DMP LT-2742 XR Control Panel User Manual
- June 10, 2024
 - DMP
 
Table of Contents
- DMP LT-2742 XR Control Panel User Manual
 - IDENTIFY PANEL COMPONENTS
 - POWER UP THE CONTROL PANEL
 - ENTER PANEL PROGRAMMER
 - ADJUST COMMUNICATION TYPE
 - ADD AN ANNUNCIATOR
 - ADJUST AN ANNUNCIATOR ADDRESS
 - CONFIGURE SYSTEM OPTIONS
 - ADD AN AREA
 - ADD A WIRELESS FIRE ZONE
 - ADD A WIRED FIRE ZONE
 - STANDARD WALK TEST
 - WIRELESS CHECK-IN TEST
 - FIRE DRILL
 - DIAGNOSTIC MENU
 - CREATE A PROFILE
 - PROGRAM A RELAY
 - Read User Manual Online (PDF format)
 - Download This Manual (PDF format)
 
DMP LT-2742 XR Control Panel User Manual
IDENTIFY PANEL COMPONENTS
1. Identify the following panel components using the panels in front of you, or the on-screen photo of the XR.
- Reset header
 - Programming header
 - Outputs
 - AC Power terminals
 - Cellular pins
 - 1100 Series receiver connection
 - On-board zone terminals
 - Network connection
 - EXP header
 
POWER UP THE CONTROL PANEL
- 
Connect AC power to terminals 1 & 2
Transformer type: 16.5VAC 50VA - 
Connect battery backup to terminals 3 & 4
 - 
Connect alarm bell to terminals 5 & 6
Normal 12VDC is supplied to terminal 5, terminal 6 is ground reference
1/2 W 1K Ohm resistor should be added across the bell circuit for supervision 
ENTER PANEL PROGRAMMER
- Reset the panel using the RESET JUMPER
 - Enter 6653 (PROG) and press CMD
 - Press CMD to navigate through the panel programmer menus:
• Initialization
• Communication
• Network Options
• Device Setup
• Remote Options
• System Reports
• System Options
• Bell Options
• Output Options
• Output Information
• Output Groups
• Status List
• Menu Display
• PC Log Reports • Area Information
• Zone Information
• Stop
• Set Lockout Code
• Feature Upgrade 
ADJUST COMMUNICATION TYPE
- 
Navigate to COMMUNICATION and press a top-row select area
 - 
Press a top-row select area to clear the default ACCOUNT NUMBER
 - 
Enter in an ACCOUNT NUMBER
 - 
Press CMD to navigate to PATH
 - 
Press 1 to program PATH 1
 - 
Press a top-row select area to display the COMMUNICATION types
 - 
Select NET
 - 
Press CMD to navigate to CHECKIN
 - 
Press a top-row select area and select YES
 - 
Press a top-row select area and enter your CHECKIN MINS
 - 
Press a top-row select area and enter your FAIL MINS
 - 
Press CMD to navigate to RECEIVER IP
 - 
Press a top-row select area and enter in the DMP Tech Support receiver IP Address
ê 209.248.148.051 (Port 2001) - 
Press CMD to navigate to PATH
 - 
Press 2 to program PATH 2
 - 
Press a top-row select area to display the
COMMUNICATION TYPES - 
Select CELL
 - 
Press CMD to navigate to CHECKIN
 - 
Press a top-row select area and select YES
 - 
Press a top-row select area and enter your CHECKIN MINS
 - 
Press a top-row select area and enter your FAIL MINS
 - 
Press CMD to navigate to RECEIVER IP
 - 
Press a top-row select area and enter in the DMP Tech Support receiver IP Address
ê 209.248.148.051 (Port 2001) - 
Press CMD to navigate to ADVANCED
 - 
Press the fourth top-row select area
 - 
Press CMD to navigate to SUB CODE
 - 
Press a top-row select area and select YES
 - 
Press CMD to exit COMMUNICATION
 
ADD AN ANNUNCIATOR
- 
Navigate to DEVICE SETUP and press a top-row select area
 - 
Enter a DEVICE NUMBER and press CMD
The valid range for an XR150 panel is 1-8, XR550 is 1-16 - 
Press a top-row select area and enter a DEVICE NAME
 - 
Press CMD to confirm the DEVICE TYPE
 - 
Press CMD to exit DEVICE SETUP
 
ADJUST AN ANNUNCIATOR ADDRESS
- Press and hold the BACK ARROW and CMD for 2 seconds
 - Enter 3577 (INST) and CMD
 - Select KEYPAD OPTIONS (KPD OPT)
 - Press a top-row select area or key to change the keypad address
 - Press CMD to exit KEYPAD OPTIONS
 - Select STOP to save keypad programming
 
CONFIGURE SYSTEM OPTIONS
- Navigate to SYSTEM OPTIONS and press a top-row select area
 - Press CMD to navigate to HOURS FROM GMT
 - Press a top-row select area, enter in the hours from GMT for your location and press CMD
 - Using CMD, navigate to HOUSE CODE
 - Press a top-row select area and enter a house code from 1-50 and press CMD
 - Press CMD to navigate to SEND 16 CHAR NAMES
 - Press the third top-row select area to select NO
 - Press CMD to exit SYSTEM OPTIONS
 
ADD AN AREA
- Navigate to AREA INFORMATION and press a toprow select area
 - Press CMD to navigate to AREA NO
 - Enter an AREA NUMBER and press CMD
 - Press a top-row select area to clear any text and enter in FIRE
 - Exit AREA INFORMATION and navigate to STOP to save changes
 
ADD A WIRELESS FIRE ZONE
Dealer Admin
6. Select the CUSTOMERS tab on the side menu
7. Select a SYSTEM to open the System Information page for that system
8. Select PROGRAMMING
9. Select ZONE INFORMATION
10. Select ADD ZONE
11. Enter a ZONE NUMBER and ZONE NAME
ê Valid wireless zone numbers are 500-599 on an XR150 and 500-999 on an XR550
12. Select the Zone Type drop-down menu and select FIRE
13. Toggle on DMP WIRELESS
14. Enter a SERIAL NUMBER
15. Select SEND ALL CHANGES
Keypad
- 
Reset the panel using the RESET JUMPER
 - 
Enter 6653 (PROG) and press CMD
 - 
Press CMD to navigate to Zone Information and press a top-row select key
 - 
Enter a ZONE NUMBER and press CMD
ê Valid wireless zone numbers are 500-599 on an XR150 and 500-999 on an XR550 - 
Press a top-row select key and enter a ZONE NAME
 - 
Press a top-row select key and select FI (FIRE)
 - 
Press a top-row select key and enter the FIRE BELL OUTPUT
 - 
At the NEXT ZONE? NO YES prompt, select NO to program a wireless zone
 - 
At the DMP WIRELESS? NO YES prompt, select YES and press CMD
 - 
Enter a SERIAL NUMBER and press CMD to navigate to the NEXT ZONE? NO YES prompt
 - 
Navigate to STOP to save programming
 
ADD A WIRED FIRE ZONE
Dealer Admin
- 
Select the CUSTOMERS tab on the side menu
 - 
Select a SYSTEM to open the System Information page for that system
 - 
Select PROGRAMMING
 - 
Select ZONE INFORMATION
 - 
Select ADD ZONE
 - 
Enter a ZONE NUMBER and ZONE NAME
ê Valid wireless zone numbers are 500-599 on an XR150 and 500-999 on an XR550 - 
Select the Zone Type drop-down menu and select FIRE
 - 
Select SEND ALL CHANGES
 
Keypad
- 
Reset the panel using the RESET JUMPER
 - 
Enter 6653 (PROG) and press CMD
 - 
Press CMD to navigate to Zone Information and press a top-row select key
 - 
Enter a ZONE NUMBER and press CMD
 - 
Press a top-row select key and enter a ZONE NAME
 - 
Press a top-row select key and select FI (FIRE)
Press a top-row select key and enter the FIRE BELL OUTPUT - 
At the NEXT ZONE? NO YES prompt, select YES
 - 
Navigate to STOP to save programming
 
STANDARD WALK TEST
- At the keypad, enter 8144 (WALK) to enter the WALK TEST menu
 - Select STD to begin the standard walk test
 - Trip wired and wireless zones to complete the standard walk test
 
WIRELESS CHECK-IN TEST
- At the keypad, enter 8144 (WALK)
 - Select WLS to begin the wireless check-in test
 
FIRE DRILL
- Enter the USER MENU and navigate to the FIRE DRILL? NO YES prompt
 - Press a top-row select key to display the SURE? YES NO prompt
 - Press the top-row select key underneath YES to start the fire drill
 - To end the fire drill either:
• Enter your USER CODE and press CMD
• Enter the USER MENU and navigate to the
ALARM SILENCE? prompt and press a top-row select key 
DIAGNOSTIC MENU
- 
At the keypad, enter 2313 (DIAG) to enter the DIAGNOSTIC MENU
 - 
Press CMD until the keypad displays COMM STATUS and press a top row select area
 - 
Press 1 to test COMMUNICATION PATH 1
 - 
When the signal strength is displayed, select YES to continue the test
• Cellular Communcation Only - 
Press CMD and select STOP to exit the DIAGNOSTIC MENU
 
CREATE A PROFILE
- 
At the keypad, press CMD until the USER MENU? prompt displays
 - 
Select YES and enter 99+CMD to enter the USER MENU
 - 
Using CMD, navigate to PROFILES? and press a toprow select area
 - 
Select ADD and enter 11 to create Profile 11
 - 
Press a top row area to name the profile ACCESS
 - 
Assign ARM/DISARM AREA 2 and press CMD
 - 
Assign ACCESS AREA 2 and press CMD
 - 
Press CMD until DISARM? displays and select YES
 - 
Navigate to DOOR ACCESS and confirm it is set to YES
 - 
Navigate to FIRST ACCESS SCHEDULE and press the third select area to enter the schedule number
for the access schedule - 
LIST will show the schedule names
 - 
Press CMD until PROFILE 11 ADDED is displayed
 - 
Create another profile named MANAGEMENT using Profile 12
 
The instructor will provide settings for this profile
ADD A USER CODE WITH PIN
14. Enter the USER MENU and navigate to the USER CODES? prompt
15. Press a top-row select area to add a USER CODE
16. Select ADD
17. Select the USER NUMBER and press CMD
•  The fourth top row select area will display the lowest available user
number
18. Enter in a 5-digit user code and press CMD
19. Press a top-row select area to add a USER NAME and press CMD
20. Press a top row select area enter 12 to assign PROFILE 12 to this user
•  LIST will display the profile names
21. Press CMD until USER ADDED displays
PROGRAM A RELAY
- 
Remove all power from the panel
 - 
Plug a MODEL 305 relay into the socket for OUTPUT 1
ê Make sure the relay is oriented correctly - 
Connect the MODEL 431 harness to the header between the output sockets
 - 
Connect the POSITIVE leg of the LED to the RED terminal on the panel
 - 
Connect the other leg of the LED to the second ORANGE wire on the harness
 - 
Connect the second GRAY wire to the BLACK terminal on the panel
 - 
Power the panel back up
 - 
Enter the Programmer by entering 6653 (PROG) at the keypad
 - 
Navigate to ZONE INFORMATION and press a toprow select area
 - 
Navigate to settings for ZONE 1
 - 
Program ZONE 1 as a NIGHT type zone in AREA 1
 - 
At the NEXT ZN? prompt, select NO
 - 
Navigate to DISARMED SHORT and press CMD until OUTPUT NO is displayed
 - 
Press a select area to set the output to 1.
 - 
Set the output action to FOLLOW
 - 
Navigate to STOP to save changes and exit the Programmer
 - 
Press the button to trip ZONE 1.
• Notice the output state follows the zone state. 
QUESTIONS
What else would you like to learn about Fire?
NOTES:
Read More About This Manual & Download PDF:
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>