legrand TS-400 Digital In-Wall Timer Switch Instruction Manual
- June 10, 2024
- Legrand
Table of Contents
TS-400 Digital In-Wall Timer Switch
Instruction Manual InteliSwitch® Digital Time Switch –
120/277VAC (version 2)
Installation Instructions
No: 24164 – 05/20 rev. 1
Catalog Number : TS-400
Country of Origin: Made in China
SPECIFICATIONS
Voltages …………………………………………………… 120/277VAC, 50/60Hz
Load Requirements
@ 120VAC ………………….. 0–800W ballast, LED or Incandescent
@ 277VAC …………………………………….. 0–1200W ballast or LED
@ 125VAC ……………………………………………………………….. 1/6 hp
Time-Out Adjustment ……………………………………….. 5 min. to 12 hours
Time-Out Override …………………..5 min. to 1 hour in 5 min. increments
………………………………. 1 hour to 12 hours in 15 min. increments
Operating Temperature …………………………… 32° to 104°F (0° to 40°C)
Humidity ……………………………………… Rh 5% to 95%, non-condensing
U.S. Patent: 5,540,113,5,804,991
DESCRIPTION AND OPERATION
The InteliSwitch® TS-400 is a digital time switch that automatically turns
lights off after a preset amount of time. The lights can also be turned off
anytime during the timer’s countdown by pushing the ON/OFF button. The TS-400
has four adjustable features: time-out period, time scroll direction, time-out
visual, and audible warnings.
Time-Out Period
The timer can be adjusted to hold lights on for five minutes to 12 hours. The
default setting is 3 hours.See the DELAY switch adjustment to set the length
of the time-out period.
Time Scrolling
The user can manually and temporarily override the time-out period without
changing the DELAY adjustment. The SCROLL adjustment determines whether the
user’s override options decrease from alonger time to a shorter time (scroll
down) or increase from a shorter time to a longer time (scroll up).
To choose the scrolling direction, consider the time-out DELAY setting, and
then whether the usual temporary need will be for more or less time.
Override Operation
Holding the ON/OFF button for longer than 4 seconds causes the timer to scroll
through time increments, starting from the time-out DELAY setting. Releasing
the ON/OFF switch resumes the countdown from that point. The minimum override
setting is 5 minutes, maximum 12 hours. The timer resets automatically to the
time-out DELAY setting when the countdown runs out or the ON/OFF button is
pushed.
Visual (Flash) Option
If this option is on there are two occasions when the controlled lights flash.
They flash one time when the countdown reaches 5 minutes and twice when the
countdown reaches 1 minute.
Audible (Sound) Option
If this option is on, the timer beeps every 5 seconds during the last minute
of the time-out period.
Timer Countdown
Since the time-out period can be set for 5 minutes to 12 hours, the time is
displayed in two different ways. For a countdown of less than an hour, the
display shows minutes:seconds. The seconds count down. For a countdown of more
than an hour, the display shows hours:minutes, the colon flashes every
second.
INSTALLATION
-
Connect the existing wires to the switch terminals.
• Hot to Line
• Load to Load
• Ground to Ground
• Signal Wire to Neutral. In case of replacement or retrofit when no neutral is present, Signal Wire to Ground. -
Attach the time switch to the wall by mounting it in the wall box with 2 mounting screws provided.
-
Turn on power to the time switch
-
7-15 seconds after power is supplied to the time switch, it will be ready to function. The time switch beeps and the word OFF appears in the display. Push the ON/OFF switch to activate the lights. The timer begins its countdown. Push the ON/OFF switch during countdown to turn the lights off.
-
Select feature settings using the Switch Adjustment procedures.
-
Install cover plate.
WARNING: TURN THE POWER OFF AT THE CIRCUIT BREAKER BEFORE WIRING.
WIRING
Single-switch Wiring Three-way Wiring
When using a three-way application, lights may be turned on from either
switch, but can only be turned off at the switch that turned them on.
Insert or wrap wire as
shown and tighten screw in the clockwise direction. *Signal Wire (Blue with White Stripe) connects to Neutral. In
case of replacement or retrofit when no neutral is present, Signal Wire can
connect to Ground.
SWITCH ADJUSTMENT
Enter Settings Mode by pressing the Calibration Button (located on the left, behind the faceplate).
- If no input occurs within four seconds the display flashes then moves to the next setting.
- Press the Calibration Button to view the settings without making changes.
- Press the ON/OFF button within four seconds to change the setting.
DELAY: 5 min. to 12 hr.
DELAY sets the time-out period. The selections begin at the currently set
time (3 hours, default). When the time is less than an hour, the time
increases by 5 minutes each time you press the ON/OFF button.
When the time is more than an hour, it increases by 15 minues. When the
selection passes 12 hours, it restarts the selection scrolling at 5 minutes.
SCROLL: Up or Down (dn)
To have the user’s time override options decrease from a longer time to a
shorter time, set Scroll for dn (down). To increase from a shorter time to a
longer time, set Scroll for UP.
FLASH: ON or OFF
SOUND: ON or OFF
When the setting selection is complete the unit will either:
- Beep once and display END if the calibration button is being held; release the button to continue.
- Beep three times while it displays END. This gives you a chance to press the ON/OFF button to restart the setting procedure.
If you don’t press either button within three seconds, the unit exits the Settings Mode and resumes its previous state.
TROUBLESHOOTING
Lights will not turn on:
- Verify that the ground wire is tightly secured.
- If lights still do not go on, call 800.879.8585 for technical support.
Lights will not turn off:
-
Do the lights turn off when you press the ON/OFF button?
• If yes, check that the time-out period is set to the correct time-out. If the time-out period is adjusted to maximum, the lights will remain ON for 12 hours.
• If no, call 800.879.8585 for technical support. -
To test if the unit is operating properly, set the time-out period to minimum. Lights should turn off after five minutes.
-
If lights still do not turn off, call 800.879.8585 for technical support.
Re-adjusting the Time-out Period:
To re-adjust the time-out period, set the new amount in the DELAY prompt of
the Switch Adjustments. If this is done while the timer is counting down a
prior setting, the new setting will not be recognized until the present
countdown has expired or the timer is turned OFF and ON again.
ORDERING INFORMATION
Catalog Number | Description |
---|---|
TS-400 | Digital Time Switch 120/277VAC, 50/60Hz |
TP26 | Cover plate for single-gang box |
TP262 | Cover plate for double-gang box |
TP263 | Cover plate for double-gang box with switch option |
TS-400 and cover plates are available in White (-W), Light Almond (-LA), Gray (-G), Black (-B), and Ivory (-I).
WARRANTY INFORMATION
Wattstopper warranties its products to be free of defects in materials and workmanship for a period of five (5) years. There are no obligations or liabilities on the part of Wattstopper for consequential damages arising out of, or in connection with, the use or performance of this product or other indirect damages with respect to loss of property, revenue or profit, or cost of removal, installation or reinstallation.
No. 24164 – 05/20 rev. 1
© Copyright 2020 Legrand All Rights Reserved.
800.879.8585
www.legrand.us/wattstopper