Simplex 4100+/UT Universal Power Supply Instruction Manual
- June 10, 2024
- Simplex
Table of Contents
4100+/UT Universal Power Supply
Instruction Manual 4100+/UT Universal Power Supply
Jumper Placements, Switch
Settings, and Terminations
Cautions and Warnings
DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED.
Upon unpacking your Simplex product, inspect the contents of the carton for
shipping damage. If damage is apparent, immediately file a claim with the
carrier and notify Simplex.
ELECTRICAL HAZARD – Disconnect electrical power when making any internal
adjustments or repairs. Servicing should be performed by qualified Simplex
Representatives.
STATIC HAZARD – Static electricity can damage components. Therefore,
handle as follows:
- Ground yourself before opening or installing components (use the 553-484 Static Control Kit).
- Keep uninstalled component wrapped in anti-static material at all times.
Introduction
The Universal Power Supply (UPS) consists of two assemblies including a Switcher Assembly (636-341) and a Communicating Power Supply Controller Assembly (565-247). Together, these two assemblies form a power supply which is electrically similar to the Intelligent Power Supply (IPS) previously installed in 4100-Family systems. The UPS has the following features that differ from the IPS.
- 110Ah battery charger.
- NICAD battery charger.
- External battery charger operation.
For further information concerning the UPS, reference field wiring diagrams
841-731 and 841-995.
In This Publication
The following topics are covered in this publication.
Topic | See Page # |
---|---|
Overview | 2 |
Jumper Placements | 5 |
DIP Switch Settings | 7 |
Connections and Terminations | 9 |
Overview
Switcher Assembly
The switcher assembly is the core of the UPS. Operating from a
120/220/240VAC line, via the four place AC connector (see Figure 1), the
switcher converts the AC line voltage to 28.5VDC for system use. It provides
8A maximum continuous current and 4A of current for battery charger use only.
Communicating Power Supply Controller Assembly
The Communicating Power Supply Controller Assembly is attached to the front of
the switcher assembly. With the controller assembly installed, the UPS
provides both 8VDC and 24VDC power and charges system batteries with up to a
110Ah capacity.
Status Monitoring
The UPS monitors and reports the following status information to the
4100Family Master Controller using 4100 communications:
- AC power loss/brownout
- Earth troubles
- Low battery
- Battery disconnected
- Overvoltage/undervoltage conditions
- PMSO/PMSI power supply monitor loop
- Supply Tap Current
Universal Power Supply Figure 1. Universal Power
Supply
Note: Product shown exploded for detailed view
Battery Charger
The UPS battery charger charges the batteries, runs tests to verify
capacity, then provides short circuit protection for the batteries. The
charger can charge batteries of up to 50Ah capacity using the UPS C-Tap.
Batteries with up to 110Ah capacity can be charged if both the B-Tap and the
C-Tap are used.
Every 90 seconds, during normal operation, while the power supply is running
on AC power, the charger tests the charge on the batteries. If the batteries
are over 23.2VDC, a normal battery status is sent to the Master Controller. If
the batteries fall below 22.5VDC, a “BATTERY LOW” Trouble is sent to the
Master Controller. If less than 2VDC is read, a “BATTERY DISCONNECTED” Trouble
is sent to the Master Controller, and the charger is turned OFF.
If after 96 hours of continuous charging, the battery charge current has not
dropped below 459mA (with lead-acid batteries), the power supply reports a
“BATTERY CAPACITY” Trouble and the charger turns OFF. This trouble clears when
the batteries become fully charged. The trouble is reported so that damaged
batteries can be replaced.
Specifications
The UPS requires 6-inches of bay space in a 4100 cabinet. With up to 50Ah
batteries, the UPS provides 8A at 28.5VDC power (Tap A and Tap B). With 110Ah
batteries the UPS provides 4A at 28.5VDC power (Tap A only). Each option
provides 3A at 8VDC for system logic.
Power Harness (See Figure 1)
The power harness connects the switcher to the controller. The RED wire goes
to the “+” connection on the switcher. The BLACK wire goes to the “-”
connection on the switcher. The YELLOW wire goes to the “CHG” connection on
the switcher.
Indicator Functions
The following indicators are present on the Communicating Supply Controller
Assembly. (See Figure 2.)
LED 1: Power LED.
The green “Power ON” LED indicates normal AC power. When this LED is ON, it
does NOT indicate whether the power supply is on batteries or AC, only that
the state of the AC power is “normal.”
LED 2: Trouble LED.
The yellow “Trouble” LED indicates that normal communications with the Master
Controller are not taking place when the supply is configured as a
communicating supply.
Jumper Placements
Jumper Functions
The PROM Configuration Jumpers listed in Table 1 are factory installed and
change only if the PROM type is changed. These jumpers are not
fieldselectable.
JW1-7: PROM Configuration Jumpers.
Table 1. PROM Configuration Jumpers (For Reference Only)
PROM| INSTALLED|
REMOVED
---|---|---
27C64| 1, 2, 5| 3, 4, 6, 7
27C256| 1, 3, 4, 5| 2, 6, 7
27C512| 3, 4, 6, 7| 1, 2, 5
Figure 2. Communicating Power Supply Controller Assembly
P6: Battery Disconnect.
This jumper allows the “NO BATTERY” Trouble to be defeated in systems without
batteries.
IMPORTANT: Do not use this jumper to bypass troubles from a temporarily
disconnected battery.
Jumper P6 is configured in the following manner:
- Position 1-2: Normal Configuration.
- Position 2-3: No Battery Configuration.
P7: Not used.
P10 and P13: Must remain in positions 1-2.
NICAD Battery Charger Adjustment
Position 1-2: Normal operating configuration
Position 2-3: Charger adjustment configuration
Follow Steps 1 through 6 for NICAD batteries only (there are not adjustments
for lead acid batteries).
- Disconnect the batteries.
- Set Jumpers P10 and P13 to Position 2-3.
- Measure the voltage at the battery charge output with respect to 0V.
- Slowly adjust R143 until the voltage reads 25.5 +/- .1 VDC
- Set Jumpers P10 and P13 to Position 1-2.
- Reconnect the batteries.
P16: Earth Detect Jumper.
Jumper P16 enables or disables the Earth Detect feature of the UPS. P16 is
configured in the following manner:
- Position 1-2: Earth Detect Enabled (Default).
- Position 2-3: Earth Detect Disabled.
Jumper Functions
SW1-3 through SW1-6: See Table 2.
SW1-7: This switch configures the battery charger. Position ON enables 50 Ah
battery charging. Position OFF enables 110 Ah battery charging.
Note: With position OFF is selected, the B-Tap is not available for system
power.
SW1-8: Spare.
The eight-position DIP switch SW1 (located on the Communicating Power Supply
Controller Assembly board) identifies the configuration of the power supply.
The various positions of Switch SW1 are described below.
SW1-1: This switch allows retrofit of the IPS. Position ON tells the supply to
act like an IPS in terms of the messages sent to and received from the
4100-Family Master Controller. Place this switch in the ON position (default).
SW1-2: This switch is used for audio applications. Position ON indicates that
amplifiers powered by the “B Tap” must switch to battery when told to do so by
the 4100 Master Controller.
WARNING: B-Tap power is removed on AC fail.
Position OFF indicates that amplifiers should switch to battery when AC is
lost.
Power Supply DIP Switch Settings
The power supply can operate in the following modes shown in Table 2 below:
Table 2. SW1-3 through SW1-6 DIP Switch Settings
DIP Switch Position | **Configuration Interpretation** |
---|---|
3 | 4 |
OFF | ON |
OFF | ON |
OFF | ON |
**** OFF | *** OFF |
NICAD Battery
OFF| OFF*| ON| OFF| Power Supply with Audio (25W Amp)
and Lead-Acid Battery
OFF| OFF*| OFF| ON| Power Supply with Audio (25W Amp)
without Battery Charger
- Requires proper programming selection (6005) Power Supply and charger
Address/Baud Rate DIP Switch SW2
DIP Switch SW2 has eight-positions that are used to set the power supply address and baud rate. The switch is configured in the same manner as the Address/Baud Rate DIP Switches on the other 4100 daughter cards.
SW2-1: Communications baud rate.
ON: 9600 Baud
OFF: 1200 Baud
SW2-2 through SW2-8: Board address, with the LSB (least significant bit) of the address being set by SW2-8.
Table 3. Typical Address 1 and 2 Settings for SW2
LSB……………………… MSB
Address # | 8 | 7 | 6 | 5 | 4 | 3 | 2 |
---|---|---|---|---|---|---|---|
Address 1 | OFF | ON | ON | ON | ON | ON | ON |
Address 2 | ON | OFF | ON | ON | ON | ON | ON |
Note: The OFF (or open) position of the switch is a logic “1”; the ON (or closed) position of the switch is a logic “0.”
Connections and Terminations
Connections and Terminations
The following I/O connections and terminations are available on the
Communicating Supply Controller Assembly. (Refer to Figure 2.)
Table 3. Signal Supervisory Inputs
Connection|
Description
---|---
P1| “A Tap” Signal Supervisory Input. P1 is used to monitor the “A Tap” Signal
Power Harness.
P2| “B Tap” Signal Supervisory Input. P2 is used to monitor the “B Tap” Signal
Power Harness.
P3| “C Tap” Signal Supervisory Input. P3 is used to monitor the “C Tap” Signal
Power Harness.
Note: Default is 733-664 Jumper Plug.
Use Tables 4 through 13 for reference purposes.
Table 4. P4-4100 Communications Interface
Connection|
Description
---|---
P4| P4 is a communications interface with 4100-style communications for use by
the communicating supply. The following connections are available.
P4-1| Common – Communication 0V.
P4-2| Code – Coding Bus (not used by UPS).
P4-3| TXD – Transmit data to system. Open collector with 620 Ohm output
impedance.
P4-4| RXD – Receive data from system. 0 to 28.5VDC input.
Table 5. P5-PMSI Interface
Connection
|
Description
---|---
P5| The PMSI interface allows connection to and control of existing non-
intelligent supplies via the Power Module Supervisory Input. The following
connections are available.
P5-1| 24V Common.
**P5-2| Coil – Open drain output sinks current for battery changeover
relay coil on expansion power supplies. Maximum current of 1 Amp.
****P5-3| PMSI – Input; 100K pullup. Monitors power supply loop.
Normally pulled low by the electrically furthest supply in a “daisy chain.”
P5-4| Not used.
P5-5| Not used.
P5-6**| Not used.
Table 6. P8-Audio Control Interface
Connection|
Description
---|---
P8| P8 is a ten position ribbon cable connector. The signals on this
connector monitor and control amplifiers. The following connections are
available:
P8-2, -4, -6, -8, -10| 24V Common.
P8-1| Music Active – Output, open collector, 150mA maximum.
P8-3| Amp Reset – Output, open collector, 150mA maximum.
P8-5| Amp Has Sw to Backup – Input, 15K pullup, normally held low by
amplifier.
P8-7| Amp Trouble – Input, 15K pullup, normally held low by amplifier.
P8-9| Amp Switch to Battery – Output, open collector, 150mA maximum.
Table 7. P9-Switcher Interface
Connection
|
Description
---|---
**P9| P9 is an eight position flex cable connector. The signals on
this connector are used to monitor and control the 565-341 switcher assembly.
The following connections are available:
P9-2, -4| +24V UPS – Power input, provides power for controller board
and 8V converter.
****P9-3| +24V Main A/D – A/D input. Used by A/D to determine the output
of the switcher portion of the supply.
****P9-6| Power Loss/Brown Out – Comparator input; 2.2K pullup. Normally
high; pulled low by switcher on power loss or brownout.
****P9-8**| Battery Changeover – Output; open collector. Activates relay
coil on switcher board when low for normal AC operation; releases for battery
operation.
Table 8. P11-Current Limit Resistor 2
Connection|
Description
---|---
P11| P11 is the connection to the 2 Ohm current-limiting resistor for the “C”
Tap charger output.
Table 9. P12-Current Limit Resistor 1
Connection
|
Description
---|---
P12| P12 is the connection to the 2 Ohm current- limiting resistor for
the “B” Tap charger output.
Table 10. P14-“A” Tap/8 Volt Output
Connection|
Description
---|---
P14-1| 0V
P14-2| 8V Common
P14-3| “A” Tap output
P14-4| 8V output
Table 11. P15-“B” Tap Output
Connection
|
Description
---|---
P15-1| 0V
P15-2| “B” Tap output
Table 12. P17-“C” Tap Output
Connection
|
Description
---|---
P17-1| 0V (Not Used).
P17-2| “C” Tap output. (Not Used).
Table 13. Terminations
Termination
|
Description
---|---
TB1| Option Interface (Not Available).
TB2| Output Connections. Terminal Block TB2 provides extra connection
points for the “A”, “B”, and “C” Taps. Transient suppression is provided at
the block. The following connections are available on TB2:
TB2-1| 0V.
TB2-2| 0V.
TB2-3| “C” Tap output (Not Used).
TB2-4| “C” Tap output (Not Used).
TB2-5| 0V.
TB2-6| 0V.
TB2-7| “B” Tap output.
TB2-8| “B” Tap output.
TB2-9| 0V.
TB2-10| 0V.
TB2-11| “A” Tap output.
TB2-12| “A” Tap output.
Technical Manuals Online! –http://www.tech-man.com
firealarmresources.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>