Simplex 4098 True Alarm Analog Addressable Detector Base Instruction Manual

June 9, 2024
Simplex

4098 True Alarm Analog Addressable Detector Base

FIRE
4098 Detectors, Sensors, and Bases Application Manual
574-709 Rev. T
firealarmresources.com

ii
firealarmresources.com

Copyrights and Trademarks

Copyrights Trademarks

© 2008- 2011 SimplexGrinnell LP. All rights reserved. Specifications and other information shown were current as of publication and are subject to change without notice.
Suffix “C” or “CA” following an eight-digit Product ID number denotes ULC- listed product.
Suffix “E” following an eight-digit Product ID number denotes Global product. The second suffix identifies market country, models with this suffix are not UL Listed.
Tyco, IDNet, Simplex and the Simplex logo are trademarks of Tyco International Ltd. and its affiliates and are used under license.
MAPNET II Communication Net is protected by US Patent No. 4,796,025. TrueAlarm Analog Detection is protected by US Patent No. 5,155,468. TrueAlarm Detector Base is protected by US Patent No. 5,173, 683.
All illustrations of actual detectors, sensors, and bases shown in this publication are artist’s renditions.

iii
firealarmresources.com

Cautions and Warnings

Cautions and Warnings

READ AND SAVE THESE INSTRUCTIONS- Follow the instructions in this installation manual. These instructions must be followed to avoid damage to this product and associated equipment. Product operation and reliability depend upon proper installation.
DO NOT INSTALL ANY SIMPLEX® PRODUCT THAT APPEARS DAMAGED- Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify an authorized Simplex product supplier.
ELECTRICAL HAZARD – Disconnect electrical field power when making any internal adjustments or repairs. All repairs should be performed by a representative or authorized agent of your local Simplex product supplier.

STATIC HAZARD – Static electricity can damage components. Handle as follows:

Ground yourself before opening or installing components.

Prior to installation, keep components wrapped in anti-static material at all times.

FCC RULES AND REGULATIONS ­ PART 15 – This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

iv
firealarmresources.com

Table of Contents
Copyrights and Trademarks ………………………………………………………………………………. iii Copyrights……………………………………………………………………………………………………. iii Trademarks………………………………………………………………………………………………….. iii
Cautions and Warnings …………………………………………………………………………………….. iv
Table of Contents ……………………………………………………………………………………………… v
Chapter 1 Overview …………………………………………………………………… 1-1
Introduction ……………………………………………………………………………………………….. 1-1 In this Chapter …………………………………………………………………………………………… 1-1
Special Considerations …………………………………………………………………………………… 1-2 Overview …………………………………………………………………………………………………… 1-2 Special Considerations for Smoke Detectors and Sensors………………………………. 1-2 Smoke Detector/Sensor Applications ……………………………………………………………. 1-2
Where to Place Detectors and Sensors ……………………………………………………………. 1-3 Proper Locations for Detectors and Sensors ……………………………………………….. 1-3
Where Not to Place Detectors and Sensors………………………………………………………. 1-6 Improper Locations for Detectors and Sensors ………………………………………………. 1-6
Principles of Operation …………………………………………………………………………………… 1-8 Introduction ……………………………………………………………………………………………….. 1-8 Heat Detector Operation……………………………………………………………………………… 1-8 Photoelectric Smoke Detectors/Sensors ……………………………………………………….. 1-8 Ionization Smoke Detectors/Sensors ……………………………………………………………. 1-8 Carbon Monoxide Gas Detectors/Sensors …………………………………………………….. 1-8
Chapter 2 4098 Smoke Detectors, Heat Detectors and Bases………. 2-1
Introduction ……………………………………………………………………………………………….. 2-1 In this Chapter …………………………………………………………………………………………… 2-1
4098 Smoke Detectors …………………………………………………………………………………… 2-2 Introduction ……………………………………………………………………………………………….. 2-2 Smoke Detector Limitations…………………………………………………………………………. 2-2 Specifications…………………………………………………………………………………………….. 2-3 Mounting Requirements………………………………………………………………………………. 2-4
4098 Heat Detectors………………………………………………………………………………………. 2-5 Introduction ……………………………………………………………………………………………….. 2-5 Heat Detector Types…………………………………………………………………………………… 2-5 Specifications…………………………………………………………………………………………….. 2-5
4098 Bases…………………………………………………………………………………………………… 2-8 Introduction ……………………………………………………………………………………………….. 2-8 Mounting …………………………………………………………………………………………………… 2-9 Wiring……………………………………………………………………………………………………… 2-10
Chapter 3 TrueAlarm Sensors, Sensor Bases, and QuickConnect Smoke Sensors ………………………………………………………………………… 3-1
Introduction ……………………………………………………………………………………………….. 3-1
v
firealarmresources.com

In this Chapter …………………………………………………………………………………………… 3-1
4098 TrueAlarm Sensors………………………………………………………………………………… 3-2 Specifications…………………………………………………………………………………………….. 3-2 Special Applications……………………………………………………………………………………. 3-2 Mounting …………………………………………………………………………………………………… 3-2
4098 TrueAlarm Sensor Bases ……………………………………………………………………….. 3-3 Introduction ……………………………………………………………………………………………….. 3-3 Specifications…………………………………………………………………………………………….. 3-3 Setting the Base’s Address………………………………………………………………………….. 3-3 Address Setting for the 2120 CDT System…………………………………………………….. 3-5 Address Setting for the 4010, 4020, 4100+, 4100U, 4100ES, 4008, or 4120 System3-5 Multi-Sensor Bases 4098-9795 and 4098-9796 …………………………………………….. 3-7 Wiring……………………………………………………………………………………………………….. 3-7
4098 TrueAlarm QuickConnect Smoke Sensors………………………………………………. 3-12 Overview …………………………………………………………………………………………………. 3-12 Specifications…………………………………………………………………………………………… 3-12 Setting the Sensor’s Address ……………………………………………………………………. 3-13 Wiring……………………………………………………………………………………………………… 3-14
Chapter 4 Accessories ………………………………………………………………. 4-1
Introduction ……………………………………………………………………………………………….. 4-1 In this Chapter …………………………………………………………………………………………… 4-1
Relay Module Accessories ……………………………………………………………………………… 4-2 2098-9737 Relay Module Wiring …………………………………………………………………. 4-2 4098-9822 Relay Module Wiring ………………………………………………………………….. 4-3 Relay Module Installation…………………………………………………………………………….. 4-4 Remote LED Module ………………………………………………………………………………….. 4-4
Chapter 5 Compatibility and Testing ………………………………………….. 5-1
Introduction ……………………………………………………………………………………………….. 5-1 In this Chapter …………………………………………………………………………………………… 5-1
Compatibility …………………………………………………………………………………………………. 5-2 Compatibility for 4098 Detectors and Detector Bases……………………………………… 5-2
Maintenance and Testing ……………………………………………………………………………….. 5-4 Maintenance ……………………………………………………………………………………………… 5-4 Preferred Method of Testing Smoke Detectors/Sensors………………………………….. 5-4 Test Equipment Available ……………………………………………………………………………. 5-4 Alternate Method for Testing Sensors …………………………………………………………… 5-5 Magnetic Test for Photoelectric Detectors……………………………………………………… 5-5 Magnetic Test for Ionization Detectors ………………………………………………………….. 5-7 Ion Detector Sensitivity Test ………………………………………………………………………… 5-7
Cleaning……………………………………………………………………………………………………….. 5-8 Introduction ……………………………………………………………………………………………….. 5-8 Photoelectric Smoke Detector/Sensor Cleaning …………………………………………….. 5-8 Special Considerations for Ion Detectors and Sensors ……………………………………. 5-8
Trouble Indications ………………………………………………………………………………………… 5-9 Trouble Indications for TrueAlarm Sensors ……………………………………………………. 5-9
Trouble Indications, Continued………………………………………………………………………. 5-10
vi
firealarmresources.com

Fire Alarm Trouble and Maintenance Log ……………………………………………………….. 5-11 Fire Alarm Trouble and Maintenance Log …………………………………………………… 5-11
Index …………………………………………………………………………………………………………….. I-1
vii
firealarmresources.com

firealarmresources.com

Chapter 1 Overview

Introduction In this Chapter

The purpose of this publication is to provide information concerning the proper application of both heat and smoke detectors/sensors in conjunction with fire alarm systems.
The information in this publication is intended to be used only as a technical guide. The requirements of applicable codes and standards, as well as directives of Authorities Having Jurisdiction (AHJ’s), should be followed.

Refer to the page number listed in this table for information on a specific topic.

Topic Special Considerations Where to Place Detectors and Sensors Where Not to Place Detectors and Sensors Principles of Operation

See Page # 1-2 1-3 1-6 1-8

1-1
firealarmresources.com

Special Considerations

Overview
Special Considerations for Smoke Detectors and Sensors
Smoke Detector/Sensor Applications

Before installing detectors/sensors, make a survey of the area to be covered in accordance with information provided in NFPA 72, (an excerpt of which is provided in the “Smoke Detector/ Sensor Applications” section below). For additional information, refer to NFPA 72 and the NEMA Guide for Proper Use of System Smoke Detectors.
Is there human occupancy? Contents to be protected. Type of construction and use. Burning characteristics of contents. Air movement – stratification. Deflections and obstructions. Height of ceilings. Surface conditions of ceilings. Type of ceiling construction. Total area. Vent locations – velocities – dilution.
Each detector/sensor is capable of providing up to 900 square feet (84 square meters) of coverage, depending on the following:
Requirements of local codes. Results of engineering evaluation.

1-2
firealarmresources.com

Where to Place Detectors and Sensors

Proper Locations for Detectors and Sensors

IMPORTANT:

The guidelines in this section are adapted from standards published by the National Fire Protection Association, Quincy, Massachusetts, U. S. A. These standards include NFPA 72, “National Fire Alarm Code”; NFPA 70, “National Electrical Code”, Article 760; and NFPA 90A, “Standard for the Installation of Air Conditioning and Ventilating Systems.”

To provide effective early warning of a developing fire situation, smoke detectors/sensors should be installed in all areas of the protected premises. Total coverage as defined by NFPA 72 should include all rooms, halls, storage areas, basements, attics, lofts, and spaces above suspended ceilings including plenum areas utilized as part of the HVAC system. In addition, this should include all closets, elevator shafts, enclosed stairways, dumbwaiter shafts, chutes and other subdivisions and accessible spaces.
Fire detection systems installed to meet local codes or ordinances may not be adequate for early warning of the fire. Some codes or ordinances have minimum objectives such as capturing elevators or preventing circulation of smoke through HVAC systems instead of early detection of fire.
You should weigh the costs against the benefits of installing a complete fire detection system when any detection system is being installed. The location, quantity and zoning of detectors/sensors should be determined by what objectives are desired rather than the minimum requirements of any local codes or ordinances.
Detectors/sensors may be omitted from combustible blind spaces when any of the following conditions prevail:
Where the ceiling is attached directly to the underside of the supporting beams of a combustible roof or floor deck.
Where the concealed space is entirely filled with noncombustible insulation. (In solid joist construction, the insulation need only fill the space from the ceiling to the bottom edge of the joist of the roof or floor deck.)
Where there are small concealed spaces over rooms, provided the space in question does not exceed 50 square feet (4.6 square meters).
In spaces formed by sets of facing studs or solid joists in walls, floors, or ceilings where the distance between the facing studs or solid joists do not exceed 6 inches (15 cm).
Detectors/sensors may also be omitted from below open grid ceilings where all of the following conditions are met:
The openings of the grid are at least 1/4 inch (6 mm) in the smallest dimension.
The thickness of the material does not exceed the smallest of the grid openings.
The openings constitute at least 70% of the area of the ceiling material.

Continued on next page

1-3
firealarmresources.com

Where to Place Detectors and Sensors, Continued

Proper Locations for Detectors and Sensors

Detectors/sensors are usually required or recommended underneath open loading docks or platforms and their covers, and in accessible under-floor areas in buildings without basements. Detectors/sensors may be omitted from combustible blind spaces when all of the following conditions prevail:

1. The space is not accessible for storage purposes, it is protected against the entrance of unauthorized persons, and it is protected against the accumulation of windblown debris.
2. The space contains no equipment/structures (such as steam pipes, electrical wiring, ducts, shafts, or conveyors) that could potentially ignite or conduct the spread of fire.
3. The floor over the space is tight.
4. Non flammable liquids are processed, handled, or stored on the floor above the space.

“Total coverage” as described in NFPA 72, is the definition of a complete fire detection system. In some of the specified areas of coverage, such as attics, closets, under open loading docks or platforms, a heat detector may be more appropriate than a smoke detector. Careful consideration should be given to the detector manufacturer’s instructions and the following recommendations in this guide.

In general, when only one detector/sensor is required in a room or space, the detector/sensor should be placed as close to the center of the ceiling as possible. Central location of the detector/sensor is best for sensing smoke and/or fire in any part of the room. If a center location is not possible, it may be placed no closer than 4 inches (10 cm) from the wall, or if listed for wall mounting, it may be mounted on the wall. Wall mounted detectors/sensor should be located approximately 4 to 12 inches (10 to 30 cm) from the ceiling to the top of the detector, and at least 4 inches (10 cm) from any corner wall junction (see the figure below). FigureTag FD4-709-01

Ceiling

4in (10 cm)

Acceptablehere

Never here

Top of the detector acceptablehere

Note:

McleoasseusNMoerttaees:eurmedmegentnessthoasowfsntahhreoetotwhdenetaercetotor. the closestedgeofthedetector.

4in (10 cm) Minimum
12in (30 cm) Maximum
Side wall

Figure 1-1. Wall and Ceiling Mounted Detector/Sensor Continued on next page
1-4
firealarmresources.com

Where to Place Detectors and Sensors, Continued

Proper Locations for Detectors and Sensors

When an air supply and/or an air return duct opening is present in a room or space, the

detector/sensor(s) should be placed in the path of the air flow toward the return air duct opening

(see below).

FigureTag FD4-709-02

Return air

Correct

Supply air

Incorrect

Figure 1-2. Detector Placement – Air Supply and/or Return Ducts
Smoke tests are helpful in determining proper placement. Special attention should be given to smoke travel directions and velocity, since either can affect detector/sensor performance.
Placement of a detector/sensor near air conditioning or incoming air vents can also cause excessive accumulation of dust and dirt on the detector/sensor. This dirt can cause the detector/sensor to malfunction and cause nuisance alarms. Detectors/sensors should not be located closer than 3 feet (0.9 m) from an air supply diffuser.
Spot type detectors/sensors in properly engineered systems, may also be placed in return air ducts, or in approved duct detector housings designed for this application. Although duct detectors are not a substitute for open area detectors, they can provide an effective method of initiating building control functions to prevent smoke from being transported from the fire area to other parts of a building.

1-5
firealarmresources.com

Where Not to Place Detectors and Sensors

Improper Locations for Detectors and Sensors

One of the major causes of nuisance alarms is improper placement of detectors/sensors. The best way to avoid nuisance alarms is to not install detectors/sensors in environments that can cause them to malfunction. See the table and examples provided below.

Table 1-1. Environmental Conditions that Influence Detector Response*

Detection Protection

Air Velocity >300 ft.
(91.4m)/min.

Atm. Pressure 3000 ft. (914m) Above Sea Level

Ion

X

X

Photo

O

O

Beam

O

O

Air Sampling

O

O

  • See Table A-5-3.6.1.1 in NFPA 72 X = May affect detector/sensor response O = Generally does not affect detector/sensor response

Humidity >93% RH
X X X X

Temp. <32°F (0C) >100°F (38C)
X X X X

Color of Smoke
O X O O

DO NOT PLACE DETECTORS/SENSORS:
In excessively dusty or dirty areas, such as feed rooms, steel mills, etc. Dust and dirt can accumulate on the detector/sensor’s sensing chamber and make it overly sensitive, or block the air entrances to the sensing chamber and make the detector/sensor less sensitive to smoke. Be especially careful to avoid areas where fumigants, fog or mist-producing materials, or sweeping and cleaning compounds are used. These substances may cause nuisance alarms.
Outdoors, in stables, open storage sheds, or other open structures affected by dust, air currents, or excessive humidity and temperature.
In damp or excessively humid areas, or next to bathrooms with showers. Water droplets can accumulate inside the sensing chamber and make the detector/sensor overly sensitive. A tremendous amount of humid air is produced during a hot shower. The moisture in this humid air can enter the sensing chamber as water vapor, then cool and condense into droplets that can cause a nuisance alarm.
In elevator lobbies over ashtrays or where people smoke while waiting for the elevator.
In very cold or very hot environments, or in unheated buildings or rooms where the temperature can fall below or exceed the operating temperature range of the detector/sensor. At temperatures below 32° F (0° C), ice crystals or condensation can appear inside the sensing chamber and make it overly sensitive or cause a nuisance alarm. At temperatures above the operating range of the detector/sensor greater than 120° F (49° C), its internal components may not function properly.
In or near areas where combustion particles are normally present, such as in kitchens or other areas with ovens and burners; in garages, where particles of combustion are present in vehicle exhausts; within 15 feet (4.5 meters) of any type of furnace, hot water heater, or gas space heater; or in welding shops or other types of work areas where some form of combustion is used in the activity normally conducted in that area. When a detector must be located in or adjacent to such an area, a fixed temperature heat detector may be appropriate.
Continued on next page

1-6
firealarmresources.com

Where Not to Place Detectors and Sensors, Continued

Improper Locations for Detectors and Sensors

In air streams passing by or through kitchens. Air often enters a residence or a residential unit of an apartment building through cracks around the front and/or back doors. If the air return is in the bedroom hallway or in the bathroom, and if air from the kitchen easily enters the air stream going from the door to the air return, combustion particles from cooking can cause nuisance alarms. Install detectors/sensors so that they protect the bedrooms, but so they are out of the air stream.
In or near manufacturing areas, battery rooms, or other areas where substantial quantities of vapors, gases or fumes may be present. Strong vapors, like excessive humidity, can make detectors/sensors overly sensitive or less sensitive than normal. In very large concentrations, gases heavier than air, such as carbon dioxide, may make detectors/sensors more sensitive, while gases lighter than air, such as helium, may make them less sensitive. Aerosol particles may collect on detector/sensor chamber surfaces and cause nuisance alarms.
Insect-infested areas. If insects enter a detector/sensor’s sensing chamber, they can cause a nuisance alarm. Take proper insect eradication procedures before installing detectors/sensors in such locations. If spraying is done, do not allow insect spray to enter the detectors/sensors.
Near fluorescent light fixtures. Electrical noise generated by fluorescent light fixtures may cause nuisance alarms. Install detectors/sensors at least 1 foot (0.3 meters) away from such light fixtures.
When using the CO Base for CO fire detection, do not install in locations that could have potentially high non-fire levels of CO.
Underwriters Laboratories (UL) has three standards for smoke detectors: one for duct detectors/sensors, UL 268A; one for single and multiple station detectors/sensors, UL 217; and one for system type detectors/sensors, UL 268. Detectors/sensors should only be used in the applications for which they are specifically listed.
The NFPA 101 Life Safety Code states that single station smoke detectors shall sound an alarm only within an individual living unit or similar area and shall not actuate the building fire alarm system. It also states, “All systems and components shall be approved for the purpose for which they are installed.”
In addition to possible code noncompliance, the following deficiencies would exist in a series of residential smoke detectors connected in a fire alarm system mode:
Since the fire alarm system is not supervised, vandals or others could disconnect a detector or the entire system, leaving a building without protection. The residents would be unaware of the serious life threatening condition.
Residential detectors do not latch in alarm. In other words, the detector self-resets. One detector in alarm sounds all the detectors connected together. It would be difficult to identify or locate a specific detector that initially put the system into alarm after the alarm condition was cleared.
System detectors/sensors latch in alarm. They do not reset until power is momentarily disconnected. This makes it convenient to identify the location of the detector/sensor that caused the control panel to alarm. In addition, system detectors are specifically designed to connect to a supervised control panel. Two-wire detectors require a UL compatibility review to verify that the detector and panel properly operate together. A typical life safety fire alarm system for an apartment complex would be to use system detectors/sensors and manual fire alarm stations in the hallways and common areas of the complex and residential single station type detectors and heat detectors in the individual apartments. The system detectors/sensors, manual stations and heat detectors would be connected to a supervised control panel, sound a general alarm and automatically notify the proper authorities that a fire condition exists. The residential detectors located in the apartments would be interconnected only within the individual living quarters of each apartment. These residential units would sound an alarm only in the apartment unit.

1-7
firealarmresources.com

Principles of Operation

Introduction

This section describes how the different types of detectors and sensors work. For additional information on TrueAlarm sensor operation, refer to the TrueAlarm Concepts publication (PER-91-024).

Heat Detector Operation

The heat detector senses the heat or the Rate-of-Rise (ROR) in the air temperature of the environment in which it is located. The heat detector is comprised of electronic circuitry and a mechanical package that is designed to sense the ROR of the air temperature in an expedient and reliable fashion. Upon detection of an abnormal increase in air temperature, or ROR in air temperature, the electronics indicate an alarm by increasing the amount of current draw from the monitor zone it is connected to. The monitor zone is a supervised detection circuit that is tied back to a main control panel that takes appropriate action to indicate an alarm has been reported, if the zone current is substantially increased.
Being of an electronic design, the temperature of the air is sensed by using two negative temperature coefficient thermistors. The resistance of the thermistors goes down with an increase in temperature. One thermistor is placed in a position such as to sense the open air temperature very rapidly (RT1). The second thermistor is positioned in a small cavity that protrudes out from the main body of the detector (RT2). The location of RT2 allows for fast detection of a quick change in the air temperature, but yet for a slow or medium rate of temperature change, the detector does not trip due to the ROR feature. For a slower change in temperature, the detector trips into alarm due to a set fixed temperature that is sensed by RT1. For a fast temperature rise, when a difference in temperature sensed by RT1 and RT2 has reached a predetermined amount, the detector trips into alarm.

Photoelectric Smoke Detectors/Sensors

These devices operate on a light scattering principle. The smoke sensing chamber contains an infrared LED source with a peak spectral emission of 880 nanometers. This source is placed at an angle from a spectrally matched photodiode receiver. During a NO SMOKE condition, only light reflected from the chamber walls enters the receiver and shows up as a small photocurrent. As smoke particles enter the sensing chamber and cross the light beam of the LED, more light reaches the receiver due to scattering. The receiver circuitry converts this photocurrent into a signal voltage. In a detector, when this voltage reaches a preset level, an alarm is produced. In a sensor, this signal voltage goes into an 8-bit, A to D (analog to digital) converter. A digital representation of this signal voltage is then transmitted to the fire alarm panel for further processing.

Ionization Smoke Detectors/Sensors

These devices use a small radiation source, Americium-241, which emits alpha particles that ionize air molecules between two electrically charged electrodes. With the application of a DC voltage .to these electrodes, a small ionization current flows within the chamber. As smoke enters the chamber, a decrease in ionization current results. This current is converted into a signal voltage by a transimpedance circuit. In a detector, when this signal voltage drops below a preset level, an alarm is produced. In a sensor, this signal voltage goes into an 8-bit A to D (analog to digital) converter. A digital representation of this signal voltage is then transmitted to the fire alarm panel for further processing.

Carbon Monoxide Gas Detectors/Sensors

The CO Sensor and Sounder Bases with a CO Replaceable Sensor (CRS) module work in conjunction with existing detector heads. The CO Sensor Base enhances fire detection and provides the ability to combine fire and toxic gas leakage detection in a single device. The CO sensor measures the concentration of carbon monoxide gas in the air in part per million (PPM). When toxic gas operation is selected, the FACP panel may generate either a supervisory, utility or priority 2 alarms. The alarm level is calculated within the panel based on the time integrated CO levels that have been measured at the detector.

1-8
firealarmresources.com

Chapter 2 4098 Smoke Detectors, Heat Detectors and Bases

Introduction In this Chapter

This chapter contains specification and mounting information for 4098 Smoke Detectors, Heat Detectors, and Bases.

Refer to the page number listed in this table for information on a specific topic.

4098 Smoke Detectors 4098 Heat Detectors 4098 Bases

Topic

See Page # 2-2 2-5 2-8

2-1
firealarmresources.com

4098 Smoke Detectors

Introduction
Smoke Detector Limitations

CAUTION:

Install the detectors described in this publication in accordance with applicable NFPA standards, local codes, and the Authorities Having Jurisdiction (AHJs). Failure to follow these instructions may result in failure of the detector to initiate an alarm condition. The manufacturer is not responsible for detectors that have been improperly installed, tested, or maintained.

The smoke detectors used with these bases are designed to activate and initiate emergency action, but do so only when used in conjunction with other equipment. They are designed for installation in accordance with NFPA 72 National Fire Alarm Code.
Smoke detectors do not work without power. AC or DC powered smoke detectors do not work if the power supply is cut off for any reason.
Smoke detectors do not sense fires when smoke does not reach the detectors. Smoke from fires in chimneys, in walls, on roofs or on the other side of closed doors may not reach the smoke detector and alarm it.
A detector may not detect a fire developing on another level of a building. For this reason, detectors should be located on every level of a building.
Smoke detectors have sensing limitations. Ionization detectors are better at detecting fast, flaming fires than slow, smoldering fires. Photoelectric detectors sense smoldering fires better than flaming fires. Because fires develop in different ways, and are often unpredictable in their growth, neither type of detector is always best, and a given detector may not always provide warning of a fire. In general, detectors cannot be expected to provide warning for fires resulting from inadequate fire protection practices, violent explosions, escaping gases, improper storage of flammable liquids like cleaning solvents, other safety hazards, or arson.
Smoke detectors cannot last forever. Smoke detectors contain electronic parts. Even though detectors are made to last for many years, any of these parts could fail at any time. Therefore, test your smoke detector system per NFPA 72 at least annually. Clean and take care of your smoke detectors regularly. (See Chapter 5 of this publication for cleaning instructions.)
Continued on next page

2-2
firealarmresources.com

4098 Smoke Detectors, Continued

Specifications

Table 2-1. Smoke Detector Specifications

Specifications
Detector PID (4098)
Type of Detector
Working Voltage (2-wire)
Rated Voltage (4-wire)
Input Ripple Voltage
Max. Alarm Current
Surge Current
Standby Current
Heat Element Rating
Humidity Range (Non-Condensing)
Air Velocity Range

-9601, -9605 Photoelectric 8.5 ­ 33 VDC 15 ­ 32 VDC
25% Max. 86 mA <200 A <100 A N/A
10-95% RH 0-2000 FPM

Smoke Detector Data
-9602 Photoelectric
with Heat 8.5 ­ 33 VDC

-9603 Ionization 8.5 ­ 33 VDC

15 ­ 32 VDC

15 ­ 32 VDC

25% Max.

25% Max.

86 mA <200 A <100 A 135 F

86 mA <200 A <100 A
N/A

10-95% RH

10-95% RH

0-2000 FPM

0-200 FPM

Continued on next page

2-3
firealarmresources.com

4098 Smoke Detectors, Continued

Mounting Requirements

All smoke detectors identified in Table 2-1 mount to a detector base (refer to the “4098 Bases” section of this chapter for more information). Use the following considerations and Figure 2-1 when mounting smoke detectors.
IMPORTANT: Smoke must enter the chamber of the detector. Thus, air flow, air stratification, air velocity, air stagnation, and air migration affects detector efficiency.
Note: Where the possibility of positive airflow from the electrical conduit/junction box exists, seal the conduit openings with 3M Weatherban #606 (or equivalent), a non-flammable sealing compound.
Do not install detectors in areas where temperatures are likely to exceed 100 F (38 C) or fall below 32 F (0 C).
Because the 4098-9602 detector combines heat sensing, DO NOT install this detector in locations where the ambient temperatures exceed 100 F (38 C) or where temperature fluctuations above 6 F/min. occur.
Do not install detectors on a ceiling within 4 inches (10 cm) of a wall.
Do not install detectors where forced air ventilation may dilute the smoke before it reaches the detector.
Do not install detectors in areas where smoke is normally present (kitchens, furnace rooms, laundry rooms, loading docks, rooms with fireplaces, rooms with candles, soldering rooms, etc.).
Do not install detectors in areas where there is likely to be steam (in hospital patient rooms with vaporizers, near shower rooms, above large sinks, etc.).
Do not install detectors above ashtrays in elevator lobbies.
Wall-mounted detectors should be located 4 to 12 inches (10-30.5 cm) from the ceiling to detector head.
Protect all detector heads during construction to avoid infiltration of construction debris. Remove any protective covers before activating the system.
If using the adapter plate, tighten the mounting screws without warping the adapter plate.

2-4
firealarmresources.com

4098 Heat Detectors

Introduction

This section contains general notes, specifications, and mounting information for the heat detectors shown in Table 2-2.

WARNING: Notes:

Heat detectors are NOT life-safety devices; USE HEAT DETECTORS FOR PROPERTY PROTECTION ONLY! For life-safety requirements, use smoke detectors.

For all heat detectors, provide electronic supervision with battery back-up at the fire alarm control panel.
Where the possibility of positive airflow from the electrical conduit/junction box exists, seal the conduit openings with 3M Weatherban #606 (or equivalent), a non-flammable sealing compound.
Refer to NFPA 72 for application, test, and maintenance requirements.

Heat Detector Types

Fixed Temperature Heat Detectors:
Electronic fixed temperature heat detectors use a fast response, thermistor based design to provide temperature sensing that quickly, accurately, and consistently identifies when fixed temperatures are exceeded. For this reason, the fixed temperature detectors are recommended for most applications. With a UL spacing distance of 60 X 60 feet, the fixed temperature electronic heat detectors replace both mechanical fixed as well as mechanical ROR heat detectors.
ROR Temperature Heat Detectors:
Electronic Rate-of-Rise (ROR) heat detectors detect fixed temperature alarm thresholds the same as the fixed temperature heat detectors, plus detect a ROR alarm with a patented ROR detection design that can quickly respond to sudden temperature variations. Due to the nature of the fast response to temperature changes, care must be taken for proper installation of ROR heat detectors. ROR heat detectors should be installed in stable environmentally controlled areas. These detectors must not be installed where hot or cold air can be blown on them (near ductwork, industrial equipment, air vents etc.). ROR detectors should not be installed where more then 6 F per minute temperature changes can normally occur.

Specifications

Features: Rate-of-Rise and Fixed Temperature (see Table 2-2) Alarm LED Compatible with 2-Wire Initiating Device Circuits Current-Limited Alarm State Electrical Specifications: Typical Standby Current – 80 Microamps Typical Alarm Current – 40 Milliamps Maximum Current – 80 Milliamps while in alarm state Operating Range – 15-32 VDC Maximum Ripple Voltage Allowed – 30%
2-5
firealarmresources.com

Continued on next page

4098 Heat Detectors, Continued

Specifications

Table 2-2. Heat Detector Models and Features

Detector Model

Rating or Class*

Area / Language

4098-9612 (UL)

135 F (57 C) FT

English

4098-9613 (UL)

135 F (57 C) FT and RR

English

4098-9614 (UL)

200 F (93 C) FT

English

4098-9615 (UL)

200 F (93 C) FT and RR

English

4098-9616E

A1

European

4098-9617E

C

European

4098-9618E

A

Australian

4098-9619E

B

Australian

4098-9621E

D

Australian

4098-9622E

I

Chinese

4098-9624E

134 F (56.7 C) FT

Korean

4098-9625E

134 F (56.7 C) FT and RR

Korean

4098-9626E

134 F (56.7 C) FT

Taiwanese

4098-9627E

134 F (56.7 C) FT and RR Taiwanese

4098-9628E

190 F (87.8 C) FT

Korean

4098-9629E

190 F (87.8 C) FT and RR

Korean

4098-9630E

190 F (87.8 C) FT

Taiwanese

4098-9631E

190 F (87.8 C) FT and RR Taiwanese

  • RR abbreviates Rate-of-Rise; FT abbreviates Fixed-Temperature.

Color Code
White White Green Red White Blue Red Green

Continued on next page

2-6
firealarmresources.com

4098 Heat Detectors, Continued

Specifications

All heat detectors identified in the table below mount to a detector base (refer to the “4098 Bases” section of this publication for more information). Use the information in Figure 2-1 when mounting.
Table 2-3. Heat Detector Specifications

Product ID 4098-9612 4098-9613 4098-9614 4098-9615

Description

Application

Fixed-Temp. Only, 135 F (57 C)
Fixed-Temp. and Rate-of-Rise, 135 F (57 C)
Fixed-Temp. Only, 200 F (93 C)
Fixed-Temp. and Rate-of-Rise, 200 F (93 C)

Unusually violent temp. fluctuations
and ceiling temperatures not
exceeding 100 F (38 C)
Normal temp. fluctuations and ceiling temperatures not exceeding 100 F
(38 C)
Unusually violent temp. fluctuations
and ceiling temperatures exceeding 100 F (38 C) but not 150 F (68 C)
Normal temp. fluctuations and ceiling temperatures exceeding 100 F (38 C) but not 150 F (68 C)

Max. Spacing Allowed (UL)
70 X 70 ft (21 X 21 m)
70 X 70 ft (21 X 21 m)
70 X 70 ft (21 X 21 m)
70 X 70 ft (21 X 21 m)

FM
RTI = Quick 20 X 20 ft
(6.1 X 6.1 m)
RTI = Quick 20 X 20 ft
(6.1 X 6.1 m)
RTI = Quick 20 X 20 ft
(6.1 X 6.1 m)
RTI = Ultra Fast 50 X 50 ft
(15.2 X 15.2 m)

2-7
firealarmresources.com

4098 Bases

Introduction

The 4098-9788 base is designed to be used with 4098 Series smoke and heat detectors, as well as the QuickConnect2 photo sensor. To use a 4-wire configuration, you must use the 4098-9682 relay base. Heat detectors require the 4098-9684 base when used with a remote LED. This section only covers the information necessary to mount and wire these base configurations. Before installing these bases, make a survey of the area to be covered in accordance with information provided in NFPA 72. For additional information, refer to the NEMA Guide for Proper Use of System Smoke Detectors.
CAUTION: Install the bases in this section in accordance with applicable NFPA standards, local codes, and Authorities Having Jurisdiction (AHJs). Failure to follow these instructions may result in failure of the detector to initiate an alarm condition. The manufacturer is not responsible for detectors that have been improperly installed, tested, or maintained.
Continued on next page

2-8
firealarmresources.com

4098 Bases, Continued

Mounting

The 4098-9788 base mounts to a 4-inch octagonal, 4-inch square, or single gang electrical box. When mounting to a 4-inch square or any surface mounted box, the 4098-9832 adapter plate kit must be used.

ALL BASES FLUSH MOUNTED (BOX TO BE FLUSH OR RECESSED 1/4 ” MAX )
SINGLE GANG (2 1/8″ DEEP) ELECTRICAL BOX (NOT SUPPLIED)

4098-9789, -9791, -9792, -9796 AND ALL DETECTOR BASES FLUSH MOUNTED (BOX TO BE FLUSH MOUNTED OR RECESSED 1/4″ MAX)

4″ (10.16cm x 1 1/2″ DEEP) OCTAGONAL
ELECTRICAL BOX ( NOT SUPPLIED)

4″ (10.16cm x 1 1/2″ DEEP) SQUARE
ELECTRICAL BOX (NOT SUPPLIED)

4098-9794, AND 4098-9795 ONLY FLUSH MOUNTED
(BOX WITH ADAPTER BRACKET TO BE FLUSH OR RECESSED 1/4″ MAX)

6-32 SCREW WITH WASHER (NOT SUPPLIED)

(SEE NOTE 4)
BASE

8-32 x 1 1/4″ PANHEAD MACHINE

SCREW (TIGHTEN TO 4-6 in.-lbs.)

4098-9832 ADAPTER PLATE KIT (REQUIRED FOR 4″ SQUARE/ OCTAGONAL SURFACE MOUNTED ELECTRICAL BOX)

RACO 787 ADAPTER BRACKET
OR EQUIVALENT (NOT SUPPLIED)

8-32 x 1 1/4″ PANHEAD MACHINE

SCREW (TIGHTEN UNTIL SNUG,
1-3 in.-lbs.)

8 x 1″ THREAD FORMING PANHEAD SCREW

(TIGHTEN TO 4-6 in.-lbs.)
BASE

6-32 x 1 1/4″ PANHEAD SCREW (TIGHTEN TO 4-6 in.-lbs.)

SENSOR (AS REQUIRED) SEE NOTES 1 AND 2
CLOCKWISE FOR ATTACHMENT
Figure 2-1. Typical Detector/Sensor Mounting
Notes:
1. Break off plastic lock tab to engage locking mechanism. To lock detector/sensor into base, turn unit until the locking tab clicks into place. To unlock detector/sensor, insert the blade of a screwdriver into this slot and then pull down on handle. This action allows the detector/sensor to be turned and removed (see Figure 2-1).
2. Refer to the “Compatibility and Testing” chapter of this publication for detailed information on compatible detectors/sensors.
3. Bases with relay modules require a 1 ½-inch extension ring (not supplied) mounted to the 4-inch square or octagonal electrical box to meet the space requirement of the relay cube and its wires. The relay module(s) cannot be used in single-gang electrical box installations. The relay cube 4098-9822 must be installed in the electrical box directly behind the sensor base.
4. Use Adapter Plate Kit 4098-9832 when mounting the 4098-9794 and 4098-9795 to a surface mounted 4-inch square or octagonal box. Adapter plates must be installed with textured side towards the electrical box for this installation only.
Continued on next page

2-9
firealarmresources.com

4098 Bases, Continued

Wiring

All screw terminals accommodate 14 to 18 AWG solid or stranded wire. When tightening screws, the range of torque is 8 to 12 in-lbs. Connect wiring to the terminals shown in the figure below. (Figures 2-2 through 2-6 show typical wiring applications for the 4098 bases.) CAUTION: Do not loop wire under terminals. Break wire run to provide
supervision of connections.
2
1
3
4

See Note 2 See Note 1 See Note 3
Figure 2-2. Wiring and Mounting the Bases FigureTag FD4-709-03 Notes:
1. Break off plastic tab where indicated to engage locking mechanism. 2. Once locking mechanism is engaged, you must insert a flat-head screwdriver in slot
indicated to release the detector from the base. 3. Use the slotted hole indicated for the first screw when mounting the base.
Continued on next page

2-10
firealarmresources.com

4098 Bases, Continued

Wiring

  • INITIATING CIRCUIT
    + –

BACKUP 2 (SEE NOTE 3)
PRIMARY 1 (SEE NOTE 3)
(SEE NOTE 5 )

(SEE NOTE 4) 4098-9788
BASE
(SEE NOTE 5 )

4098-9788 BASE
(SEE NOTE 5)

4098-9788 BASE

EOL RESISTOR (IF USED)

LISTED SIMPLEX FIRE ALARM CONTROL
PANEL 2120, 4001, 4002 4020, 4100+, 4100U, 4100ES, 4004, 4005 OR 4006

4 3
1 2

4 3
1 2

4 3
1 2

(SEE NOTE 2)

RED

BLK

REMOTE LED 4098-9830
(SEE NOTE 1)

RED

BLK

REMOTE LED 4098-9830
(SEE NOTE 1)

FigureTag FD4-709-04 Figure 2-3. 4098-9788 Base Connections for Style B or D Initiating Circuits
Notes:
1. If used, 4098-9830 Remote LED is polarized. Refer to Figure 2-6 to wire remote LED to the Heat Detector; observe color-coded wiring.
2. Refer to wiring diagrams provided with system panel for proper End-Of-Line (EOL) resistor value.
3. It is recommended that the Primary-1 and the Backup-2 lines be in separate wire runs and in compliance with local requirements.
4. For Style D initiating circuit, wire per dotted lines and do not use EOL resistor.
5. Break wires before connecting to Terminal 4 to maintain supervision. Do not loop wire underneath Terminal 4.

Continued on next page

2-11
firealarmresources.com

4098 Bases, Continued

Wiring

FigureTag FD4-709-05

  • INITIATING CIRCUIT
    + –

BACKUP 2 SEE NOTE 4
PRIMARY 1 SEE NOTE 4

SEE NOTE 3

SEE NOTE
3
EOL RESISTOR (IF USED)

LISTED SIMPLEX FIRE ALARM CONTROL
PANEL 2120, 4001, 4002 4020, 4100+, 4100U, 4100ES, 4004, 4005 OR 4006

2 1
3 4

BLK
REMOTE LED 4098-9830
(SEE NOTE 1)

RED

RED BLK BLK

VIO N/C BLU C GRY N/O YEL N/C ORN C GRN N/O

(SEE NOTE 2)

(SEE NOTE 5)

Figure 2-4. 4098-9683 2-Wire Relay Base Connections for Style B or D Initiating Circuits

Notes:

1. If used, 4098-9830 remote LED is polarized; refer to Figure 2-6 to wire remote LED to a heat detector, observe color-coded wiring.
2. Wire only one relay base per initiating circuit.
3. For Style D initiating circuit, wire per dotted lines and do not use EOL resistor. If Style B initiating circuit, refer to wiring diagrams provided with the system panel for proper EOL resistor value.
4. It is recommended that the Primary-1 and the Backup-2 lines be in separate wire runs and in compliance with local requirements.
5. Aux. Relay contacts, each rated 1 amp at 28 VDC/0.5 amp at 125 VAC, resistive.

Continued on next page

2-12
firealarmresources.com

4098 Bases, Continued

Wiring

FigureTag FD4-709-06

RESETABLE POWER

SOURCE

24VDC

REMOTE LED 4098-9830
(SEE NOTE 1)

REMOTE LED 4098-9830
(SEE NOTE 1)

RED

24VDC EOL RELAY 2098-9735
OR 2098-9739

BLK

YEL

YEL

INITIATING + CIRCUIT –
LISTED SIMPLEX FIRE ALARM CONTROL PANEL
2120, 4001, 4002 4020, 4100+, 4100U 4100ES , 4004, 4005 OR 4006

RED

RED

BLK

BLK

ORG GRN

RED

ORG GRN

ORG GRN

N/C

VIO

SEE

N/O

BLU GRY

NOTE 6

RED

ORG GRN

N/C

VIO

N/O

BLU GRY

SEE NOTE
6

ORG GRN

RED ORG
GRN

N/C

VIO

N/O

BLU GRY

BLK

BLK

RELAY

BLK

BLK

RELAY

BLK

BLK

RELAY

EOL RESISTOR (SEE NOTE 3)
SEE NOTE
6

Figure 2-5. 4098-9682 4-Wire Base Connections for Style B Initiating Circuits
Notes:
1. If used, 4098-9830 remote LED is polarized, observe color-coded wiring. (Refer to Figure 2-6 to wire remote LED to heat detector.)
2. Aux. Alarm contacts – Form C – each rated 3 amps at 28 VDC/115 VAC, resistive. 3. Refer to wiring diagrams provided with system panel for proper EOL resistor value.
Continued on next page

2-13
firealarmresources.com

4098 Bases, Continued

Wiring

FigureTag FD4-709-07

  • INITIATING CIRCUIT
    + –
    LISTED SIMPLEX FIRE ALARM CONTROL
    PANEL 2120, 4001, 4002 4020, 4100+, 4100U 4100ES , 4004, 4005 OR 4006

BACKUP 2 SEE NOTE 2
PRIMARY 1 SEE NOTE 2

SEE NOTE 3
4098-9684 HEAT DETECTOR
BASE

2 1
3 4

RED BLK BLK

BROWN WHITE

4098-9684 HEAT DETECTOR
BASE

2 1
3 4

4098-9830 REMOTE LED
(SEE NOTE 1)

RED BLK BLK

BROWN WHITE

SEE NOTE
3
EOL RESISTOR (IF USED)
4098-9830 REMOTE LED
(SEE NOTE 1)

Figure 2-6. 4098-9684 Heat Detector LED Base Connections for Style B or D Initiating Circuits
Notes:
1. If used, 4098-9830 remote LED is polarized; observe color-coded wiring. 2. It is recommended that the Primary-1 and the Backup-2 lines be in separate wire runs and in
compliance with local requirements. 3. For Style D initiating circuit, wire per dotted lines and do not use EOL resistor. If Style B
initiating circuit, refer to wiring diagrams provided with the system panel for proper EOL resistor value.

2-14
firealarmresources.com

Chapter 3 TrueAlarm Sensors, Sensor Bases, and
QuickConnect Smoke Sensors

Introduction In this Chapter

This chapter contains general notes, specifications, and mounting information for the TrueAlarm Sensors, Sensor Bases and QuickConnect Smoke Sensors.

WARNING:

Be sure that the location of each smoke sensor and each heat sensor has been planned per local and national fire codes (see NFPA 72).

Smoke sensor sensitivities are set and continuously monitored by the control panel. This functionality complies with NFPA 72. When functional testing of these sensors is required per NFPA 72, use the test methods described in Chapter 5 of this manual “Compatibility and Testing.”

Refer to NFPA 72 for application, test, and maintenance requirements.

The 4098-9733 heat sensor and 4098-9754 multi-sensor provide a Rate-of-Rise function that is software programmed and selectable at 15° F (8.3° C) or 20° F (11.1° C) per minute. The 4098-9733 and 4098-9754 also provide general temperature monitoring within the range of 32°-122° F (0°-50° C).

Refer to the page number listed in this table for information on a specific topic.

Topic 4098 TrueAlarm Sensors 4098 TrueAlarm Sensor Bases 4098 TrueAlarm QuickConnect Smoke Sensors

See Page # 3-2 3-3 3-12

Agency UL UL FM
FM

Table 3-1. 4098-9733 Spacing

Program Selection 135º F (57 C) 155º F (68 C) 135º F/155º F (57 C/68 C)
135º F/155º F (57 C/68 C) with 15 or 20 º F/min (8.3 or 11.1 C/min)Rate of Rise

Spacing
60 X 60 ft (18.3 X 18.3 m)
40 X 40 ft (12.2 X 12.2 m)
RTI = Quick 20 X 20 ft (6.1 X 6.1 m)
RTI = Ultra Fast 50 X 50 ft (15.2 X 15.2 m)

3-1
firealarmresources.com

4098 TrueAlarm Sensors

Specifications
Sensor PID
Type of Sensor
Average Operating Current UL Temperature Rating* Humidity Range (Non- Condensing)
Air Velocity Range

Table 3-2. TrueAlarm Sensor Specifications

4098-9714 Photoelectric
80 A
10-95% RH

40989717
Ionizat ion

4098-9733 Heat

80 A

6 A at 68 F (20°C) 13 A at 135 F (57 C)

135 F (57 C)** 155 F (68 C)

1095% RH

10-95% RH

4098-9754 Photo/Heat
90 A 135 F (57 C)** 155 F (68 C)
10-95% RH

4098-9746 Gas
50µA
15-95% RH (15-90% for
long term exposure)

0-2000 FPM

0-200 FPM

0-2000 FPM

0-1000 FPM

  • Fixed temperature functions are software programmed and selectable from the UL temperature rating. ** UL Max. Ambient Ceiling Temp. of 100° F (38° C) at 3600 sq. ft of Max. Coverage. UL Max. Ambient Ceiling Temp. of 100° F (38° C) at 1600 sq. ft of Max. Coverage.

Special Applications Mounting

1. Smoke sensor sensitivities are set and continuously monitored by the control unit. The sensitivity range (setting) for the 4098-9714 and 4098-9754 sensor is 0.2%/FT to 3.7%/FT smoke obscuration. The sensitivity range (setting) for 4098-9717 sensors is 0.5%/FT to 1.3%/FT.
2. The 0.2%/FT, 0.5%/FT, and 1.0%/FT settings for the 4098-9714 and 4098-9754 sensor and the 0.5%/FT and 0.9%/FT settings for the 4098-9717 sensor are for special applications only. The 0.2%/FT, 0.5%/FT, 0.9%/FT, and 1.0%/FT settings are very sensitive settings: only use the 0.2%/FT setting when a sensor is located in a totally smoke-free and controlled temperature environment, such as a computer room or telephone switching exchange.
3. To determine if an area is suitable for the 0.2%/FT setting, set the sensitivity for the installed sensor at 1.5%/FT and monitor the peak values for 90 days. If you record a peak value of 0.1%FT or higher during the 90 days, do not use the 0.2%/FT setting.
4. To determine if an area is suitable for the 0.5%/FT setting, set the sensitivity for the installed sensor at 1.5%/FT and monitor the peak values for 90 days. If you record a peak value of 0.25%FT or higher during the 90 days, do not use the 0.5%/FT setting.
5. To determine if an area is suitable for the 0.9%/FT or 1.0%/FT setting, set the sensitivity for the installed sensor at 1.3%/FT (Ion) 1.5/FT (Photo) and monitor the peak values for 90 days. If you record a peak value of 0.5% or higher during the 90 days, do not use the 0.9%/FT (Ion) or 1.0%/FT (Photo) settings.
All sensors identified in Table 3-2 mount to a sensor base (refer to the “4098 TrueAlarm Sensor Bases” section of this chapter for more information). Use the following information and Figure 2-1 when mounting TrueAlarm sensors.

3-2

firealarmresources.com

4098 TrueAlarm Sensor Bases

Introduction

TrueAlarm smoke/heat sensor bases are connected to a 2120 Multiplex Communicating Device Transponder (CDT), 4020, 4100+, 4100U, 4100ES, 4120, 4008, or 4010 panel by a single wire pair (MAPNET II/IDNet). The 4098-9792, -9789, 9793, 9796, 9797, and 9798 bases and their sensors obtain both power and data over MAPNET II/IDNet wiring. The 4098-9791 sensor base requires 24VDC power for relay operation and the 4098-9794 and 4098-9795 sensor base with sounder requires 24 VDC or Notification Appliance Circuit (NAC) power. The 4098-9791, -9794, -9795, and ­9796 are NOT compatible with the 2120 CDT. The 4098-9793 is only compatible with the 4010, 4008, 4100U and 4100ES (except with 4100-3103 Quad Panel Isolator).

Specifications

The table below contains specifications for TrueAlarm Sensor Bases. Table 3-3. TrueAlarm Sensor Bases Specifications

Sensor Base PID
Working Voltage (MAPNET II/IDNet)
24V Working Voltage (Relay or Sounder Power)
MAPNET II/IDNet Current *
24V Standby Current (Relay or Sounder)
24V Current (Relay or Sounder Activated)
LED Output
Sounder Output

4098-9789 (w/
Remote LED)

4098-9791 (w/ Relay
and Remote
LED)

4098-9792

4098-9793 (Isolator Base)

4098-9794 (Sounder
Base)

4098-9795 (MultiSensor
Sounder Base)

24-40 VDC

24-40 VDC

24-40 VDC

24-40 VDC 24-40 VDC 24-40 VDC

18 ­ 32 VDC

18 ­ 32 VDC

18 ­ 32 VDC

400 A

400 A

400 A

500 A

400 A

500 A

270 A

270 A

270 A

28 mA

17 mA

20 mA

Yes

Yes

Yes

Yes

88 dBA minimum

88 dBA minimum

  • MAPNET II/IDNet current with Photo Sensor plugged into Base

4098-9796 (Multi-
Sensor w/ Remote
LED) 24-40 VDC

500 A

Yes

4098-9797 (CO Sensor
Base)
24-40 VDC

450 A

4098-9798 (CO Sounder
Base)
24-40 VDC
18 ­ 32 VDC
500 A
270 A
17 mA Yes
88 dBA minimum

Setting the Base’s Address

Each sensor base has a unique address. This address is associated with a custom label that identifies its physical location within a building. The base’s address and location must match up with the address listed in the specification sheets of the 2120 Job Configuration Report or the Programmer’s Report for the 4020, 4100+, 4100U, 4100ES, 4120, 4008, or 4010 System. See Figure 3-1 for DIP Switch location for 4098-9789, -9791, -9792, -9793, and -9796, Sensor Bases. See Figure 3-2 for DIP Switch location for 4098-9794, 4098-9795, -9797 and -9798.
Continued on next page

3-3
firealarmresources.com

4098 TrueAlarm Sensor Bases, Continued
Setting the Base’s Address

128 64 32 16 8 4 2 1
ON

OFF

DIP Switches

12345678

Figure 3-1. 4098-9789, -9791, -9792, -9793, -9796, Sensor Bases Location of DIP Switches

“ON” Position

DIP Switch Position 9 “ON” for NAC Power Input

DIP Switches

“OFF” Position

DIP Switch Position 9 “OFF” for 24 VDC Power Input

Figure 3-2. 4098-9794, 4098-9795, , 4098-9798 Sensor Bases Location of DIP Switches
Note: The 4098-9794 Sounder Base, 4098-9795 Multi-Sensor Sounder Base, and 4098-9798 Sounder Base have a 9-position DIP Switch. The first eight DIP Switches set the sounder base address. DIP Switch Position 9 is set to OFF or ON depending upon the sounder base power source. When the sounder base is connected to a 24 VDC power source, DIP Switch Position 9 is set to “OFF” and the 24 VDC power is supervised by the sounder base. When the sounder base is powered by the panel’s Notification Appliance Circuit (NAC), DIP Switch Position 9 is set to “ON” and the power is supervised by the NAC and not the sounder base. The -9797 Base has the same layout, but doesn’t offer sounder functionality. It uses only an 8-way DIP switch.
Continued on next page
3-4
firealarmresources.com

4098 TrueAlarm Sensor Bases, Continued

Address Setting for the 2120 CDT System
Address Setting for the 4010, 4020, 4100+, 4100U, 4100ES, 4008, or 4120 System

1. Using the 2120 Job Configuration Report, find the entry for the sensor base (4098-9792 and 4098-9789 only) you are about to install. The CUSTOM LABEL column provides the location while the DEVICE ADDRESS column provides the switch setting data.
2. Using the switch setting data for the base you are installing, set the base’s address. See Figure 3-1 for location of switches. Use a small screwdriver or pen to set the switches.
3. Double-check the location of the sensor base and its address before proceeding to electrical installation (see Figure 2-1).
1. Using the Programmer’s Report for the 4020 (Figure 3-3), 4100+, 4100U, 4100ES, 4120, 4008, or 4010 (Figure 3-4), find the entry for the sensor base you are about to install. The device ADDRESS and CUSTOM LABEL are located in the SYSTEM POINT SUMMARY under “M.”For example, Address M1-7 (for the 4100+, 4100U, 4100ES, 4120, 4008, or 4010 system) is circled in Figure 3-4. M1 is the addressable channel while -7 is the device address on the channel. For a base with Address M1-7, Address 7 must be set on the base’s DIP Switches (SW1).
2. Using the example given in Step 1 as guideline, set the base’s address using the information in Figure 3-5. See Figure 3-1 and 3-2 for location of DIP Switches. Use a small screwdriver or pen to set the switches.
3. Mark an address label with the appropriate address for your base by shading a label box for each base DIP Switch in the ON position. Then apply the label to the base near the base’s DIP Switch.
4. Double-check the location of the sensor base and its address before proceeding to electrical installation.

Device Address

Figure 3-3. 4020 Programmer’s Report

Device Address

Figure 3-4. 4100+, 4100U, 4100ES, 4120, 4008, or 4010 Programmer’s Report Continued on next page
3-5
firealarmresources.com

4098 TrueAlarm Sensor Bases, Continued

Address Setting for the 4010, 4020, 4100+, 4100U, 4100ES, 4008, or 4120 System
LSB

The figure below shows the address DIP Switch settings for the 4010, 4008, 4020, 4100+, 4100U, 4100ES and 4120 Systems. Refer to the “Compatibility and Testing” chapter of this publication for information on which devices are compatible with the various FACPs.

Note: The 4020, 4100+, 4100U, 4100ES, 4008, and 4120 systems support up to 127 devices on

each of their MAPNET II channels. The 4010 supports up to 250 devices on its IDNet

channel.

FigureTag FD4-709-08

MSB

DIPSWITCH IS SHOWN SET AT ADDRESS 7.

1 2 34 56 78 ON
OFF

1 = ON

0 = OFF

DIP SWITCHES 5 THRU 8

0000 1000 0100 1100 0010 1010 0110 1110 0001 1001 0101 1101 0011 1011 0111 1111

0000 1000 0100 1100 0010 1010 0110 1110 0001 1001 0101 1101 0011 1011 0111 1111 0 16 32 48 64 80 96 112 128 144 160 176 192 208 224 240 1 17 33 49 65 81 97 113 129 145 161 177 193 209 225 241 2 18 34 50 66 82 98 114 130 146 162 178 194 210 226 242 3 19 35 51 67 83 99 115 131 147 163 179 195 211 227 243 4 20 36 52 68 84 100 116 132 148 164 180 196 212 228 244 5 21 37 53 69 85 101 117 133 149 165 181 197 213 229 245 6 22 38 54 70 86 102 118 134 150 166 182 198 214 230 246 7 23 39 55 71 87 103 119 135 151 167 183 199 215 231 247 8 24 40 56 72 88 104 120 136 152 168 184 200 216 232 248 9 25 41 57 73 89 105 121 137 153 169 185 201 217 233 249 10 26 42 58 74 90 106 122 138 154 170 186 202 218 234 250 11 27 43 59 75 91 107 123 139 155 171 187 203 219 235 251 12 28 44 60 76 92 108 124 140 156 172 188 204 220 236 252 13 29 45 61 77 93 109 125 141 157 173 189 205 221 237 253 14 30 46 62 78 94 110 126 142 158 174 190 206 222 238 254 15 31 47 63 79 95 111 127 143 159 175 191 207 223 239 255

Figure 3-5. 4010, 4020, 4100+, 4100U, 4100ES, 4008, or 4120 MAPNET/IDNet Addresses Continued on next page

3-6
firealarmresources.com

4098 TrueAlarm Sensor Bases, Continued

Multi-Sensor Bases 4098-9795 and 4098-9796

The 4098-9795 and 4098-9796 Multi-Sensor Bases are only for use with the 4098-9754 multi-sensor and are not compatible with the 2120 CDT. Both bases have remote LED output and the 4098-9795 also has an integrated sounder similar to the 4098-9794 Sounder Base. The 4098-9795 and 4098-9796 Multi- Sensor Bases must be used with the 4098-9754 multi-sensor when connected to a 4010, 4020, 4100+, 4008, or 4120 system. When connected to a 4100U or a 4100ES the 4098-9754 multi-sensor can also be used with the 4098-9789, -9791, -9792, -9793, 9794, -9797, and -9798 bases.
The Multi-Sensor Base answers to two addresses, therefore the DIP Switch must be set for even addresses only. The even address is a photo sensor/sounder base (4098-9795) or a photo sensor/standard base (4098-9796), and the odd address (DIP Switch + 1) is a heat sensor/standard base. The figure below shows the allowable addresses for the Multi-Sensor Bases.
IMPORTANT: Switch Position 1 is not used and must always be OFF (0) for the Multi-Sensor Bases to function properly. The odd address immediately after the DIP Switch setting must not be used by any other sensor base or MAPNET/IDNet device.

Wiring

LSB

MSB

SEE NOTE 1
ON

1 2 34 56 78 9

OFF

DIPSWITCH IS SHOWN SET AT ADDRESS 4.
1 = ON

SEE NOTE

0 = OFF

RESERVED FOR FUTURE USE

DIP SWITCHES 5 THRU 8

DIP SWITCHES 1 THRU 4

0000 1000 0100 1100 0010 1010 0110 1110 0001 1001 0101 1101 0011 1011 0111 1111

0000 0 0100 2

16 32 48 64 80 96 112 128 144 160 176 192 208 224 240 18 34 50 66 82 98 114 130 146 162 178 194 210 226 242

0010 4 0110 6

20 36 52 68 84 100 116 132 148 164 180 196 212 228 244 22 38 54 70 86 102 118 134 150 166 182 198 214 230 246

0001 8 24 40 56 72 88 104 120 136 152 168 184 200 216 232 248 0101 10 26 42 58 74 90 106 122 138 154 170 186 202 218 234 250

0011 12 28 44 60 76 92 108 124 140 156 172 188 204 220 236 252

0111 14 30 46 62 78 94 110 126 142 158 174 190 206 222 238 254

SWITCH 1 MUST BE SET TO OFF FOR PROPER OPERATION

RESERVED FOR FUTURE USE

Figure 3-6. 4098-9795, -9796, 9798 Multi-Sensor Base DIP Switch Address Settings
Note: The 4098-9795 Multi-Sensor Sounder Base has a 9-position DIP Switch that is used for setting base address and selecting the sounder power source. See Figure 3-2 for DIP Switch location.

Sensor bases are connected to the fire alarm control panel via a single wire pair for the 4098-9789, -9792, -9793, -9796, and -9797 and two pairs of wires for the 4098-9791, -9794, -9795, and -9798. Using Figure 3-7 as a reference, connect the bases to the MAPNET II/IDNet wire pair and 24V power (if used). IMPORTANT: For additions to existing installations, remove power from the panel
before wiring any bases to avoid damage to equipment.
Continued on next page
3-7
firealarmresources.com

4098 TrueAlarm Sensor Bases, Continued

Wiring

FigureTag FD4-709-09

FROM PANEL

+24V OR NAC +ALM 0V OR NAC -ALM

FROM PANEL

+24V 0V

+24V 0V

TO OTHER 24V DEVICES

TO NEXT 24V OR NAC
CIRCUIT

2098-9808

REMOTE LED

OR 4098-9822

RELAY (IF USED)

(SEE NOTE 1)

+ WHITE BLUE

(SEE NOTES 8 & 10)

+S

+COMM

4098-9794, -9795 -9797 , -979 8

-S

4098-9792 SENSOR BASE

-COMM

+COMM

-COMM

SHIELD (SEE NOTE 3)

SHIELD (SEE NOTE 3)

FROM PANEL

+ MAPNET II/IDNet – MAPNET II/IDNet

+COMM -COMM

BLUE WHITE

(SEE

NOTE 6)

(SEE NOTE 5)

BLUE WHITE
RED RED BLACK

4098-9822 RELAY
MODULE
(SEE NOTE 6)

4098-9789, -9796 SENSOR BASE

BLACK

CENTER N.C. N.O.

BROWN VIOLET GREY

ORANGE YELLOW GREEN

CENTER N.C. N.O.

SHIELD (SEE NOTE 3)

CONTACT B (SEE NOTE 4)

CONTACT A (SEE NOTE 4)

BLUE WHITE BLACK/WHITE BLACK

(SEE NOTE 9)

CENTER N.C. N.O.

BLACK BLACK
BLUE

2098-9737 RELAY (SEE
NOTE 9)

VIOLET

GREY

ORANGE YELLOW GREEN

CENTER N.C. N.O.

4098-9791 SENSOR BASE

CONTACT B (SEE NOTE 7)

SHIELD (SEE NOTE 3)

CONTACT A (SEE NOTE 7)
4098-9793 SENSOR BASE (SE NOTE 8)

+COMM -COMM

+ MAPNET II/IDNet – MAPNET II/IDNet

TO OTHER MAPNET II/ IDNet DEVICES (SEE NOTE 2)

FROM 4010 PANEL

IDNet IDNet

COMM

COMM

COMM

COMM

TO OTHER IDNET DEVICES
(SEE NOTE 2)

Figure 3-7 Smoke/Heat Sensor Base Connections

SHIELD IS OPTIONAL (SEE NOTE 3)

SHIELD

Notes:

1. Remote LED and relay wires are not supervised.

2. Maximum quantity of devices per circuit is 127 for 4020, 4100+, 4100U/4100ES (MAPNET), or 4120, 128 for the 2120 CDT panel, 200 for the 4008 panel, and 250 for the 4010 and 4100U/4100ES (IDNET) panel. Maximum quantity of 4098-9795 -9796 and -9797 Multi-Sensor bases is 63 with 4020, 4100+, 4100U, 4100ES and 4120, 100 for 4008 panel, and 124 for the 4010 panel. If the sounder output is coded (Temporal code, etc.) via MAPNET II/IDNet control see Note 10.

3. If shield is used, twist shield wires together and cap with wire nut. Shield should be insulated from electrical box.

4. Contact A or B: Dry, Form C – each rated 2 amperes at 24 VDC/0.5 amperes at 110 VAC, resistive.

5. 18 to 32 VDC, .008 amperes typical/.013 amperes max.

6. Do not use remote LED if the 4098-9822 relay module is used.

7. Contact A or B: Dry, Form C ­ Each rated at 3 amperes at 28 VDC/115 VAC, resistive.

8. Remove the protective tape over the CO Sensor on the 4098-9797 and -9798 bases only after the sensor head has been installed.

9. Maximum wire length between 4098-9791 sensor base and 2098-9737 relay module is 100 feet.

10. Maximum quantity of sensors with 4098-9794, -9795, and -9798 sounder bases limited to 43 if output is coded (Temporal code, etc.) via MAPNET II/IDNet control. If coding is performed via 24VDC or NAC circuit, see Note 2.

Continued on next page

3-8
firealarmresources.com

4098 TrueAlarm Sensor Bases, Continued

Wiring

Figure 3-8 shows the wiring connections for the isolator sensor base. All screw terminals accept 14 to 18-gauge AWG solid or stranded. Maximum torque should not exceed 12-inch-pounds.
CAUTION: Do not loop wire under terminals. Break wire runs to provide supervision.

COMM COMM COMM COMM COMM COMM COMM COMM COMM COMM COMM COMM

FROM 4010 PANEL

IDNet IDNet

IDNet IDNet

TO OTHER IDNet DEVICES (SEE NOTE 2)

SHIELD IS OPTIONAL (SEE NOTE 3)

SHIELD

SHIELD

SHIELD

Figure 3-8. 4098-9793 Isolator Sensor Base Connections

Notes: 1. Isolator base compatible with 4010, 4100U, 4100ES or 4008 panel ONLY. 2. Maximum quantity of devices per circuit is 250 for 4010, 4100U and 4100ES panels. 3. If shield is used, twist shield wires together and cap with wire nut. Shield should be insulated
from electrical box.

3-9
firealarmresources.com

4098 TrueAlarm Sensor Bases, Continued

CRS Replacement Instructions

This section contains the instructions for the end-of-life replacement of the 4098-9746 CO Replacement Cartridge (CORC), in the CO SSD Bases (Carbon Monoxide Smoke Sensor and Detector Bases). Replacement is necessary due to normal component degradation over time. It is standard maintenance for the CO SSD Bases in order to prolong normal function without requiring base replacement.

Note: During installation, you may be exposed to live circuits – attention required to ensure personal safety and to avoid product damage.

Model number reference:

Model 4098-9746 4098-9797 4098-9798

Name CORC Replacement CO SSD Sensor Base CO SSD Sounder Base

Removing the expired CORC
1. Remove sensor head (not shown) and set aside for later re-installation. 2. Insert a fine blade screwdriver into the slot, as shown below.

3. Gently free the CORC from the sensor base by pushing straight in. Do not pry. Remove the CORC and dispose.

Figure 3-9. Removing the CORC from the Sensor Base


Continued on next page
3-10
firealarmresources.com

4098 TrueAlarm Sensor Bases, Continued

CRS Replacement Instructions

Installing the replacement CORC (refer to photo below) 1. Remove the replacement CORC from its packaging. 2. Hook the loop of the CORC on the tab in the outer rim of the base (center of the CORC below
the CO sensor cylinder) 3. Gently rotate the CORC inward until it snaps onto the CO SSD Sensor Base. 4. Re-install the detector head. 5. Remove the dust cover from the CORC (shown to the side below). 6. The CORC replacement is complete.

Figure 3-10. Installing the replacement CORC

3-11
firealarmresources.com

4098 TrueAlarm QuickConnect Smoke Sensors

Overview Specifications

This section contains general notes, specifications, and mounting information for the TrueAlarm QuickConnect Smoke Sensor shown in Table 3-4.

WARNING:

Ensure that the location of each smoke sensor has been planned per local and national fire codes (see NFPA 72).

1. Smoke sensor sensitivities are set and continuously monitored by the control panel. This functionality complies with NFPA 72. When functional testing of these sensors is required per NFPA 72, use the test methods described in the “Compatibility and Testing” chapter of this publication. The sensitivity range (settings) of the 4098-9757 is 1.5%/ft to 3.7%/ft smoke obscuration.
2. Refer to NFPA 72 for application, test, and maintenance requirements.

Table 3-4. TrueAlarm QuickConnect Smoke Sensor Specifications

Sensor PID
Type of Sensor
Operating Current
Humidity Range (Non-Condensing)
Air Velocity Range Working Voltage (MAPNET II and IDNet) 24V Working Voltage (Sounder Power
Sounder Output 24V Standby Current (Sounder) 24V Current (Sounder Activated)
Remote LED Output

4098-9757 Photoelectric 500 A max. 10-95% RH 0-2000 FPM 24-40 VDC

NO

Continued on next page

3-12
firealarmresources.com

4098 TrueAlarm QuickConnect Smoke Sensors, Continued

Specifications
Setting the Sensor’s Address

The 4098-9757 QuickConnect2 sensor requires the 4098-9788 base.
The 4098-9757 QuickConnect2 sensor is only compatible with the 4010, 4100U and 4100ES (with 4100-3106). The sensors obtain both power and data over IDNet wiring.
Each QuickConnect sensor has a unique address. This address is associated with a custom label that identifies its physical location within a building. The sensor’s address and location must match up with the address listed in the Programmer’s Report for the 4010, 4100U or the 4100ES.
Use the method described in the “4098 TrueAlarm Sensor Bases” section of this chapter to complete the sensor setup. Refer to the figure below for the location of the DIP Switches. Double-check the location of the QuickConnect sensor and its address before proceeding to electrical installation (see Figures 3-12 and 3-13).

Address DIP Switches

4098-9757
Figure 3-11. Location of DIP Switches on QuickConnect Sensor Continued on next page
3-13
firealarmresources.com

4098 TrueAlarm QuickConnect Smoke Sensors, Continued

Wiring

Use the following to wire the QuickConnect smoke sensors.

CAUTION:

Do not loop wire under terminals. Break wire runs to provide supervision.

4098-9788

4098-9788 (SEE NOTE 1)

4098-9788

FROM PANEL

-IDNet +IDNet

SHIELD IS OPTIONAL (SEE NOTE 3)

SHIELD

SHIELD

SHIELD

-IDNet TO OTHER IDNet DEVICES
+IDNet (SEE NOTE 2)

Figure 3-12. QuickConnect Sensor Connections
FigureTag FD4-709-10 Notes:
1. 4098-9757 QuickConnect sensor uses the 4098-9788 base. 2. Maximum quantity of devices per IDNet circuit is 250 for the 4010, 4100U and 4100ES (with
4190-3106) panel. 3. If shield is used, twist shield wires together and cap with wire nut. Shield should be insulated
from electrical box.

3-14
firealarmresources.com

Chapter 4 Accessories

Introduction In this Chapter

This chapter covers relay module accessories.

Refer to the page number listed in this table for information on a specific topic.

Topic Relay Module Accessories

See Page # 4-2

4-1
firealarmresources.com

Relay Module Accessories

2098-9737 Relay Module Wiring

The 2098-9737 Relay module is used with 4098-9791 sensor base. Install the relay module using Figure 3-7 and the figure below as a reference.

FROM PANEL

+24VDC

+24VDC

TO OTHER 24VDC DEVICES OR
SUPERVISORY MODULE

SEE NOTE 1

BLACK/WHITE

BLACK BLACK

2098-9737 RELAY

TO 4098-9791 SENSOR BASE
SEE NOTE 3

CONTACT B SEE NOTE 2

CENTER N.C. N.O.

BLUE VIOLET GREY

ORANGE YELLOW GREEN

CENTER N.C. N.O.

CONTACT A SEE NOTE 2

Figure 4-1. 2098-9737 Relay Module Wiring
Notes: 1. 18 to 32 VDC 24 mA typical/35 mA maximum. 2. Contact A or B: dry, Form C, each rated 3 amps at 28 VDC/115 VAC, resistive. 3. Maximum wire length between sensor and relay module is 100 feet.
Continued on next page

4-2
firealarmresources.com

Relay Module Accessories, Continued

4098-9822 Relay Module Wiring

The 4098-9822 Relay Module is used with the 4098-9789, -9791, -9794, -9795, and -9796 Sensor Bases. Install the relay module using Figure 3-7 and the figure below as a reference.

IMPORTANT: Do not use a remote LED if using the 4098-9822 relay module.

The 4098-9822 relay module is not supervised and should only be

used for non-critical supplementary functions. There is a limit of

ten control outputs activated on a MAPNET II/IDNet channel. If the

channel capacity is exceeded, the relay module may not function

properly.

FigureTag FD4-709-10

FROM PANEL (IF USED)

+24VDC 0V

+24VDC 0V

TO OTHER 24VDC DEVICESOR
SUPERVISORY MODULE

(SEENOTE2)
CONTACT B (SEENOTE3)

CENTER N.C. N.O.

WHITE BLUE RED RED BLACK BLACK BROWN VIOLET GREY

4098-9822 RELAY

(SEENOTE1) -BLUE +WHITE

From 4098-9789, -9791, -9794,-9795, -9796 Sensor Base

ORANGE YELLOW GREEN

CENTER N.C. N.O.

CONTACT A (SEENOTE3)

Figure 4-2. 4098-9822 Relay Module Wiring
Notes:
1. Do not use remote LED. 2. 18 to 32 VDC, .008 amps typical / .013 amps. Maximum. 3. Contact A or B: Dry, Form “C” – each rated 2 amps resistive at 24 VDC/0.5 amps at
110 VAC, resistive.
Continued on next page

4-3
firealarmresources.com

Relay Module Accessories, Continued

Relay Module Installation

Install the relay module using the following steps:
1. Mount a 1-1/2 inch (3.81 cm) extension ring (not supplied) to an octagonal or square electrical box (not supplied). The extension ring is required to meet the minimum box volume requirement (32.3 cu. inch/529.4 cu. cm) for relay module installation.
2. Mount relay module inside extension ring directly behind base and sensor. Do not mount remotely. See Figure 4-1 or 4-2 for relay module connections.
Note: Use the exact configuration of electrical box (square or octagonal) with extension to mount sensor base when installing the relay module.

Remote LED Module

The 2098-9808 Remote LED Module is available for the 4098-9789 ,-9791, -9794, -9795, -9796 Sensor Bases.
Use the figure below as a reference when installing the Remote LED Module to a sensor base.

RED

BLACK

2098-9808

To 4098-9789, -9791, -9794, -9795, -9796 Sensor Base

LED

Figure 4-3. 2098-9808 Remote LED Module Wiring

4-4
firealarmresources.com

Chapter 5 Compatibility and Testing

Introduction In this Chapter

This chapter covers the compatibility of 4098 Sensors, Detectors, and Bases. Maintenance and testing are also covered.

Refer to the page number listed in this table for information on a specific topic.

Topic Compatibility Maintenance and Testing Cleaning Trouble Indications Fire Alarm Trouble and Maintenance Log

See Page # 5-2 5-4 5-8 5-9 5-11

5-1
firealarmresources.com

Compatibility

Compatibility for 4098 Detectors and Detector Bases

This section describes the compatibility between FACPs, detectors, and detector bases. Table 5-1. 4098 Detector and Detector Base Compatibility

Detectors
4098-9601 4098-9602 4098-9603 4098-9605 4098-9612 4098-9613 4098-9614 4098-9615

Compatible 2Wire Detector
Base 4098-9788 4098-9684 (LED base for Heat Detectors
Only)
4098-9683

System
2120 ET/FADM 2120 FABT/VPBT 2120/4100+ ZAM
4001 4002 4020 4100ES/4100U/4100+/4120/UT 4004/4005 4006 4004/4005 High Current (Relay base not used with 4004 and 4005 Low Current systems)

Max. Quantity of Bases per
Initiating Circuit
25 18 20 18 30 30 30 20 30 30
1 (See Note 1)

Notes:

Relay operation cannot be guaranteed unless it is the only device on that zone.

Panel compatibility identification marker is model number of the module or panel.

Detector compatibility identification marker is model number found on detector label.

For detailed interconnection data, see wiring diagrams for specific panels.

For additional compatibility listings see 579-832 for 2-wire detector compatibility charts.

Continued on next page

5-2
firealarmresources.com

Compatibility, Continued

Compatibility for 4098 Detectors and Detector Bases

This section describes the compatibility between FACPs, sensors, and sensor bases. Table 5-2. 4098 Sensor and Sensor Base Compatibility

Notes:
1. For detailed interconnection data, see wiring diagrams for specific panels.
2. Panel compatibility identification marker is model number of the module or panel.
3. Sensor compatibility identification marker is model number found on sensor label.
4. 4098-9754 sensor NOT compatible with bases that have a RED DOT located in sensor mounting area.
5. Maximum quantity of 4098-9794
Sounder Bases, 4098-9795 Multi-Sensor Sounder Bases, and CO Sounder bases (4098-9798) when output is coded via MAPNET II/IDNet control (Temporal Code) is 43. If coding is performed via 24 VDC or NAC circuit, use limits specified in Table 5-2.

Sensors 4098-9714 4098-9717 4098-9733 4098-9714 4098-9717 4098-9733
4098-9714 4098-9717 4098-9733
4098-9714 4098-9733
4098-9714 4098-9717 4098-9733
4098-9754

4098-9754
4098-9757 4098-9746

Compatible Bases
4098-9789 4098-9791 4098-9792
4098-9789 4098-9792
4098-9789 4098-9791 4098-9792 4098-9793 4098-9797 (4100U/4100ES
only) 4098-9789 4098-9791 4098-9792 4098-9793
4098-9794 (See Note 5) 4098-9798 (See Note 5) (4100U/4100ES, IDNet only)
4098-9795 (See Note 5) 4098-9796
4098-9792 4098-9789 4098-9791 4098-9794 (See Note 5) 4098-9797 4098-9798 (See Note 5)
4098-9788
4098-9797 4098-9798 (See Note 5)

Max. Quantity of Devices Per Circuit
MAPNET II: 127 (4020), 127 (4100+) 127 (4120), 127 (4100U), 127 (4100ES)
Addresses 1-127
128 (CDT TrueAlarm) Addresses 0-127
IDNET:
250 (4010), 250 (4100U), 250 (4100ES) Addresses 1-250
IDNET: 200 (4008) Addresses 1-200
MAPNET II: 127 (4020), 127 (4100+) 127 (4100U), 127 (4100ES), 127 (4120)
Addresses 1-127
IDNET: 250 (4010), 250(4100U), 250 (4100ES)
Addresses 1-250 MAPNET II:
63 (4020, 4100+, 4100U, 4100ES, 4120) Addresses 2 to 126
IDNET: 124 (4010), 124 (4100U), 124 (4100ES)
Addresses 2 to 248
IDNET: 250 (4100U), 250 (4100ES)
Addresses 1-250
IDNET: 250 (4100U/4100ES with 4100-3106)
250 (4010) Addresses 1-250
IDNET: 250 (4100U), 250 (4100ES)
Addresses 1-250

5-3
firealarmresources.com

Maintenance and Testing

Maintenance

The minimal requirement for detector and sensor maintenance should consist of clearing surface dust by using a vacuum cleaner. Cleaning programs should comply with NFPA and local environments. Cleaning of the internal chamber should only be done by a qualified technical representative.
For service, return to your local branch office.

Testing

Smoke sensor sensitivities are set and continuously monitored by the control unit. Dirty or out-or-range sensors are annunciated by the control unit. This functionality complies with NFPA 72.
Note: When testing detectors/sensors, refer to NFPA 72, or contact your local branch office.
CAUTION: Before functionally testing the detectors/sensors, be sure to disconnect the city connection, releasing devices, and extinguishing systems (or for the 4020, 4010, 4100+, 4100U, 4100ES, 4006, 4008, or 4120 panel, put the panel in the Walk Test mode).

Preferred Method of Testing Smoke Detectors/Sensors

NFPA minimally requires annual functional testing of smoke detectors/sensors at their installed location. To perform this annual test, use the Solo 336 Aerosol Smoke Dispenser.
IMPORTANT: After testing detectors, reset the fire alarm panel to restore the fire alarm system to normal status. After testing sensors, you must clear the peak values.

Test Equipment Available

The following test equipment is available:

553-760:
553-761: 553-635: 553-805: 553-810:
553-832:

Test and Removal Tool ­ attached to Mr. Longarm 4 ft. pole (Item #7508) or 6 ft. pole (Item #7512). Heat Detector/Sensor Removal Adapter (use with 553-760). Aerosol spray, Simplex Dry Smoke. Removal Adapter Head Attachment (attaches to the 553-760 tool). Magnet Tester ­ attached to Mr. Longarm 4 ft. pole (Item #7508) or 6 ft. pole (Item #7512). Ion Detector Test Cable.

Also available are the:

Gemini Sensitivity Tester (Model 501 or 502).

Solo 336 Aerosol Smoke Dispenser ­attached to either the Solo 100 (15 ft.)

telescopic fiberglass pole or the Solo 101 (4 ft.) fiberglass pole.

Solo A4 Aerosol Spray.

Solo Red Cup (709-024). Use to hold the 553-635 Aerosol Spray Can.

Solo (708-021) Adapter for Solo Poles. Use to adapt 553-760 Test and Removal

Tool to the Solo Pole.

TrueTest 801 ­ Smoke Detector Sensitivity Test Equipment.

Smoke 400 ­ Smoke aerosol for TrueTest.

Note: The TrueTest 801 is the only tester to be used with the 4098-9797 and 4098-9798 bases.

5-4
firealarmresources.com

Continued on next page

Maintenance and Testing, Continued

Alternate Method for Testing Sensors

The following test method is suitable for functional checks of sensor bases or QuickConnect sensors during installation; however, testing with smoke must be performed to comply with NFPA requirements.
For all sensor bases, position the 553-810 Magnet Tester ½” to ¾” counterclockwise from the visible LED found on the sensor base, (see the figure below).
For the 4098-9757 QuickConnect2 photo sensor, position the 553-810 Magnet Tester as shown in Figure 5-2.
Testing a sensor with a magnet reports a value of 255 for actual / peak (exception 4010 panel, 4100U panel and 4100ES panel). Clear the peak value after testing.
Note: For 4098-9795 and 4098-9796 Multi-Sensor Bases both photo and heat address (even and odd) must alarm.

Magnetic Test for Photoelectric Detectors

Figure 5-1. Magnet Test Location for 4098-9789, -9791, -9792, -9793, and -9796 Sensor Bases using 553-810 Magnet Tester
The 4098 photoelectric detectors may be tested by placing a magnet above the location indicated by a “” mark embossed on the cover (see Figure 5-2) for four (4) seconds. Use the Magnetic Tester (Part No. 553-810), Table 5-3, and the following information to test detectors.
Table 5-3 describes the LED reaction during Normal and MAG TEST modes to the Normal, More Sensitive, Less Sensitive, and Non-Functional states of the detector.
Continued on next page

5-5
firealarmresources.com

Maintenance and Testing, Continued
Magnetic Test for Photoelectric Detectors

Figure 5-2. Magnet Test Location for 4098-9601, -9602, -9603, -9605 Smoke Detectors using 553-810 Magnet Tester
Table 5-3. MAG TEST/Normal Modes – States and Reactions

STATE
Normal More Sensitive Less Sensitive Non-Functional

Normal Mode
(LED flashes every 4 secs.)
X X X

LED Flashes Quickly 6 Times
X

MAG TEST Mode

LED Flashes Slowly 4 Times
X X

Latches in Alarm Mode/LED stays “ON”
X X X

When placing the magnet at the location indicated by a “” mark embossed on the cover, the visible LED flashes indicating the detector’s condition. The following are descriptions of what you should see when using the MAG TEST.

NORMAL – When in MAG TEST, the detector latches into alarm if the detector is within calibration range and the visible LED stays ON.

MORE SENSITIVE – When in MAG TEST, if the detector is more sensitive than the maximum calibration, the visible LED quickly flashes, twice a second. Following the sixth flash, the detector latches into alarm and the visible LED stays ON.

LESS SENSITIVE – When in MAG TEST, if the detector is less sensitive than the minimum calibration, the visible LED slowly flashes four times, once every two seconds. Following the fourth flash, the detector latches into alarm and the visible LED stays ON.
NON-FUNCTIONAL DETECTOR – If the detector is less sensitive than the minimum allowable sensitivity or if there is a fault in the temperature sensing circuit (4098-9602), the visible LED does not flash normally. When in MAG TEST, the visible LED slowly flashes four times, once every two seconds. After the fourth flash, the detector does NOT latch into alarm and the LED stops flashing and turns OFF.
If the detector is out of the normal operating range, it should be cleaned. If the detector still indicates as other than normal sensitivity, replace the detector.

Continued on next page

5-6

firealarmresources.com

Maintenance and Testing, Continued

Magnetic Test for Ionization Detectors

The 4098 Ionization Detectors may be tested with a magnet to verify proper operation of the Fire Alarm Control Panel.
Note: When ionization detectors alarm, the red LED indicator activates and latches into the ON position.
Place a magnet against the detector’s side (over the location marked by a “” on the head of the ionization detector) and hold for ten seconds to activate an internal reed switch. Use the Magnet Tester (Part No. 553-810).

Ion Detector Sensitivity Test

Plug the 553-832 Ion Detector Test Cable into the Detector’s sensitivity voltage pins located on the Ion Detector Head. Perform the following steps to test the Ion detector’s sensitivity:
1. Connect a 10M/V digital voltmeter to the 553-832 test cable, connect the negative terminal of the voltmeter to the red wire of the test cable and connect the positive terminal of the voltmeter to the white wire of the test cable. The black wire of the 553-832 test cable is not used.
2. The voltage measured by the voltmeter should be within 0.2 and 0.8 volts. Detectors outputting a voltage outside this range should be cleaned or replaced.
3. If the Ion Detector voltage output is outside of the range, it should be removed and cleaned as described in the cleaning section. Re-check the voltage measurement on the Ion Detector; if the Ion Detector is still outside the voltage range after cleaning, replace the device.

5-7
firealarmresources.com

Cleaning

Introduction

If the device’s sensitivity is other than what is marked on the device’s label, clean the device using a source of oil-free, filtered, compressed air such as Dust-Off, Tech Duster, etc.
CAUTION: Notify appropriate building personnel prior to removing any detectors/sensors from service.

Photoelectric Smoke Detector/Sensor Cleaning

Blow the compressed air through the open vents around the device so that air enters and cleans the black chamber cover/insect screen assembly (Part No. 677-224) located beneath the white protective cover.
If the device’s sensitivity is still other than what is marked on the device’s label, replace the device.

Special Considerations for Ion Detectors and Sensors

Note: Do not remove the Ion Detector/ Sensor protective cover.
Blow compressed air through the open vents around the device so that air enters and cleans the black chamber cover assembly located beneath the white protective cover. If the device sensitivity is still outside the marked range replace the device and return the failed device to 130 Perinton Parkway, Fairport, NY 14450-9199.
IMPORTANT: Once cleaned, the detector/sensor should be tested with smoke per NFPA 72.

5-8
firealarmresources.com

Trouble Indications

Trouble Indications for TrueAlarm Sensors

The TrueAlarm smoke sensor is a measuring device that sends data regarding smoke density to the 4010, 4020, 4100, 4100+, 4100U, 4100ES, 4008, and 2120 fire alarm control panels (FACPs). The TrueAlarm heat sensor operates in a similar fashion, but sends temperature data instead of smoke density data. The FACP uses this data to determine whether a trouble has occurred.
The TrueAlarm sensor has two automatic trouble indications:
Dirty Excessively Dirty
A “Smoke Sensor Dirty” trouble condition is reported any time the average value on an individual sensor reaches a set threshold value. At this time, the FACP is still compensating for environmental factors and is holding the set sensitivity level.
A “Smoke Sensor is Excessively Dirty” trouble condition is reported anytime the average value of an individual sensor reaches a slightly higher set threshold level. At this point, the FACP can no longer compensate for environmental factors, and the sensitivity level may begin to drift. Although an “excessively dirty” trouble is reported, the sensor continues to operate and reports an alarm condition when one is detected.
In addition to the two automatic trouble conditions, the FACPs have digital pseudo points that must be turned ON to allow a TrueAlarm sensor that is close to being a dirty sensor to report as if it is “almost dirty.” This is useful when maintenance is being scheduled for dirty sensors, as it provides a means of seeing if other sensors are approaching a dirty state.
The table below shows your responsibilities when certain trouble indications occur.
Table 5-4. TrueAlarm Troubles and Descriptions

Trouble Indication

Description

Almost Dirty

Using the front panel keys, it is possible for a technical representative to turn ON a digital pseudo point in the FACP that allows an “almost dirty” sensor to report a trouble. Although the “almost dirty” sensor is holding its sensitivity level, you can schedule maintenance for the sensor before the dirty sensor trouble occurs.

Dirty

A “dirty” indication means that the sensor is holding its sensitivity level, but that you should schedule maintenance for the sensor. Clean the sensor as required and, when necessary, call your local branch office for service.

Excessively Dirty

The “excessively dirty” indication means that the sensor is no longer compensating for dirt and dust. Because nuisance alarms are possible with this condition, sensors must be cleaned or replaced immediately. When necessary, call your local branch office for service.

Self-Test Abnormal

All FACP system sensors are automatically tested once every minute. When a sensor fails to report properly to the FACP, a “Self-Test Abnormal” condition occurs. Since the sensor is not working properly, it must be replaced. Replace it, or call your local branch office for service.

Expired

The FACP panel generates an Expired trouble to notify the user that a replacement sensor is required. To clear the trouble, a new CRS with a valid date must be installed, and a hardware reset of the FACP panel must be performed.

5-9
firealarmresources.com

Continued on next page

Trouble Indications, Continued

Table 5-5. Sensor’s Analog Value

The panel will automatically indicate when a sensor is out of its sensitivity calibration. If

the sensor has an analog value below what is listed in the table, the sensor is within its

sensitivity setting.

Sensor’s Analog Value

Type

Almost Dirty Dirty

Excessively Dirty

Photo

115

120

135

Ion

135

140

155

To view a Sensor’s analog value, refer to your panels operating instructions

5-10
firealarmresources.com

Fire Alarm Trouble and Maintenance Log

Fire Alarm Trouble and Maintenance Log

Date

Time

Event/Description

Initials

5-11
firealarmresources.com

firealarmresources.com

Index

2 2120 CDT System
address setting, 3-5 2-Wire Relay Base Connections, 2-12 4 4010 System
address setting, 3-5 4020 System
address setting, 3-5 4100+ System
address setting, 3-5 4100U/ 4100ES System
address setting, 3-5 4120 System
address setting, 3-5 4-Wire Base Connections, 2-13 A Accessories, 4-1 Authorities Having Jurisdiction, 2-2 B Base compatibility, 5-2 Bases
4098, 2-8 wiring, 2-10 C Cautions and Warnings, iv Cleaning, 5-8 CO Sensor Bases, 1-8 CRS, replacing, 3-10, 3-11 Common Code Requirements, 2-8 Compatibility, 5-1 Copyrights, iii CRS replacing, 3-10, 3-11 D Detector compatibility, 5-2 Detectors placement, 1-5 Wall and Ceiling Mounted, 1-4 where not to place, 1-6 where to place, 1-3 E Environmental conditions, 1-6 H Heat Detectors 4098, 2-5 fixed temperature, 2-5 LED Base Connections, 2-14 models, 2-6 ROR Temperature, 2-5 specifications, 2-6 types, 2-5 HVAC Systems, 1-3 I IDNet Addresses, 3-6 Ionization Detectors testing, 5-7
1 IN-1

Isolator Sensor Bases connections, 3-9
M Magnetic Test, 5-5 Maintenance, 5-4 MAPNET Addresses, 3-6 Mulit-Sensor Bases
DIP Switch settings, 3-7 Multi-Sensor Bases, 3-7 N NFPA 70, 1-3 NFPA 72, 1-2, 1-3, 1-4, 2-2, 2-8, 3-1 NFPA 90A, 1-3 O Operation
principles of, 1-8 P Photoelectric Detectors
testing, 5-5 Programmer reports, 3-5 Q QuickConnect Smoke Sensors, 3-12
DIP Switch settings, 3-13 specifications, 3-12 R Rate-of-rise, 1-8 Relay module 2098-9737 wiring, 4-2 4098-9822 wiring, 4-3 accessories, 4-1 installation, 4-4 Remote LED module, 4-4 S Sensor base compatibility, 5-3 Sensor Compatibility, 5-3 Sensors Wall and Ceiling Mounted, 1-4 where not to place, 1-6 where to place, 1-3 Smoke Detector Application, 1-2 Smoke Detectors 4098, 2-2 limitations, 2-2 mounting, 2-4 photoelectric, 1-8 specifications, 2-3 Smoke Sensor Application, 1-2 Smoke Sensors photoelectric, 1-8 Style B or D Initiating Circuits, 2-11 T Test Equipment, 5-4 Testing, 5-4 detectors and sensors, 5-4 thermistors, 1-8 Trademarks, iii Trouble and Maintenance Log, 5-10

firealarmresources.com

Trouble Indications, 5-9 TrueAlarm Concepts, 1-8 TrueAlarm QuickConnect Smoke Sensors,
3-12 TrueAlarm Sensor Bases
4098, 3-3 setting the address, 3-4

specifications, 3-3 wiring, 3-8 TrueAlarm Sensors DIP Switch location, 3-4 special applications, 3-2 TrueAlarm Sensors, mounting, 3-2

IN-2 2
firealarmresources.com

firealarmresources.com

574-709 Rev. T
© 2008-2011 SimplexGrinnell LP. Specifications and other information were current as of publication and are subject to change without notice.
4
firealarmresources.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals