DELTA DVP04DA-H2 Analog Output Module Instruction Manual
- June 10, 2024
- Delta
Table of Contents
- DELTA DVP04DA-H2 Analog Output Module
- Introduction
- Specifications
- Other Specifications
- Control Registers
- parameter Latched
- 0
- 1
- 6| H’4038| ╳| R/W| CH1 output value|
- 7| H’4039| ╳| R/W| CH2 output value
- 8| H’403A| ╳| R/W| CH3 output value
- 9| H’403B| ╳| R/W| CH4 output value
- 18| H’4044| ○| R/W| Adjusted OFFSET value of CH1| Range of OFFSET at CH1 ~
- 19| H’4045| ○| R/W| Adjusted OFFSET value of CH2
- 20| H’4046| ○| R/W| Adjusted OFFSET value of CH3
- 21
- 24| H’404A| ○| R/W| Adjusted GAIN value of CH1| Range of GAIN at CH1 ~ CH4:
- 25| H’404B| ○| R/W| Adjusted GAIN value of CH2
- 26| H’404C| ○| R/W| Adjusted GAIN value of CH3
- 27
- 30
- 31
- 32
- 33
- 34
- 35 ~ #48| For system use.
- Adjusting D/A Conversion Curve
- Documents / Resources
DELTA DVP04DA-H2 Analog Output Module
Warning
- DVP04DA-H2 is an OPEN-TYPE device. It should be installed in a control cabinet free of airborne dust, humidity, electric shock and vibration. To prevent non-maintenance staff from operating DVP04DA-H2, or to prevent an accident from damaging DVP04DA-H2, the control cabinet in which DVP04DA-H2 is installed should be equipped with a safeguard. For example, the control cabinet in which DVP04DA-H2 is installed can be unlocked with a special tool or key.
- DO NOT connect AC power to any of I/O terminals, otherwise serious damage may occur. Please check all wiring again before DVP04DA-H2 is powered up. After DVP04DA-H2 is disconnected, Do NOT touch any terminals in a minute. Make sure that the ground terminal on DVP04DA-H2 is correctly grounded in order to prevent electromagnetic interference.
Introduction
- Model Explanation & Peripherals
- Thank you for choosing Delta DVP series PLC. The data in DVP04DA-H2 can be read or written FROM/TO instructions given by the program of DVP-EH2 series MPU. The analog signal output module receives 4 groups of 12-bit digital data from PLC MPU and converts the data into 4 points of analog signals for output in either voltage or current.
- You can select voltage or current output by wiring. Range of voltage output: 0V ~ +10V DC (resolution: 2.5mV). Range of current output: 0mA ~ 20mA (resolution: 5μA).
- Product Profile (Indicators, Terminal Block, I/O Terminals)
- DIN rail (35mm)
- Connection port for extension modules
- Model name
- POWER, ERROR, D/A indicator
- DIN rail clip
- Terminals
- Mounting hole
- I/O terminals
- Mounting port for extension modules
External Wiring
- Note 1: When performing analog output, please isolate other power wirings.
- Note 2: If the ripples at the loaded input terminal are too significant that causes noise interference on the wiring, connect the wiring to 0.1 ~ 0.47μF 25V capacitor.
- Note 3: Please connect the terminal on both the power modules and DVP04DA-H2 to the system earth point and ground the system contact or connect it to the cover of power distribution cabinet.
- Note 4: If there is much noise, please connect the terminal FG to the ground terminal.
- Warning: DO NOT wire empty terminals .
Specifications
Digital/Analog (4D/A) module | Voltage output | Current output |
---|---|---|
Power supply voltage | 24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%) | |
Analog output channel | 4 channels/module | |
Range of analog output | 0 ~ 10V | 0 ~ 20mA |
Range of digital data | 0 ~ 4,000 | 0 ~ 4,000 |
Resolution | 12 bits (1LSB = 2.5mV) | 12 bits (1LSB = 5μA) |
Output impedance | 0.5Ω or lower | |
Overall accuracy | ±0.5% when in full scale (25°C, 77°F) |
±1% when in full scale within the range of 0 ~ 55°C, 32 ~ 131°F
Responding time| 3ms × the number of channels
Max. output current| 10mA (1KΩ ~ 2MΩ)| –
Tolerable load impedance| –| 0 ~ 500Ω
Digital data format| 11 significant bits out of 16 bits are available; in 2’s
complement.
Isolation| Internal circuit and analog output terminals are isolated by
optical coupler. No isolation among analog channels.
Protection| Voltage output is protected by short circuit. Short circuit
lasting for too long may cause damage on internal circuits. Current output can
be open circuit.
Communication mode (RS-485)
| Supported, including ASCII/RTU mode. Default communication format: 9600, 7, E, 1, ASCII; refer to CR#32 for details on the communication format.
Note1: RS-485 cannot be used when connected to CPU series PLCs.
Note2: Use extension module wizard in ISPSoft to search or modify the control register (CR) in the modules.
When connected to DVP-PLC MPU in series| The modules are numbered from 0 to 7 automatically by their distance from MPU. No.0 is the closest to MPU and No.7 is the furthest. Maximum 8 modules are allowed to connect to MPU and will not occupy any digital I/O points.
Other Specifications
Power supply
Max. rated power consumption| 24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%),
4.5W, supplied by external power.
Environment
Operation/storage
Vibration/shock immunity
| Operation: 0°C ~ 55°C (temperature); 5 ~ 95% (humidity); pollution degree 2
Storage: -25°C ~ 70°C (temperature); 5 ~ 95% (humidity)
International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC
68-2-27 (TEST Ea)
Control Registers
CR RS-485
parameter Latched
|
Register content
|
b15
|
b14
|
b13
|
b12
|
b11
|
b10
|
b9
|
b8
|
b7
|
b6
|
b5
|
b4
|
b3
|
b2
|
b1
|
b0
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
address
0
|
H’4032
|
○
|
R
|
Model name
| Set up by the system. DVP04DA-H2 model code = H’6401.
The user can read the model name from the program and see if the extension module exists.
1
|
H’4033
|
○
|
R/W
|
Output mode setting
| Reserved| CH4| CH3| CH2| CH1
Output mode: Default = H’0000 Mode 0: Voltage output (0V ~ 10V) Mode 1:
Voltage output (2V ~ 10V)
Mode 2: Current output (4mA ~ 20mA)
Mode 3: Current output (0mA ~ 20mA)
CR#1: The working mode of the four channels in the analog input module. There are 4 modes for each channel which can be set up separately. For example, if the user needs to set up CH1: mode 0 (b2 ~ b0 = 000); CH2: mode 1 (b5 ~ b3 = 001), CH3: mode 2 (b8 ~ b6 = 010) and CH4: mode 3 (b11 ~ b9 = 011), CR#1 has to be set as H’000A and the higher bits (b12 ~
b15) have to be reserved. Default value = H’0000.
6| H’4038| ╳| R/W| CH1 output value|
Range of output value at CH1 ~ CH4: K0 ~ K4,000 Default = K0 (unit: LSB)
7| H’4039| ╳| R/W| CH2 output value
8| H’403A| ╳| R/W| CH3 output value
9| H’403B| ╳| R/W| CH4 output value
18| H’4044| ○| R/W| Adjusted OFFSET value of CH1| Range of OFFSET at CH1 ~
CH4: K-2,000 ~ K2,000
Default = K0 (unit: LSB)
Adjustable voltage-range: -2,000 LSB ~ +2,000 LSB
Adjustable current-range: -2,000 LSB ~ +2,000 LSB
Note: When modifying CR#1, adjusted OFFSET is changed to default.
19| H’4045| ○| R/W| Adjusted OFFSET value of CH2
20| H’4046| ○| R/W| Adjusted OFFSET value of CH3
21
|
H’4047
|
○
|
R/W
| Adjusted OFFSET value of CH4
24| H’404A| ○| R/W| Adjusted GAIN value of CH1| Range of GAIN at CH1 ~ CH4:
K0 ~ K4,000 Default = K2,000 (unit: LSB)
Adjustable voltage-range: 0 LSB ~ +4,000 LSB
Adjustable current-range: 0 LSB ~ +4,000 LSB
Note: When modifying CR#1, adjusted GAIN is changed to default.
25| H’404B| ○| R/W| Adjusted GAIN value of CH2
26| H’404C| ○| R/W| Adjusted GAIN value of CH3
27
|
H’404D
|
○
|
R/W
| Adjusted GAIN value of CH4
CR#18 ~ CR#27: Please note that: GAIN value – OFFSET value = +400LSB ~ +6,000
LSB (voltage or current). When GAIN – OFFSET is small (steep oblique), the
resolution of output signal will be finer and variation on the digital value
will be greater. When GAIN – OFFSET is big (gradual oblique), the resolution
of output signal will be rougher and variation on the
digital value will be smaller.
30
|
H’4050
|
╳
|
R
|
Error status
| Register for storing all error status.
See the table of error status for more information.
---|---|---|---|---|---
CR#30: Error status value (See the table below)
Note: Each error status is determined by the corresponding bit (b0 ~ b7) and there may be more than 2 errors occurring at the same time. 0 = normal; 1 = error.
Example: If the digital input exceeds 4,000, error (K2) will occur. If the analog output exceeds 10V, both analog input value error K2 and K32 will occur.
31
|
H’4051
|
○
|
R/W
|
Communication address
| For setting up RS-485 communication address.
Range: 01 ~ 254. Default = K1
32
|
H’4052
|
○
|
R/W
|
Communication format
| 6 communication speeds: 4,800 bps /9,600 bps /19,200 bps / 38,400 bps /57,600 bps /115,200 bps. Data formats include:
ASCII: 7, E, 1/ 7,O,1 / 8,E,1 / 8,O,1 / 8,N,1 / 7,E,2 / 7,O,2 / 7,N,2 / 8,E,2 / 8,O,2 / 8,N,2
RTU: 8, E, 1 / 8,O,1 / 8,N,1 / 8,E,2 / 8,O,2 / 8,N,2 Default: ASCII,9600,7,E,1(CR#32=H‘0002)
Please refer to✽CR#32 at the bottom of the page for more details.
33
|
H’4053
|
○
|
R/W
|
Return to default; OFFSET/GAIN tuning authorization
| Reserved| CH4| CH3| CH2| CH1
Default = H’0000. Take the setting of CH1 for example:
1. When b0 = 0, the user is allowed to tune CR#18 (OFFSET) and CR#24 (GAIN) of CH1. When b0 = 1, the user is not allowed to tune CR#18 (OFFSET) and CR#24 (GAIN) of CH1.
2. b1 represents whether the OFFSET/GAIN tuning registers are latched. b1 = 0 (default, latched); b1 = 1 (non-latched).
3. When b2 = 1, all settings will return to default values. (except CR#31, CR#32)
CR#33: For authorizations on some internal functions, e.g. OFFSET/GAIN tuning. The latched function will store the
output setting in the internal memory before the power is cut off.
34
|
H’4054
|
○
|
R
|
Firmware version
| Displaying the current firmware version In hex; e.g. version 1.0A is indicated as H’010A.
35 ~ #48| For system use.
Symbols:
○ : Latched (when written in through RS-485 communication);
╳: Non-latched;
R: Able to read data by FROM instruction or RS-485 communication; W: Able to write data by TO instruction or RS-485 communication.
LSB (Least Significant Bit):
For voltage output: 1LSB = 10V/4,000 = 2.5mV. For current output: 1LSB = 20mA/4,000 = 5μA.
- Reset Module (Firmware V4.06 or above): Having connected the external power 24V, write the reset code H’4352 in CR#0, then disconnect and reboot to complete the setup.
- CR#32 Communication Format Setting:
- Firmware V4.04 (and lower): Data format (b11~b8) is not available, ASCII format is 7, E, 1 (code H’00xx), RTU format is 8, E, 1 (code H’C0xx/H’80xx).
- Firmware V4.05 (and higher): Refer to the following table for setup. For new communication format, please take note that modules in the original setting code H’C0xx/H’80xx is to 8E1 for RTU.
b15 ~ b12| b11 ~ b8|
b7 ~ b0
---|---|---
ASCII/RTU
& High/Low Bit Exchange of CRC
| Data Format| Communication Speed
Description
H’0| ASCII| H’0| 7,E,11| H’6| 7,E,21| H’01| 4800 bps
H’8
| RTU,
No High/Low Bit Exchange of CRC
| H’1| 8,E,1| H’7| 8,E,2| H’02| 9600 bps
H’2| –| H’8| 7,N,2*1| H’04| 19200 bps
H’C
| RTU,
High/Low Bit Exchange of CRC
| H’3| 8,N,1| H’9| 8,N,2| H’08| 38400 bps
H’4| 7,O,11| H’A| 7,O,21| H’10| 57600 bps
H’5| 8.O,1| H’B| 8,O,2| H’20| 115200 bps
Ex: To setup 8N1 for RTU (High/Low Bit Exchange of CRC), communication
speed is 57600 bps, write H’C310 in CR #32.
*Note 1. Supports ASCII mode ONLY.
CR#0 ~ CR#34:** The corresponding parameter addresses H’4032 ~ H’4054 are
for users to read/write data by RS-485 communication. When using RS-485, the
user has to separate the module with MPU first.
- Function: H’03 (read register data); H’06 (write 1 word datum to register); H’10 (write many word data to register).
- Latched CR should be written by RS-485 communication to stay latched. CR will not be latched if written by MPU through TO/DTO instruction.
Adjusting D/A Conversion Curve
Voltage output mode
Current output mode
Documents / Resources
|
DELTA DVP04DA-H2 Analog Output
Module
[pdf] Instruction Manual
DVP04DA-H2, DVP04DA-H2 Analog Output Module, Analog Output Module, Output
Module
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>