Schneider Electric METSEPM3210 1 or 3 Phase LCD Energy Meter Installation Guide

October 29, 2023
Schneider Electric

Schneider Electric METSEPM3210 1 or 3 Phase LCD Energy Meter

Schneider Electric-METSEPM3210-1-or-3-Phase-LCD-Energy-
Meter

Product Information

PM3200 / PM3210

The PM3200/PM3210 is an energy meter device manufactured by Schneider Electric. This device comes with features like pulse output for remote transfer, energy pulse LED, sealing points, and a display with white backlight. The PM3210 model has cancellation and confirmation features, while the PM3200 model does not. The device has a maximum current of 6A and is equipped with over-counting protection to prevent incorrect configuration or overload.

Product Usage Instructions

Installation:

  1. Download the user manual and other documentation from www.schneider-electric.com by typing “PM3200” in the search field.
  2. Turn off all power supplying the device before working on it.
  3. Always use a properly rated voltage-sensing device to confirm that all power is off.

Usage:

  • The PM3210 model has cancellation and confirmation features while the PM3200 model does not.
  • Use an energy pulse LED to monitor energy consumption.
  • The device has sealing points for added security.
  • The display comes with a white backlight for better visibility.
  • The device has over-counting protection to prevent incorrect configuration or overload.
  • The device has an LCD in power-saving mode when not in use.
  • The alarm/diagnosis feature is active for three hours before going into power-saving mode.

Note: Refer to section 12 of the user manual for more information on the alarm/diagnosis feature.

Installation sheet
You can download user manuals and other documentation at www.schneider- electric.com. Type PM3200 in the search field.

Power meter

  • Instantaneous values (I, In, U, V, PQS, PF, Hz)
  • Import and export values for active, reactive and apparent energy
  • Power/current demand
  • Min/max
  • Multi-tariffs
  • Advanced features (PM3210):
    • THD and peak demand
    • Remote transfer of metered pulses (kWh)
    • Time-stamped alarms (5)

Safety precautions

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

  • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E in the USA or applicable local standards.
  • Turn off all power supplying this device before working on it.
  • Always use a properly rated voltage sensing device to confirm that all power is off.
  • Do not exceed the device’s ratings for maximum limits.
  • Do not use this device for critical control or protection applications where human or equipment safety relies on the operation of the control circuit.
  • Never short the secondary of a voltage transformer (VT).
  • Never open circuit a current transformer (CT).
  • Always use grounded external CTs for current inputs.

Failure to follow these instructions will result in death or serious injury.

  1. Turn off all power supplying this device before working on it.
  2. Always use a properly rated voltage sensing device to confirm that all power is off.

Overview

Schneider Electric-METSEPM3210-1-or-3-Phase-LCD-Energy-
Meter-1

Schneider Electric-METSEPM3210-1-or-3-Phase-LCD-Energy-
Meter-2

  • A. Pulse output for remote transfer (PM3210)
  • B. Energy pulse LED (5000 / kWh)
  • C. Cancellation
  • D. Confirmation
  • E. Up
  • F. Down
  • G. Display with white backlight
  • H. Sealing points
  • I. Sealable covers

Energy pulse LED

Backlight and Error

Schneider Electric-METSEPM3210-1-or-3-Phase-LCD-Energy-
Meter-4

Dimensions

Schneider Electric-METSEPM3210-1-or-3-Phase-LCD-Energy-
Meter-5

Installation

Schneider Electric-METSEPM3210-1-or-3-Phase-LCD-Energy-
Meter-6

Wiring

  • The pulse output on the PM3210 indicates the primary consumption with consideration of transformer ratios.
  • The pulse output on the PM3210 can be directly connected to a 24 V DC (< 30 V DC) input on a Zelio or Twido PLC.
  • For other concentrators, if V DC /Rin > 15 mA, add a resistor Radd = (V DC / 0.01) – Rin Ω

Schneider Electric-METSEPM3210-1-or-3-Phase-LCD-Energy-
Meter-8

 | | |
---|---|---|---
V1, V2, V3, Vn| 2.5 mm2 (14 AWG)| 0.5 N·m (4.4 in·lb)| 8 mm (0.31 in)
S0+, S0-| 2.5 mm2 (14 AWG)| 0.5 N·m (4.4 in·lb)| 7 mm (0.28 in)
I1, I2, I3| 6 mm2 (10 AWG)| 0.8 N·m (7.0 in·lb)| 8 mm (0.31 in)
L1, L2| 6 mm2 (10 AWG)| 0.8 N·m (7.0 in·lb)| 8 mm (0.31 in)

  • A. 250 mA fuses and disconnect switch
  • B. Shorting block
  • C. VT primary fuses and disconnect switch

indicates wiring for a balanced system
Clearly label the device’s disconnect circuit mechanism and install it within easy reach of the operator.
Fuses/circuit breakers must be rated for the installation voltage and sized for the available fault current.
Fuse for neutral is required if the source neutral is not grounded.
Meter requires x/5A or x/1A current transformers.

Schneider Electric-METSEPM3210-1-or-3-Phase-LCD-Energy-
Meter-12 Schneider Electric-
METSEPM3210-1-or-3-Phase-LCD-Energy-Meter-13 Schneider Electric-METSEPM3210-1-or-3-Phase-LCD-Energy-
Meter-14 Schneider Electric-
METSEPM3210-1-or-3-Phase-LCD-Energy-Meter-15 Schneider Electric-METSEPM3210-1-or-3-Phase-LCD-Energy-
Meter-16

Control power

D. 250 mA fuses
E. Control power transformer fuses and disconnect switch. Secondary: 50 VA maximum

L1 and L2 are non-polarized. If using an AC power supply with neutral, connect neutral to the meter’s L2 terminal.
Always use a fuse on L1. Fuse L2 when connecting an ungrounded neutral to the control power.
If using a control power transformer, fuse both primary and secondary sides of the transformer.
The fuses/circuit breakers must be rated for the installation voltage and sized for the available fault current.

Schneider Electric-METSEPM3210-1-or-3-Phase-LCD-Energy-
Meter-18

Display overview

Schneider Electric-METSEPM3210-1-or-3-Phase-LCD-Energy-
Meter-19

  • A. Screen title
  • B. List of screens
  • C. Error/alert indicator
  • D. Cancel and go back to parent screen, Summry screen (display mode) or Setup screen (configuration mode)
  • E. Select a menu item or confirm an entry
  • F. Navigate up, select a setting from a list or increase a number in a numeric setting
  • G. Navigate down, select a setting from a list or decrease a number in a numeric setting
  • H. Values or settings
  • I. Press and hold OK and ESC to enter Configuration mode
  • J. Enter password – default Password
  • K. (High): 0010 (setup and clock); default Password (Low): 0000 (alarms and resets)
  • L. Configuration mode icon

Initial clock setting

Schneider Electric-METSEPM3210-1-or-3-Phase-LCD-Energy-
Meter-20

These instructions only apply when you power up the meter.

Configuration

Schneider Electric-METSEPM3210-1-or-3-Phase-LCD-Energy-
Meter-21

A. PM3210PM3255 only
B. Resets partial energy, energy by tariff and phase energy

Verification

After performing basic configuration, navigate to the real-time data screens and verify that the readings are correct.

Tariffs

A scheduler supports a maximum 4 time segments (Ta, Tb,Tc and Td) for a maximum 4 tariffs (T1, T2, T3 and T4).
You can assign Ta, Tb, Tc or Td to any tariff provided that any adjacent time segment has a different tariff.

Troubleshooting

If the combination of the backlight and the error / alert icon indicates an error or an abnormal situation, navigate to the diagnostics screen and find the diagnostics code (see sections 8-9 for instructions on navigating the display or performing configuration). If the problem persists after following the instructions below, please contact Technical Support.

Code PM3200 PM3210 Description Possibile solution
LCD display not visible. Check and adjust LCD

contrast/backlight setting.
—| | | Push buttons do not function.| Restart the meter by powering off and powering on again.
101, 102| | | Metering stops due to internal error. Total energy consumption is displayed.| Enter the configuration mode and implement Reset Config.
201| | | Metering continues. Mismatch between frequency settings and frequency measurements.| Correct frequency settings according to the nominal frequency of the power system.
202| | | Metering continues. Mismatch between wiring settings and wiring inputs.| Correct wiring settings according to wiring inputs.
203| | | Metering continues. Phase sequence reversed.| Check wire connections and correct wiring settings, if needed.
205| | | Metering continues. Date and time have been reset due to loss of power.| Set date and time.
206| | | Metering continues. Pulse is missing due to overload on energy pulse output.| Check the energy pulse output settings.
207| | | Metering continues. Abnormal internal clock function.| Restart the meter by powering off and powering on again then reset the date and time.

Specifications

Control power

  • AC: 100 – 277 V L-N, 173 – 480 V L-L ± 20%
  • Frequency: 45 – 65 Hz
  • DC: 100 – 300 V
  • Burden:
    • AC: 5 VA
    • DC: 3 W
  • Installation category III

Voltage inputs

  • Wye: 60 – 277 V L-N, 100 – 480 V L-L ± 20%
  • Delta: 100 – 480 V L-L ± 20%
  • Frequency: 50 / 60 Hz ±10%
  • Minimum wire temperature rating required: 90 °C (194 °F)
  • Permanent overload: 332 V L-N or 575 V L-L
  • Impedance: 3 MΩ
  • Measurement category III
  • Burden: 0.2 VA
  • Electromagnetic environment: E2
  • Mechanical environment: M1

Current inputs

  • 1 A or 5 A nominal; requires x/5A or x/1A current transformers
  • Measured current: 20 mA – 6 A
  • Withstand: 10 A continuous, 20 A at 10 sec/hr
  • Minimum wire temperature rating required: 90 °C (194 °F)
  • Impedance: < 1 mΩ
  • Burden: < 0.036 VA at 6 A

Pulse output (PM3210)

  • Type: opto-coupler output for remote transfer
  • IEC62053-31 compatible (S0 format output)
  • 5 – 30 V DC, 1 – 15 mA
  • Pulse width: configurable, 50 ms minimum

Installation

  • Operating temperature: -25 °C (-13 °F) to + 55 °C (131 °F) (K55)
  • Storage temperature: -40 °C (-40 °F) to + 85 °C (185 °F)
  • 5% – 95% RH non-condensing
  • IP40 front panel, IP20 meter body
  • < 3000 m (9842 ft) above sea level
  • Pollution degree 2
  • Double insulated
  • Not suitable for wet locations
  • For indoor use only

GOST 31819.21-2012 GOST 31819.23-2012

PM3200
PM3210

Representative Offices

Authorized suppliers:
Schneider Electric Russia Address: 12/1Dvintsev st., 127018 Moscow,
Russia
Tel.: +7 (495) 777 99 90
Fax: +7 (495) 777 99 92 Schneider Electric Kazakhstan
Address: Dostyk ave 38, Ken Dala
business center, Almaty, Kazakhstan A25D9D1
Тel.: +7 (727) 357 23 57
Fax: +7 (727) 357 24 39

Serial Number Decoding

    A Model number identification code
   B Year of manufacture;

Example: 14 meaning 2014 year

  C| Calendar week;

Example: 11 meaning Week 11

  D| Day of the week;

Example: 1 meaning Monday

  E| The number of product; Example: 010 meaning tenth product

Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it. The following special messages may appear throughout this bulletin or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.

The addition of either symbol to a “Danger” or “Warning” safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.

DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.

Electrical equipment should be installed, operated, serviced and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved.

PowerLogic and Schneider Electric are trademarks or registered trademarks of Schneider Electric in France, the USA and other countries.

  • This product must be installed, connected and used in compliance with prevailing standards and/or installation regulations.
  • If this product is used in a manner not specified by the manufacturer, the protection provided by the product may be impaired.
  • The safety of any system incorporating this product is the responsibility of the assembler/installer of the system.
    As standards, specifications and designs change from time to time, always ask for confirmation of the information given in this publication.

Schneider Electric
35, rue Joseph Monier
CS 30323
F – 92506 Rueil Malmaison Cedex
www.schneider-electric.com

S1B46605-04
© 2019 Schneider Electric. All rights reserved. 01/2019

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Schneider Electric User Manuals

Related Manuals