v (4P)| 5| 110…690V| –
THD-R u (3P), THD-R v (4P)| –| –| –
I h| –| –| –
THD i| 5| 400A 400A 400A 400A 400A 630A 800A 1000A 1250A
1600A| –
THD-R i**| –| –| –
Safety instructions
This product should be installed in compliance with installation rules,
preferably by a qualified electrician. Incorrect installation and use can lead
to risk of electric shock or fire. Before carrying out the installation, read
the instructions and take account of the product’s specific mounting location.
Do not open up, dismantle, alter or modify the device except where
specifically required to do so by the instructions. All Legrand products must
be opened and repaired exclusively by personnel trained and approved by
Legrand. Any unauthorised opening or repair completely cancels all liabilities
and the rights to replacement and guarantees.
Use only Legrand brand accessories.