simplex S49SVC Ceiling Mount Addressable Speaker User Manual

June 5, 2024
Simplex

simplex logo

*UL,ULC Listed; FM Approved
Datasheet
TrueAlert Addressable Notification Appliances
Ceiling Mount Addressable Speaker Visible (S/V) Notification Appliances**

Introduction

Ceiling mount addressable speaker visible (S/V) notification appliances
Use the Simplex fire alarm control unit (FACU) IDNAC signaling line circuit (SLC) to individually power, address, and control ceiling mount addressable S/V notification appliances. A separate compatible Simplex FACU audio NAC supplies audio. Electronic monitoring of wiring supervision means you can T-tap audio and IDNAC wiring for Class B wiring, reducing wiring costs and wiring distances.
Install ceiling mount addressable S/V notification appliances on a standard 4 in. (101.6 mm) square 2 1/8 in. (53.97 mm) deep electrical box, provided by others, for flush installations. Install on a surface or weatherproof backbox, see Table 8 for surface or weatherproof (WP) installations.
Appliances are available in 400 Hz to 4000 Hz and 200 Hz to 10000 Hz high fidelity models. Select the appliance and cover it separately to simplify the ordering and installation process. Model numbers ending in –BA are assembled in the USA. For more information, refer to datasheet S49SWC-0001.

Figure 1: Ceiling mount addressable S/V notification appliance
Ceiling mount addressable speaker product selection
Table 1: Ceiling mount addressable speaker S/V appliances

Model Description Installation instructions
49SV-APPLC 49SV-APPLC-BA S/V appliance only. If required, select a cover and
surface or WP box separately. 579-1203

Table 2: High fidelity appliances

Model Description Installation instructions
49HFV-APPLC 49HFV-APPLC-BA High fidelity S/V appliance only. If required,
select a cover and surface or WP box separately. 579-1203

Table 3: High candela appliances

Model Description Installation instructions
49SVH-APPLC-O 49SVH-APPLC-CO (Canada only) S/V Appliance Only. Select a cover
and surface or WP box separately 579-1241

Table 5: S/V covers, required when ordering APPLC models

SKU Color Wording
49SVC-CRALT-O Red ALERT
49SVC-CWALT-O White
49SVC-CRBA-O Red FIRE
49SVC-CWBA-O White
49SVC-CRBC-O Red FIRE ALARM
49SVC-CWBC-O White
49SVC-CRBF-O Red FEU/FIRE
49SVC-CWBF-O White
49SVC-CRFEU-O Red FEU
49SVC-CWFEU-O White
49SVC-CRFIRE-O Red FIRE
49SVC-CWFIRE-O White
49SVC-CRS-O Red Simplex logo only
49SVC-CWS-O White

Table 5: S/V covers, required when ordering APPLC models

Model Color Wording
49SVC-CRALT Red ALERT
49SVC-CWALT White
49SVC-CRBA Red FIRE
49SVC-CWBA White
49SVC-CRBC Red FIRE ALARM
49SVC-CWBC White
49SVC-CRBF Red FIRE
49SVC-CWBF White
49SVC-CRFEU Red FEU
49SVC-CWFEU White
49SVC-CRFBL Red FOGO
49SVC-CRFIRE Red FIRE
49SVC-CWFIRE White
49SVC-CRS Red Simplex logo only
49SVC-CWS White
49SVC-CK Black No logo or lettering
  • Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co.

Weatherproof product selection

Table 6: Weatherproof ceiling mount addressable S/V appliances

Model Description Installation instructions

49SVH-APPLC-O

49SVH-APPLC-CO (Canada only)

| S/V Appliance Only. Select a cover and surface or WP box separately| 579-1241

Table 7: S/V covers, required when ordering APPLC-O models

SKU Color Wording
49SVC-CRALT-O Red ALERT
49SVC-CWALT-O White
49SVC-CRBA-O Red FIRE
49SVC-CWBA-O White
49SVC-CRBC-O Red FIRE ALARM
49SVC-CWBC-O White
49SVC-CRBF-O Red FIRE
49SVC-CWBF-O White
49SVC-CRFEU-O Red FEU
49SVC-CWFEU-O White
49SVC-CRFIRE-O Red FIRE
49SVC-CWFIRE-O White
49SVC-CRS-O Red Simplex logo only
49SVC-CWS-O White

Table 8: Surface or WP back boxes

SKU Color Description Installation instructions
49WPBB-SVCR Red Surface or WP back box in red 579-1240
49WPBB-SVCW White Surface or WP back box in white

Table 9: Wire guards and wire guard back boxes

SKU Description
49WGBB-SVCR-O Wire guard back box, ceiling, red, WP
49WG-SVWCR Wire guard, ceiling, red

Ceiling mount S/V specifications

Table 10: Non-weatherproof appliance general specifications

Specification Rating
Dimensions 8 1/8 in. H x 7 1/8 in. W x 3in. D (206 mm x 180 mm x 76 mm)
Environmental 32°F to 120°F (0°C to 49°C); 10% to 93%, non-condensing

at 104°F (40°C)
Connections| Terminal blocks for 18 AWG to 12 AWG (0.82 mm2 to 3.31 mm2); two wires for each terminal for in/out wiring. Use unshielded twisted pair (UTP) for IDNAC and audio wiring.

Table 11: Weatherproof appliance general specifications

Specification Rating
Dimensions 8 1/8 in. H x 7 1/8 in. W x 3in. D (206 mm x 180 mm x 76 mm)


Environmental

| UL/ULC temperature rating, W110 CD/W135 CD/W185 CD: -40°F to 150.8°F (-40°C to 66°C) UL/ULC temperature rating for indoor and uncontrolled wet Public Mode – 110 CD: 32°F to 120°F (0°C to 49°C)
FM temperature rating: -40°F to 120°F (-40°C to 49°C)
UL/ULC humidity range: 95 %, non-condensing at 140°F (60°C)
Connections| Terminal blocks for 18 AWG to 12 AWG (0.82 mm2 to 3.31 mm2); two wires for each terminal for in/out wiring. Use unshielded twisted pair (UTP) for IDNAC and audio wiring.

Table 12: Speaker audio specifications

Specification Rating
Input voltage 25 Vrms or 70.7 Vrms
Power taps 1/4 W, 1/2 W, 1 W, and 2 W
Frequency response 400 Hz to 4000 Hz (S/V, S/VH), 200 Hz to 10000 Hz
(H/F, HF/VH) General Signaling = 125 Hz to 12 kHz

Table 13: Speaker output ratings

Wattage tap 1/4 W 1/2 W 1 W 2 W
Model S/V H/F S/V H/F
S/V H/F
Reverberant chamber test, in accordance with UL 1480 (dBA) 79 76 83 80
86* 84 89* 87*
Anechoic chamber test, in accordance with ULC-S541 (dBA)* 79 78 83 82
86* 85* 89* 88*
  • Select taps as indicated to satisfy the ULC fire alarm applications requirement of 85 dBA minimum
    Polar dispersion reference in accordance with ULC-S541 Anechoic Chamber Testing| Attenuation| Angle| Attenuation| Angle
    -3 dB| 70°| -6 dB| 80°

Table 14: Percentage of rated light

Angle| On-axis| Vertical, below axis| Horizontal, left/right of axis
---|---|---|---
| 45°| 90°| 45°| 90°
UL required output| 100%| 45%| 25%| 45%| 25%
Typical output| 327%| 134%| 83%| 129%| 47%

Table 15: IDNAC SLC specifications

Specification Rating
Typical operating voltage range 23 VDC to 30 VDC, Special

Application
Appliance voltage design reference| 23 VDC (with 6 VDC drop)
Supervisory requirements| 1 unit load (= 0.8 mA control unit current)
Flash rate and synchronized SLC loading| 1 Hz; with up to 63 synchronized strobes maximum for each powered circuit, max 127 S/V appliances for each IDNAC channel
IDC SLC loading| Maximum of 127 addresses for each SLC, 139 unit loads. See device and compatible fire control unit installation instructions for circuit current load limits.
IDC SLC wiring specifications refer to the control unit installation instructions for more information| UTP, unshielded twisted pair recommended
Maximum wire length allowed with T-taps for Class B wiring for each SLC = 10,000 ft (3048 m)
Maximum wire length to any appliance = 4000 ft (1219 m). This can be doubled to 8000 ft (2438 m) by using a 4009 IDNAC Repeater.

Table 16: Current consumption**

Candela setting 15 cd 30 cd 75 cd 110 cd 135 cd 185 cd
49SV and 49HFV models 59 mA 82 mA 145 mA 193 mA N/A N/A
49SVH and 49HFVH models N/A N/A N/A 259 mA 281 mA 325 mA
Weatherproof SV appliances N/A N/A N/A Inside 110CD = 305 mA
Outside 110CD = 308 mA 335 mA 398 mA

** Measured at 23 VDC on IDNAC Addressable SLC
Speakers are for connection to compatible fire alarm audio circuits. Anechoic speaker output ratings are typically more representative of actual installed sound output.

Table 17: Equipment compatibility references

Compatible equipment Data sheet reference
4100ES with EPS+ or EPS Power Supply S4100-0100
4009 IDNAC Repeater S4009-0004
4100ES Flex 35 and 50 Watt Amplifiers ****

S4100-0034

4100ES 100 Watt Amplifiers
4100ES Constant Supervision and Signal Cards

Ceiling mount S/V installation referencesimplex S49SVC Ceiling Mount
Addressable Speaker - fig

Callout Description Callout Description
1 Appliance with cover, front 2 Appliance, rear
A Appliance test points, audio circuit power taps, and address dip switch

Set audio circuit power taps and device address before fixing cover in place.

| B| Mount to 4 in. x 4 in. x 2 1/8 in. electrical box using 8-32 screws. Ceiling mount only.
C| Wiring terminals for speaker and strobe connections. These terminals accept two #12-18 AWG wires.| D| Candela flag setting Set flag to FACU to control candela rating from a FACU providing IDNAC notification. To set candela manually, set the flag to the desired candela rating.
E| Use slotted screwdriver here to remove cover.| F| Magnet test location indicated by area that is not textured.

© 2022 Johnson Controls. All rights reserved. All specifications and other information is shown were current as of document revision and are subject to change without notice. Additional listings may be applicable, contact your local Simplex® product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. Simplex and the product names listed in this material are marks or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code have registered
trademarks of the National Fire Protection Association (NFPA). S49SVC-0001 Rev. 11 1/2022

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Simplex User Manuals

Related Manuals