Simplex 4098 True Alarm Analog Addressable Detector Base Instruction Manual
- June 9, 2024
- Simplex
Table of Contents
- 4098 True Alarm Analog Addressable Detector Base
- 6-32 SCREW WITH WASHER (NOT SUPPLIED)
- 8-32 x 1 1/4″ PANHEAD MACHINE
- 8-32 x 1 1/4″ PANHEAD MACHINE
- 8 x 1″ THREAD FORMING PANHEAD SCREW
- 6-32 x 1 1/4″ PANHEAD SCREW (TIGHTEN TO 4-6 in.-lbs.)
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
4098 True Alarm Analog Addressable Detector Base
FIRE
4098 Detectors, Sensors, and Bases Application Manual
574-709 Rev. T
firealarmresources.com
ii
firealarmresources.com
Copyrights and Trademarks
Copyrights Trademarks
© 2008- 2011 SimplexGrinnell LP. All rights reserved. Specifications and other
information shown were current as of publication and are subject to change
without notice.
Suffix “C” or “CA” following an eight-digit Product ID number denotes ULC-
listed product.
Suffix “E” following an eight-digit Product ID number denotes Global product.
The second suffix identifies market country, models with this suffix are not
UL Listed.
Tyco, IDNet, Simplex and the Simplex logo are trademarks of Tyco International
Ltd. and its affiliates and are used under license.
MAPNET II Communication Net is protected by US Patent No. 4,796,025. TrueAlarm
Analog Detection is protected by US Patent No. 5,155,468. TrueAlarm Detector
Base is protected by US Patent No. 5,173, 683.
All illustrations of actual detectors, sensors, and bases shown in this
publication are artist’s renditions.
iii
firealarmresources.com
Cautions and Warnings
Cautions and Warnings
READ AND SAVE THESE INSTRUCTIONS- Follow the instructions in this installation
manual. These instructions must be followed to avoid damage to this product
and associated equipment. Product operation and reliability depend upon proper
installation.
DO NOT INSTALL ANY SIMPLEX® PRODUCT THAT APPEARS DAMAGED- Upon unpacking your
Simplex product, inspect the contents of the carton for shipping damage. If
damage is apparent, immediately file a claim with the carrier and notify an
authorized Simplex product supplier.
ELECTRICAL HAZARD – Disconnect electrical field power when making any internal
adjustments or repairs. All repairs should be performed by a representative or
authorized agent of your local Simplex product supplier.
STATIC HAZARD – Static electricity can damage components. Handle as follows:
Ground yourself before opening or installing components.
Prior to installation, keep components wrapped in anti-static material at all times.
FCC RULES AND REGULATIONS PART 15 – This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
iv
firealarmresources.com
Table of Contents
Copyrights and Trademarks ………………………………………………………………………………. iii
Copyrights……………………………………………………………………………………………………. iii
Trademarks………………………………………………………………………………………………….. iii
Cautions and Warnings …………………………………………………………………………………….. iv
Table of Contents ……………………………………………………………………………………………… v
Chapter 1 Overview …………………………………………………………………… 1-1
Introduction ……………………………………………………………………………………………….. 1-1 In this Chapter
…………………………………………………………………………………………… 1-1
Special Considerations …………………………………………………………………………………… 1-2 Overview
…………………………………………………………………………………………………… 1-2 Special Considerations for Smoke
Detectors and Sensors………………………………. 1-2 Smoke Detector/Sensor Applications
……………………………………………………………. 1-2
Where to Place Detectors and Sensors ……………………………………………………………. 1-3 Proper
Locations for Detectors and Sensors ……………………………………………….. 1-3
Where Not to Place Detectors and Sensors………………………………………………………. 1-6 Improper
Locations for Detectors and Sensors ………………………………………………. 1-6
Principles of Operation …………………………………………………………………………………… 1-8 Introduction
……………………………………………………………………………………………….. 1-8 Heat Detector
Operation……………………………………………………………………………… 1-8 Photoelectric Smoke
Detectors/Sensors ……………………………………………………….. 1-8 Ionization Smoke
Detectors/Sensors ……………………………………………………………. 1-8 Carbon Monoxide Gas
Detectors/Sensors …………………………………………………….. 1-8
Chapter 2 4098 Smoke Detectors, Heat Detectors and Bases………. 2-1
Introduction ……………………………………………………………………………………………….. 2-1 In this Chapter
…………………………………………………………………………………………… 2-1
4098 Smoke Detectors …………………………………………………………………………………… 2-2 Introduction
……………………………………………………………………………………………….. 2-2 Smoke Detector
Limitations…………………………………………………………………………. 2-2
Specifications…………………………………………………………………………………………….. 2-3 Mounting
Requirements………………………………………………………………………………. 2-4
4098 Heat Detectors………………………………………………………………………………………. 2-5 Introduction
……………………………………………………………………………………………….. 2-5 Heat Detector
Types…………………………………………………………………………………… 2-5
Specifications…………………………………………………………………………………………….. 2-5
4098 Bases…………………………………………………………………………………………………… 2-8 Introduction
……………………………………………………………………………………………….. 2-8 Mounting
…………………………………………………………………………………………………… 2-9
Wiring……………………………………………………………………………………………………… 2-10
Chapter 3 TrueAlarm Sensors, Sensor Bases, and QuickConnect Smoke Sensors
………………………………………………………………………… 3-1
Introduction ……………………………………………………………………………………………….. 3-1
v
firealarmresources.com
In this Chapter …………………………………………………………………………………………… 3-1
4098 TrueAlarm Sensors………………………………………………………………………………… 3-2
Specifications…………………………………………………………………………………………….. 3-2 Special
Applications……………………………………………………………………………………. 3-2 Mounting
…………………………………………………………………………………………………… 3-2
4098 TrueAlarm Sensor Bases ……………………………………………………………………….. 3-3 Introduction
……………………………………………………………………………………………….. 3-3
Specifications…………………………………………………………………………………………….. 3-3 Setting the Base’s
Address………………………………………………………………………….. 3-3 Address Setting for the 2120 CDT
System…………………………………………………….. 3-5 Address Setting for the 4010, 4020, 4100+,
4100U, 4100ES, 4008, or 4120 System3-5 Multi-Sensor Bases 4098-9795 and
4098-9796 …………………………………………….. 3-7
Wiring……………………………………………………………………………………………………….. 3-7
4098 TrueAlarm QuickConnect Smoke Sensors………………………………………………. 3-12 Overview
…………………………………………………………………………………………………. 3-12
Specifications…………………………………………………………………………………………… 3-12 Setting the Sensor’s
Address ……………………………………………………………………. 3-13
Wiring……………………………………………………………………………………………………… 3-14
Chapter 4 Accessories ………………………………………………………………. 4-1
Introduction ……………………………………………………………………………………………….. 4-1 In this Chapter
…………………………………………………………………………………………… 4-1
Relay Module Accessories ……………………………………………………………………………… 4-2 2098-9737 Relay
Module Wiring …………………………………………………………………. 4-2 4098-9822 Relay Module Wiring
………………………………………………………………….. 4-3 Relay Module
Installation…………………………………………………………………………….. 4-4 Remote LED Module
………………………………………………………………………………….. 4-4
Chapter 5 Compatibility and Testing ………………………………………….. 5-1
Introduction ……………………………………………………………………………………………….. 5-1 In this Chapter
…………………………………………………………………………………………… 5-1
Compatibility …………………………………………………………………………………………………. 5-2 Compatibility for
4098 Detectors and Detector Bases……………………………………… 5-2
Maintenance and Testing ……………………………………………………………………………….. 5-4 Maintenance
……………………………………………………………………………………………… 5-4 Preferred Method of Testing Smoke
Detectors/Sensors………………………………….. 5-4 Test Equipment Available
……………………………………………………………………………. 5-4 Alternate Method for Testing Sensors
…………………………………………………………… 5-5 Magnetic Test for Photoelectric
Detectors……………………………………………………… 5-5 Magnetic Test for Ionization Detectors
………………………………………………………….. 5-7 Ion Detector Sensitivity Test
………………………………………………………………………… 5-7
Cleaning……………………………………………………………………………………………………….. 5-8 Introduction
……………………………………………………………………………………………….. 5-8 Photoelectric Smoke Detector/Sensor
Cleaning …………………………………………….. 5-8 Special Considerations for Ion Detectors and
Sensors ……………………………………. 5-8
Trouble Indications ………………………………………………………………………………………… 5-9 Trouble Indications
for TrueAlarm Sensors ……………………………………………………. 5-9
Trouble Indications, Continued………………………………………………………………………. 5-10
vi
firealarmresources.com
Fire Alarm Trouble and Maintenance Log ……………………………………………………….. 5-11 Fire Alarm
Trouble and Maintenance Log …………………………………………………… 5-11
Index …………………………………………………………………………………………………………….. I-1
vii
firealarmresources.com
firealarmresources.com
Chapter 1 Overview
Introduction In this Chapter
The purpose of this publication is to provide information concerning the
proper application of both heat and smoke detectors/sensors in conjunction
with fire alarm systems.
The information in this publication is intended to be used only as a technical
guide. The requirements of applicable codes and standards, as well as
directives of Authorities Having Jurisdiction (AHJ’s), should be followed.
Refer to the page number listed in this table for information on a specific topic.
Topic Special Considerations Where to Place Detectors and Sensors Where Not to Place Detectors and Sensors Principles of Operation
See Page # 1-2 1-3 1-6 1-8
1-1
firealarmresources.com
Special Considerations
Overview
Special Considerations for Smoke Detectors and Sensors
Smoke Detector/Sensor Applications
Before installing detectors/sensors, make a survey of the area to be covered
in accordance with information provided in NFPA 72, (an excerpt of which is
provided in the “Smoke Detector/ Sensor Applications” section below). For
additional information, refer to NFPA 72 and the NEMA Guide for Proper Use of
System Smoke Detectors.
Is there human occupancy? Contents to be protected. Type of construction and
use. Burning characteristics of contents. Air movement – stratification.
Deflections and obstructions. Height of ceilings. Surface conditions of
ceilings. Type of ceiling construction. Total area. Vent locations –
velocities – dilution.
Each detector/sensor is capable of providing up to 900 square feet (84 square
meters) of coverage, depending on the following:
Requirements of local codes. Results of engineering evaluation.
1-2
firealarmresources.com
Where to Place Detectors and Sensors
Proper Locations for Detectors and Sensors
IMPORTANT:
The guidelines in this section are adapted from standards published by the National Fire Protection Association, Quincy, Massachusetts, U. S. A. These standards include NFPA 72, “National Fire Alarm Code”; NFPA 70, “National Electrical Code”, Article 760; and NFPA 90A, “Standard for the Installation of Air Conditioning and Ventilating Systems.”
To provide effective early warning of a developing fire situation, smoke
detectors/sensors should be installed in all areas of the protected premises.
Total coverage as defined by NFPA 72 should include all rooms, halls, storage
areas, basements, attics, lofts, and spaces above suspended ceilings including
plenum areas utilized as part of the HVAC system. In addition, this should
include all closets, elevator shafts, enclosed stairways, dumbwaiter shafts,
chutes and other subdivisions and accessible spaces.
Fire detection systems installed to meet local codes or ordinances may not be
adequate for early warning of the fire. Some codes or ordinances have minimum
objectives such as capturing elevators or preventing circulation of smoke
through HVAC systems instead of early detection of fire.
You should weigh the costs against the benefits of installing a complete fire
detection system when any detection system is being installed. The location,
quantity and zoning of detectors/sensors should be determined by what
objectives are desired rather than the minimum requirements of any local codes
or ordinances.
Detectors/sensors may be omitted from combustible blind spaces when any of the
following conditions prevail:
Where the ceiling is attached directly to the underside of the supporting
beams of a combustible roof or floor deck.
Where the concealed space is entirely filled with noncombustible insulation.
(In solid joist construction, the insulation need only fill the space from the
ceiling to the bottom edge of the joist of the roof or floor deck.)
Where there are small concealed spaces over rooms, provided the space in
question does not exceed 50 square feet (4.6 square meters).
In spaces formed by sets of facing studs or solid joists in walls, floors, or
ceilings where the distance between the facing studs or solid joists do not
exceed 6 inches (15 cm).
Detectors/sensors may also be omitted from below open grid ceilings where all
of the following conditions are met:
The openings of the grid are at least 1/4 inch (6 mm) in the smallest
dimension.
The thickness of the material does not exceed the smallest of the grid
openings.
The openings constitute at least 70% of the area of the ceiling material.
Continued on next page
1-3
firealarmresources.com
Where to Place Detectors and Sensors, Continued
Proper Locations for Detectors and Sensors
Detectors/sensors are usually required or recommended underneath open loading docks or platforms and their covers, and in accessible under-floor areas in buildings without basements. Detectors/sensors may be omitted from combustible blind spaces when all of the following conditions prevail:
1. The space is not accessible for storage purposes, it is protected against
the entrance of unauthorized persons, and it is protected against the
accumulation of windblown debris.
2. The space contains no equipment/structures (such as steam pipes,
electrical wiring, ducts, shafts, or conveyors) that could potentially ignite
or conduct the spread of fire.
3. The floor over the space is tight.
4. Non flammable liquids are processed, handled, or stored on the floor above
the space.
“Total coverage” as described in NFPA 72, is the definition of a complete fire detection system. In some of the specified areas of coverage, such as attics, closets, under open loading docks or platforms, a heat detector may be more appropriate than a smoke detector. Careful consideration should be given to the detector manufacturer’s instructions and the following recommendations in this guide.
In general, when only one detector/sensor is required in a room or space, the detector/sensor should be placed as close to the center of the ceiling as possible. Central location of the detector/sensor is best for sensing smoke and/or fire in any part of the room. If a center location is not possible, it may be placed no closer than 4 inches (10 cm) from the wall, or if listed for wall mounting, it may be mounted on the wall. Wall mounted detectors/sensor should be located approximately 4 to 12 inches (10 to 30 cm) from the ceiling to the top of the detector, and at least 4 inches (10 cm) from any corner wall junction (see the figure below). FigureTag FD4-709-01
Ceiling
4in (10 cm)
Acceptablehere
Never here
Top of the detector acceptablehere
Note:
McleoasseusNMoerttaees:eurmedmegentnessthoasowfsntahhreoetotwhdenetaercetotor. the closestedgeofthedetector.
4in (10 cm) Minimum
12in (30 cm) Maximum
Side wall
Figure 1-1. Wall and Ceiling Mounted Detector/Sensor Continued on next page
1-4
firealarmresources.com
Where to Place Detectors and Sensors, Continued
Proper Locations for Detectors and Sensors
When an air supply and/or an air return duct opening is present in a room or space, the
detector/sensor(s) should be placed in the path of the air flow toward the return air duct opening
(see below).
FigureTag FD4-709-02
Return air
Correct
Supply air
Incorrect
Figure 1-2. Detector Placement – Air Supply and/or Return Ducts
Smoke tests are helpful in determining proper placement. Special attention
should be given to smoke travel directions and velocity, since either can
affect detector/sensor performance.
Placement of a detector/sensor near air conditioning or incoming air vents can
also cause excessive accumulation of dust and dirt on the detector/sensor.
This dirt can cause the detector/sensor to malfunction and cause nuisance
alarms. Detectors/sensors should not be located closer than 3 feet (0.9 m)
from an air supply diffuser.
Spot type detectors/sensors in properly engineered systems, may also be placed
in return air ducts, or in approved duct detector housings designed for this
application. Although duct detectors are not a substitute for open area
detectors, they can provide an effective method of initiating building control
functions to prevent smoke from being transported from the fire area to other
parts of a building.
1-5
firealarmresources.com
Where Not to Place Detectors and Sensors
Improper Locations for Detectors and Sensors
One of the major causes of nuisance alarms is improper placement of detectors/sensors. The best way to avoid nuisance alarms is to not install detectors/sensors in environments that can cause them to malfunction. See the table and examples provided below.
Table 1-1. Environmental Conditions that Influence Detector Response*
Detection Protection
Air Velocity >300 ft.
(91.4m)/min.
Atm. Pressure 3000 ft. (914m) Above Sea Level
Ion
X
X
Photo
O
O
Beam
O
O
Air Sampling
O
O
- See Table A-5-3.6.1.1 in NFPA 72 X = May affect detector/sensor response O = Generally does not affect detector/sensor response
Humidity >93% RH
X X X X
Temp. <32°F (0C) >100°F (38C)
X X X X
Color of Smoke
O X O O
DO NOT PLACE DETECTORS/SENSORS:
In excessively dusty or dirty areas, such as feed rooms, steel mills, etc.
Dust and dirt can accumulate on the detector/sensor’s sensing chamber and make
it overly sensitive, or block the air entrances to the sensing chamber and
make the detector/sensor less sensitive to smoke. Be especially careful to
avoid areas where fumigants, fog or mist-producing materials, or sweeping and
cleaning compounds are used. These substances may cause nuisance alarms.
Outdoors, in stables, open storage sheds, or other open structures affected by
dust, air currents, or excessive humidity and temperature.
In damp or excessively humid areas, or next to bathrooms with showers. Water
droplets can accumulate inside the sensing chamber and make the
detector/sensor overly sensitive. A tremendous amount of humid air is produced
during a hot shower. The moisture in this humid air can enter the sensing
chamber as water vapor, then cool and condense into droplets that can cause a
nuisance alarm.
In elevator lobbies over ashtrays or where people smoke while waiting for the
elevator.
In very cold or very hot environments, or in unheated buildings or rooms where
the temperature can fall below or exceed the operating temperature range of
the detector/sensor. At temperatures below 32° F (0° C), ice crystals or
condensation can appear inside the sensing chamber and make it overly
sensitive or cause a nuisance alarm. At temperatures above the operating range
of the detector/sensor greater than 120° F (49° C), its internal components
may not function properly.
In or near areas where combustion particles are normally present, such as in
kitchens or other areas with ovens and burners; in garages, where particles of
combustion are present in vehicle exhausts; within 15 feet (4.5 meters) of any
type of furnace, hot water heater, or gas space heater; or in welding shops or
other types of work areas where some form of combustion is used in the
activity normally conducted in that area. When a detector must be located in
or adjacent to such an area, a fixed temperature heat detector may be
appropriate.
Continued on next page
1-6
firealarmresources.com
Where Not to Place Detectors and Sensors, Continued
Improper Locations for Detectors and Sensors
In air streams passing by or through kitchens. Air often enters a residence or
a residential unit of an apartment building through cracks around the front
and/or back doors. If the air return is in the bedroom hallway or in the
bathroom, and if air from the kitchen easily enters the air stream going from
the door to the air return, combustion particles from cooking can cause
nuisance alarms. Install detectors/sensors so that they protect the bedrooms,
but so they are out of the air stream.
In or near manufacturing areas, battery rooms, or other areas where
substantial quantities of vapors, gases or fumes may be present. Strong
vapors, like excessive humidity, can make detectors/sensors overly sensitive
or less sensitive than normal. In very large concentrations, gases heavier
than air, such as carbon dioxide, may make detectors/sensors more sensitive,
while gases lighter than air, such as helium, may make them less sensitive.
Aerosol particles may collect on detector/sensor chamber surfaces and cause
nuisance alarms.
Insect-infested areas. If insects enter a detector/sensor’s sensing chamber,
they can cause a nuisance alarm. Take proper insect eradication procedures
before installing detectors/sensors in such locations. If spraying is done, do
not allow insect spray to enter the detectors/sensors.
Near fluorescent light fixtures. Electrical noise generated by fluorescent
light fixtures may cause nuisance alarms. Install detectors/sensors at least 1
foot (0.3 meters) away from such light fixtures.
When using the CO Base for CO fire detection, do not install in locations that
could have potentially high non-fire levels of CO.
Underwriters Laboratories (UL) has three standards for smoke detectors: one
for duct detectors/sensors, UL 268A; one for single and multiple station
detectors/sensors, UL 217; and one for system type detectors/sensors, UL 268.
Detectors/sensors should only be used in the applications for which they are
specifically listed.
The NFPA 101 Life Safety Code states that single station smoke detectors shall
sound an alarm only within an individual living unit or similar area and shall
not actuate the building fire alarm system. It also states, “All systems and
components shall be approved for the purpose for which they are installed.”
In addition to possible code noncompliance, the following deficiencies would
exist in a series of residential smoke detectors connected in a fire alarm
system mode:
Since the fire alarm system is not supervised, vandals or others could
disconnect a detector or the entire system, leaving a building without
protection. The residents would be unaware of the serious life threatening
condition.
Residential detectors do not latch in alarm. In other words, the detector
self-resets. One detector in alarm sounds all the detectors connected
together. It would be difficult to identify or locate a specific detector that
initially put the system into alarm after the alarm condition was cleared.
System detectors/sensors latch in alarm. They do not reset until power is
momentarily disconnected. This makes it convenient to identify the location of
the detector/sensor that caused the control panel to alarm. In addition,
system detectors are specifically designed to connect to a supervised control
panel. Two-wire detectors require a UL compatibility review to verify that the
detector and panel properly operate together. A typical life safety fire alarm
system for an apartment complex would be to use system detectors/sensors and
manual fire alarm stations in the hallways and common areas of the complex and
residential single station type detectors and heat detectors in the individual
apartments. The system detectors/sensors, manual stations and heat detectors
would be connected to a supervised control panel, sound a general alarm and
automatically notify the proper authorities that a fire condition exists. The
residential detectors located in the apartments would be interconnected only
within the individual living quarters of each apartment. These residential
units would sound an alarm only in the apartment unit.
1-7
firealarmresources.com
Principles of Operation
Introduction
This section describes how the different types of detectors and sensors work. For additional information on TrueAlarm sensor operation, refer to the TrueAlarm Concepts publication (PER-91-024).
Heat Detector Operation
The heat detector senses the heat or the Rate-of-Rise (ROR) in the air
temperature of the environment in which it is located. The heat detector is
comprised of electronic circuitry and a mechanical package that is designed to
sense the ROR of the air temperature in an expedient and reliable fashion.
Upon detection of an abnormal increase in air temperature, or ROR in air
temperature, the electronics indicate an alarm by increasing the amount of
current draw from the monitor zone it is connected to. The monitor zone is a
supervised detection circuit that is tied back to a main control panel that
takes appropriate action to indicate an alarm has been reported, if the zone
current is substantially increased.
Being of an electronic design, the temperature of the air is sensed by using
two negative temperature coefficient thermistors. The resistance of the
thermistors goes down with an increase in temperature. One thermistor is
placed in a position such as to sense the open air temperature very rapidly
(RT1). The second thermistor is positioned in a small cavity that protrudes
out from the main body of the detector (RT2). The location of RT2 allows for
fast detection of a quick change in the air temperature, but yet for a slow or
medium rate of temperature change, the detector does not trip due to the ROR
feature. For a slower change in temperature, the detector trips into alarm due
to a set fixed temperature that is sensed by RT1. For a fast temperature rise,
when a difference in temperature sensed by RT1 and RT2 has reached a
predetermined amount, the detector trips into alarm.
Photoelectric Smoke Detectors/Sensors
These devices operate on a light scattering principle. The smoke sensing chamber contains an infrared LED source with a peak spectral emission of 880 nanometers. This source is placed at an angle from a spectrally matched photodiode receiver. During a NO SMOKE condition, only light reflected from the chamber walls enters the receiver and shows up as a small photocurrent. As smoke particles enter the sensing chamber and cross the light beam of the LED, more light reaches the receiver due to scattering. The receiver circuitry converts this photocurrent into a signal voltage. In a detector, when this voltage reaches a preset level, an alarm is produced. In a sensor, this signal voltage goes into an 8-bit, A to D (analog to digital) converter. A digital representation of this signal voltage is then transmitted to the fire alarm panel for further processing.
Ionization Smoke Detectors/Sensors
These devices use a small radiation source, Americium-241, which emits alpha particles that ionize air molecules between two electrically charged electrodes. With the application of a DC voltage .to these electrodes, a small ionization current flows within the chamber. As smoke enters the chamber, a decrease in ionization current results. This current is converted into a signal voltage by a transimpedance circuit. In a detector, when this signal voltage drops below a preset level, an alarm is produced. In a sensor, this signal voltage goes into an 8-bit A to D (analog to digital) converter. A digital representation of this signal voltage is then transmitted to the fire alarm panel for further processing.
Carbon Monoxide Gas Detectors/Sensors
The CO Sensor and Sounder Bases with a CO Replaceable Sensor (CRS) module work in conjunction with existing detector heads. The CO Sensor Base enhances fire detection and provides the ability to combine fire and toxic gas leakage detection in a single device. The CO sensor measures the concentration of carbon monoxide gas in the air in part per million (PPM). When toxic gas operation is selected, the FACP panel may generate either a supervisory, utility or priority 2 alarms. The alarm level is calculated within the panel based on the time integrated CO levels that have been measured at the detector.
1-8
firealarmresources.com
Chapter 2 4098 Smoke Detectors, Heat Detectors and Bases
Introduction In this Chapter
This chapter contains specification and mounting information for 4098 Smoke Detectors, Heat Detectors, and Bases.
Refer to the page number listed in this table for information on a specific topic.
4098 Smoke Detectors 4098 Heat Detectors 4098 Bases
Topic
See Page # 2-2 2-5 2-8
2-1
firealarmresources.com
4098 Smoke Detectors
Introduction
Smoke Detector Limitations
CAUTION:
Install the detectors described in this publication in accordance with applicable NFPA standards, local codes, and the Authorities Having Jurisdiction (AHJs). Failure to follow these instructions may result in failure of the detector to initiate an alarm condition. The manufacturer is not responsible for detectors that have been improperly installed, tested, or maintained.
The smoke detectors used with these bases are designed to activate and
initiate emergency action, but do so only when used in conjunction with other
equipment. They are designed for installation in accordance with NFPA 72
National Fire Alarm Code.
Smoke detectors do not work without power. AC or DC powered smoke detectors do
not work if the power supply is cut off for any reason.
Smoke detectors do not sense fires when smoke does not reach the detectors.
Smoke from fires in chimneys, in walls, on roofs or on the other side of
closed doors may not reach the smoke detector and alarm it.
A detector may not detect a fire developing on another level of a building.
For this reason, detectors should be located on every level of a building.
Smoke detectors have sensing limitations. Ionization detectors are better at
detecting fast, flaming fires than slow, smoldering fires. Photoelectric
detectors sense smoldering fires better than flaming fires. Because fires
develop in different ways, and are often unpredictable in their growth,
neither type of detector is always best, and a given detector may not always
provide warning of a fire. In general, detectors cannot be expected to provide
warning for fires resulting from inadequate fire protection practices, violent
explosions, escaping gases, improper storage of flammable liquids like
cleaning solvents, other safety hazards, or arson.
Smoke detectors cannot last forever. Smoke detectors contain electronic parts.
Even though detectors are made to last for many years, any of these parts
could fail at any time. Therefore, test your smoke detector system per NFPA 72
at least annually. Clean and take care of your smoke detectors regularly. (See
Chapter 5 of this publication for cleaning instructions.)
Continued on next page
2-2
firealarmresources.com
4098 Smoke Detectors, Continued
Specifications
Table 2-1. Smoke Detector Specifications
Specifications
Detector PID (4098)
Type of Detector
Working Voltage (2-wire)
Rated Voltage (4-wire)
Input Ripple Voltage
Max. Alarm Current
Surge Current
Standby Current
Heat Element Rating
Humidity Range (Non-Condensing)
Air Velocity Range
-9601, -9605 Photoelectric 8.5 33 VDC 15 32 VDC
25% Max. 86 mA <200 A <100 A N/A
10-95% RH 0-2000 FPM
Smoke Detector Data
-9602 Photoelectric
with Heat 8.5 33 VDC
-9603 Ionization 8.5 33 VDC
15 32 VDC
15 32 VDC
25% Max.
25% Max.
86 mA <200 A <100 A 135 F
86 mA <200 A <100 A
N/A
10-95% RH
10-95% RH
0-2000 FPM
0-200 FPM
Continued on next page
2-3
firealarmresources.com
4098 Smoke Detectors, Continued
Mounting Requirements
All smoke detectors identified in Table 2-1 mount to a detector base (refer to
the “4098 Bases” section of this chapter for more information). Use the
following considerations and Figure 2-1 when mounting smoke detectors.
IMPORTANT: Smoke must enter the chamber of the detector. Thus, air flow, air
stratification, air velocity, air stagnation, and air migration affects
detector efficiency.
Note: Where the possibility of positive airflow from the electrical
conduit/junction box exists, seal the conduit openings with 3M Weatherban #606
(or equivalent), a non-flammable sealing compound.
Do not install detectors in areas where temperatures are likely to exceed 100
F (38 C) or fall below 32 F (0 C).
Because the 4098-9602 detector combines heat sensing, DO NOT install this
detector in locations where the ambient temperatures exceed 100 F (38 C) or
where temperature fluctuations above 6 F/min. occur.
Do not install detectors on a ceiling within 4 inches (10 cm) of a wall.
Do not install detectors where forced air ventilation may dilute the smoke
before it reaches the detector.
Do not install detectors in areas where smoke is normally present (kitchens,
furnace rooms, laundry rooms, loading docks, rooms with fireplaces, rooms with
candles, soldering rooms, etc.).
Do not install detectors in areas where there is likely to be steam (in
hospital patient rooms with vaporizers, near shower rooms, above large sinks,
etc.).
Do not install detectors above ashtrays in elevator lobbies.
Wall-mounted detectors should be located 4 to 12 inches (10-30.5 cm) from the
ceiling to detector head.
Protect all detector heads during construction to avoid infiltration of
construction debris. Remove any protective covers before activating the
system.
If using the adapter plate, tighten the mounting screws without warping the
adapter plate.
2-4
firealarmresources.com
4098 Heat Detectors
Introduction
This section contains general notes, specifications, and mounting information for the heat detectors shown in Table 2-2.
WARNING: Notes:
Heat detectors are NOT life-safety devices; USE HEAT DETECTORS FOR PROPERTY PROTECTION ONLY! For life-safety requirements, use smoke detectors.
For all heat detectors, provide electronic supervision with battery back-up at
the fire alarm control panel.
Where the possibility of positive airflow from the electrical conduit/junction
box exists, seal the conduit openings with 3M Weatherban #606 (or equivalent),
a non-flammable sealing compound.
Refer to NFPA 72 for application, test, and maintenance requirements.
Heat Detector Types
Fixed Temperature Heat Detectors:
Electronic fixed temperature heat detectors use a fast response, thermistor
based design to provide temperature sensing that quickly, accurately, and
consistently identifies when fixed temperatures are exceeded. For this reason,
the fixed temperature detectors are recommended for most applications. With a
UL spacing distance of 60 X 60 feet, the fixed temperature electronic heat
detectors replace both mechanical fixed as well as mechanical ROR heat
detectors.
ROR Temperature Heat Detectors:
Electronic Rate-of-Rise (ROR) heat detectors detect fixed temperature alarm
thresholds the same as the fixed temperature heat detectors, plus detect a ROR
alarm with a patented ROR detection design that can quickly respond to sudden
temperature variations. Due to the nature of the fast response to temperature
changes, care must be taken for proper installation of ROR heat detectors. ROR
heat detectors should be installed in stable environmentally controlled areas.
These detectors must not be installed where hot or cold air can be blown on
them (near ductwork, industrial equipment, air vents etc.). ROR detectors
should not be installed where more then 6 F per minute temperature changes can
normally occur.
Specifications
Features: Rate-of-Rise and Fixed Temperature (see Table 2-2) Alarm LED
Compatible with 2-Wire Initiating Device Circuits Current-Limited Alarm State
Electrical Specifications: Typical Standby Current – 80 Microamps Typical
Alarm Current – 40 Milliamps Maximum Current – 80 Milliamps while in alarm
state Operating Range – 15-32 VDC Maximum Ripple Voltage Allowed – 30%
2-5
firealarmresources.com
Continued on next page
4098 Heat Detectors, Continued
Specifications
Table 2-2. Heat Detector Models and Features
Detector Model
Rating or Class*
Area / Language
4098-9612 (UL)
135 F (57 C) FT
English
4098-9613 (UL)
135 F (57 C) FT and RR
English
4098-9614 (UL)
200 F (93 C) FT
English
4098-9615 (UL)
200 F (93 C) FT and RR
English
4098-9616E
A1
European
4098-9617E
C
European
4098-9618E
A
Australian
4098-9619E
B
Australian
4098-9621E
D
Australian
4098-9622E
I
Chinese
4098-9624E
134 F (56.7 C) FT
Korean
4098-9625E
134 F (56.7 C) FT and RR
Korean
4098-9626E
134 F (56.7 C) FT
Taiwanese
4098-9627E
134 F (56.7 C) FT and RR Taiwanese
4098-9628E
190 F (87.8 C) FT
Korean
4098-9629E
190 F (87.8 C) FT and RR
Korean
4098-9630E
190 F (87.8 C) FT
Taiwanese
4098-9631E
190 F (87.8 C) FT and RR Taiwanese
- RR abbreviates Rate-of-Rise; FT abbreviates Fixed-Temperature.
Color Code
White White Green Red White Blue Red Green
Continued on next page
2-6
firealarmresources.com
4098 Heat Detectors, Continued
Specifications
All heat detectors identified in the table below mount to a detector base
(refer to the “4098 Bases” section of this publication for more information).
Use the information in Figure 2-1 when mounting.
Table 2-3. Heat Detector Specifications
Product ID 4098-9612 4098-9613 4098-9614 4098-9615
Description
Application
Fixed-Temp. Only, 135 F (57 C)
Fixed-Temp. and Rate-of-Rise, 135 F (57 C)
Fixed-Temp. Only, 200 F (93 C)
Fixed-Temp. and Rate-of-Rise, 200 F (93 C)
Unusually violent temp. fluctuations
and ceiling temperatures not
exceeding 100 F (38 C)
Normal temp. fluctuations and ceiling temperatures not exceeding 100 F
(38 C)
Unusually violent temp. fluctuations
and ceiling temperatures exceeding 100 F (38 C) but not 150 F (68 C)
Normal temp. fluctuations and ceiling temperatures exceeding 100 F (38 C) but
not 150 F (68 C)
Max. Spacing Allowed (UL)
70 X 70 ft (21 X 21 m)
70 X 70 ft (21 X 21 m)
70 X 70 ft (21 X 21 m)
70 X 70 ft (21 X 21 m)
FM
RTI = Quick 20 X 20 ft
(6.1 X 6.1 m)
RTI = Quick 20 X 20 ft
(6.1 X 6.1 m)
RTI = Quick 20 X 20 ft
(6.1 X 6.1 m)
RTI = Ultra Fast 50 X 50 ft
(15.2 X 15.2 m)
2-7
firealarmresources.com
4098 Bases
Introduction
The 4098-9788 base is designed to be used with 4098 Series smoke and heat
detectors, as well as the QuickConnect2 photo sensor. To use a 4-wire
configuration, you must use the 4098-9682 relay base. Heat detectors require
the 4098-9684 base when used with a remote LED. This section only covers the
information necessary to mount and wire these base configurations. Before
installing these bases, make a survey of the area to be covered in accordance
with information provided in NFPA 72. For additional information, refer to the
NEMA Guide for Proper Use of System Smoke Detectors.
CAUTION: Install the bases in this section in accordance with applicable NFPA
standards, local codes, and Authorities Having Jurisdiction (AHJs). Failure to
follow these instructions may result in failure of the detector to initiate an
alarm condition. The manufacturer is not responsible for detectors that have
been improperly installed, tested, or maintained.
Continued on next page
2-8
firealarmresources.com
4098 Bases, Continued
Mounting
The 4098-9788 base mounts to a 4-inch octagonal, 4-inch square, or single gang electrical box. When mounting to a 4-inch square or any surface mounted box, the 4098-9832 adapter plate kit must be used.
ALL BASES FLUSH MOUNTED (BOX TO BE FLUSH OR RECESSED 1/4 ” MAX )
SINGLE GANG (2 1/8″ DEEP) ELECTRICAL BOX (NOT SUPPLIED)
4098-9789, -9791, -9792, -9796 AND ALL DETECTOR BASES FLUSH MOUNTED (BOX TO BE FLUSH MOUNTED OR RECESSED 1/4″ MAX)
4″ (10.16cm x 1 1/2″ DEEP) OCTAGONAL
ELECTRICAL BOX ( NOT SUPPLIED)
4″ (10.16cm x 1 1/2″ DEEP) SQUARE
ELECTRICAL BOX (NOT SUPPLIED)
4098-9794, AND 4098-9795 ONLY FLUSH MOUNTED
(BOX WITH ADAPTER BRACKET TO BE FLUSH OR RECESSED 1/4″ MAX)
6-32 SCREW WITH WASHER (NOT SUPPLIED)
(SEE NOTE 4)
BASE
8-32 x 1 1/4″ PANHEAD MACHINE
SCREW (TIGHTEN TO 4-6 in.-lbs.)
4098-9832 ADAPTER PLATE KIT (REQUIRED FOR 4″ SQUARE/ OCTAGONAL SURFACE MOUNTED ELECTRICAL BOX)
RACO 787 ADAPTER BRACKET
OR EQUIVALENT (NOT SUPPLIED)
8-32 x 1 1/4″ PANHEAD MACHINE
SCREW (TIGHTEN UNTIL SNUG,
1-3 in.-lbs.)
8 x 1″ THREAD FORMING PANHEAD SCREW
(TIGHTEN TO 4-6 in.-lbs.)
BASE
6-32 x 1 1/4″ PANHEAD SCREW (TIGHTEN TO 4-6 in.-lbs.)
SENSOR (AS REQUIRED) SEE NOTES 1 AND 2
CLOCKWISE FOR ATTACHMENT
Figure 2-1. Typical Detector/Sensor Mounting
Notes:
1. Break off plastic lock tab to engage locking mechanism. To lock
detector/sensor into base, turn unit until the locking tab clicks into place.
To unlock detector/sensor, insert the blade of a screwdriver into this slot
and then pull down on handle. This action allows the detector/sensor to be
turned and removed (see Figure 2-1).
2. Refer to the “Compatibility and Testing” chapter of this publication for
detailed information on compatible detectors/sensors.
3. Bases with relay modules require a 1 ½-inch extension ring (not supplied)
mounted to the 4-inch square or octagonal electrical box to meet the space
requirement of the relay cube and its wires. The relay module(s) cannot be
used in single-gang electrical box installations. The relay cube 4098-9822
must be installed in the electrical box directly behind the sensor base.
4. Use Adapter Plate Kit 4098-9832 when mounting the 4098-9794 and 4098-9795
to a surface mounted 4-inch square or octagonal box. Adapter plates must be
installed with textured side towards the electrical box for this installation
only.
Continued on next page
2-9
firealarmresources.com
4098 Bases, Continued
Wiring
All screw terminals accommodate 14 to 18 AWG solid or stranded wire. When
tightening screws, the range of torque is 8 to 12 in-lbs. Connect wiring to
the terminals shown in the figure below. (Figures 2-2 through 2-6 show typical
wiring applications for the 4098 bases.) CAUTION: Do not loop wire under
terminals. Break wire run to provide
supervision of connections.
2
1
3
4
See Note 2 See Note 1 See Note 3
Figure 2-2. Wiring and Mounting the Bases FigureTag FD4-709-03 Notes:
1. Break off plastic tab where indicated to engage locking mechanism. 2. Once
locking mechanism is engaged, you must insert a flat-head screwdriver in slot
indicated to release the detector from the base. 3. Use the slotted hole
indicated for the first screw when mounting the base.
Continued on next page
2-10
firealarmresources.com
4098 Bases, Continued
Wiring
–
- INITIATING CIRCUIT
+ –
BACKUP 2 (SEE NOTE 3)
PRIMARY 1 (SEE NOTE 3)
(SEE NOTE 5 )
(SEE NOTE 4) 4098-9788
BASE
(SEE NOTE 5 )
4098-9788 BASE
(SEE NOTE 5)
4098-9788 BASE
EOL RESISTOR (IF USED)
LISTED SIMPLEX FIRE ALARM CONTROL
PANEL 2120, 4001, 4002 4020, 4100+, 4100U, 4100ES, 4004, 4005 OR 4006
4 3
1 2
4 3
1 2
4 3
1 2
(SEE NOTE 2)
RED
BLK
REMOTE LED 4098-9830
(SEE NOTE 1)
RED
BLK
REMOTE LED 4098-9830
(SEE NOTE 1)
FigureTag FD4-709-04 Figure 2-3. 4098-9788 Base Connections for Style B or D
Initiating Circuits
Notes:
1. If used, 4098-9830 Remote LED is polarized. Refer to Figure 2-6 to wire
remote LED to the Heat Detector; observe color-coded wiring.
2. Refer to wiring diagrams provided with system panel for proper End-Of-Line
(EOL) resistor value.
3. It is recommended that the Primary-1 and the Backup-2 lines be in separate
wire runs and in compliance with local requirements.
4. For Style D initiating circuit, wire per dotted lines and do not use EOL
resistor.
5. Break wires before connecting to Terminal 4 to maintain supervision. Do
not loop wire underneath Terminal 4.
Continued on next page
2-11
firealarmresources.com
4098 Bases, Continued
Wiring
FigureTag FD4-709-05
–
- INITIATING CIRCUIT
+ –
BACKUP 2 SEE NOTE 4
PRIMARY 1 SEE NOTE 4
SEE NOTE 3
SEE NOTE
3
EOL RESISTOR (IF USED)
LISTED SIMPLEX FIRE ALARM CONTROL
PANEL 2120, 4001, 4002 4020, 4100+, 4100U, 4100ES, 4004, 4005 OR 4006
2 1
3 4
BLK
REMOTE LED 4098-9830
(SEE NOTE 1)
RED
RED BLK BLK
VIO N/C BLU C GRY N/O YEL N/C ORN C GRN N/O
(SEE NOTE 2)
(SEE NOTE 5)
Figure 2-4. 4098-9683 2-Wire Relay Base Connections for Style B or D Initiating Circuits
Notes:
1. If used, 4098-9830 remote LED is polarized; refer to Figure 2-6 to wire
remote LED to a heat detector, observe color-coded wiring.
2. Wire only one relay base per initiating circuit.
3. For Style D initiating circuit, wire per dotted lines and do not use EOL
resistor. If Style B initiating circuit, refer to wiring diagrams provided
with the system panel for proper EOL resistor value.
4. It is recommended that the Primary-1 and the Backup-2 lines be in separate
wire runs and in compliance with local requirements.
5. Aux. Relay contacts, each rated 1 amp at 28 VDC/0.5 amp at 125 VAC,
resistive.
Continued on next page
2-12
firealarmresources.com
4098 Bases, Continued
Wiring
FigureTag FD4-709-06
RESETABLE POWER
–
SOURCE
24VDC
REMOTE LED 4098-9830
(SEE NOTE 1)
REMOTE LED 4098-9830
(SEE NOTE 1)
RED
24VDC EOL RELAY 2098-9735
OR 2098-9739
BLK
YEL
YEL
INITIATING + CIRCUIT –
LISTED SIMPLEX FIRE ALARM CONTROL PANEL
2120, 4001, 4002 4020, 4100+, 4100U 4100ES , 4004, 4005 OR 4006
RED
RED
BLK
BLK
ORG GRN
RED
ORG GRN
ORG GRN
N/C
VIO
SEE
N/O
BLU GRY
NOTE 6
RED
ORG GRN
N/C
VIO
N/O
BLU GRY
SEE NOTE
6
ORG GRN
RED ORG
GRN
N/C
VIO
N/O
BLU GRY
BLK
BLK
RELAY
BLK
BLK
RELAY
BLK
BLK
RELAY
EOL RESISTOR (SEE NOTE 3)
SEE NOTE
6
Figure 2-5. 4098-9682 4-Wire Base Connections for Style B Initiating Circuits
Notes:
1. If used, 4098-9830 remote LED is polarized, observe color-coded wiring.
(Refer to Figure 2-6 to wire remote LED to heat detector.)
2. Aux. Alarm contacts – Form C – each rated 3 amps at 28 VDC/115 VAC,
resistive. 3. Refer to wiring diagrams provided with system panel for proper
EOL resistor value.
Continued on next page
2-13
firealarmresources.com
4098 Bases, Continued
Wiring
FigureTag FD4-709-07
- INITIATING CIRCUIT
+ –
LISTED SIMPLEX FIRE ALARM CONTROL
PANEL 2120, 4001, 4002 4020, 4100+, 4100U 4100ES , 4004, 4005 OR 4006
BACKUP 2 SEE NOTE 2
PRIMARY 1 SEE NOTE 2
SEE NOTE 3
4098-9684 HEAT DETECTOR
BASE
2 1
3 4
RED BLK BLK
BROWN WHITE
4098-9684 HEAT DETECTOR
BASE
2 1
3 4
4098-9830 REMOTE LED
(SEE NOTE 1)
RED BLK BLK
BROWN WHITE
SEE NOTE
3
EOL RESISTOR (IF USED)
4098-9830 REMOTE LED
(SEE NOTE 1)
Figure 2-6. 4098-9684 Heat Detector LED Base Connections for Style B or D
Initiating Circuits
Notes:
1. If used, 4098-9830 remote LED is polarized; observe color-coded wiring. 2.
It is recommended that the Primary-1 and the Backup-2 lines be in separate
wire runs and in
compliance with local requirements. 3. For Style D initiating circuit, wire
per dotted lines and do not use EOL resistor. If Style B
initiating circuit, refer to wiring diagrams provided with the system panel
for proper EOL resistor value.
2-14
firealarmresources.com
Chapter 3 TrueAlarm Sensors, Sensor Bases, and
QuickConnect Smoke Sensors
Introduction In this Chapter
This chapter contains general notes, specifications, and mounting information for the TrueAlarm Sensors, Sensor Bases and QuickConnect Smoke Sensors.
WARNING:
Be sure that the location of each smoke sensor and each heat sensor has been planned per local and national fire codes (see NFPA 72).
Smoke sensor sensitivities are set and continuously monitored by the control panel. This functionality complies with NFPA 72. When functional testing of these sensors is required per NFPA 72, use the test methods described in Chapter 5 of this manual “Compatibility and Testing.”
Refer to NFPA 72 for application, test, and maintenance requirements.
The 4098-9733 heat sensor and 4098-9754 multi-sensor provide a Rate-of-Rise function that is software programmed and selectable at 15° F (8.3° C) or 20° F (11.1° C) per minute. The 4098-9733 and 4098-9754 also provide general temperature monitoring within the range of 32°-122° F (0°-50° C).
Refer to the page number listed in this table for information on a specific topic.
Topic 4098 TrueAlarm Sensors 4098 TrueAlarm Sensor Bases 4098 TrueAlarm QuickConnect Smoke Sensors
See Page # 3-2 3-3 3-12
Agency UL UL FM
FM
Table 3-1. 4098-9733 Spacing
Program Selection 135º F (57 C) 155º F (68 C) 135º F/155º F (57 C/68 C)
135º F/155º F (57 C/68 C) with 15 or 20 º F/min (8.3 or 11.1 C/min)Rate of
Rise
Spacing
60 X 60 ft (18.3 X 18.3 m)
40 X 40 ft (12.2 X 12.2 m)
RTI = Quick 20 X 20 ft (6.1 X 6.1 m)
RTI = Ultra Fast 50 X 50 ft (15.2 X 15.2 m)
3-1
firealarmresources.com
4098 TrueAlarm Sensors
Specifications
Sensor PID
Type of Sensor
Average Operating Current UL Temperature Rating* Humidity Range (Non-
Condensing)
Air Velocity Range
Table 3-2. TrueAlarm Sensor Specifications
4098-9714 Photoelectric
80 A
10-95% RH
40989717
Ionizat ion
4098-9733 Heat
80 A
6 A at 68 F (20°C) 13 A at 135 F (57 C)
135 F (57 C)** 155 F (68 C)
1095% RH
10-95% RH
4098-9754 Photo/Heat
90 A 135 F (57 C)** 155 F (68 C)
10-95% RH
4098-9746 Gas
50µA
15-95% RH (15-90% for
long term exposure)
0-2000 FPM
0-200 FPM
0-2000 FPM
0-1000 FPM
- Fixed temperature functions are software programmed and selectable from the UL temperature rating. ** UL Max. Ambient Ceiling Temp. of 100° F (38° C) at 3600 sq. ft of Max. Coverage. UL Max. Ambient Ceiling Temp. of 100° F (38° C) at 1600 sq. ft of Max. Coverage.
Special Applications Mounting
1. Smoke sensor sensitivities are set and continuously monitored by the
control unit. The sensitivity range (setting) for the 4098-9714 and 4098-9754
sensor is 0.2%/FT to 3.7%/FT smoke obscuration. The sensitivity range
(setting) for 4098-9717 sensors is 0.5%/FT to 1.3%/FT.
2. The 0.2%/FT, 0.5%/FT, and 1.0%/FT settings for the 4098-9714 and 4098-9754
sensor and the 0.5%/FT and 0.9%/FT settings for the 4098-9717 sensor are for
special applications only. The 0.2%/FT, 0.5%/FT, 0.9%/FT, and 1.0%/FT settings
are very sensitive settings: only use the 0.2%/FT setting when a sensor is
located in a totally smoke-free and controlled temperature environment, such
as a computer room or telephone switching exchange.
3. To determine if an area is suitable for the 0.2%/FT setting, set the
sensitivity for the installed sensor at 1.5%/FT and monitor the peak values
for 90 days. If you record a peak value of 0.1%FT or higher during the 90
days, do not use the 0.2%/FT setting.
4. To determine if an area is suitable for the 0.5%/FT setting, set the
sensitivity for the installed sensor at 1.5%/FT and monitor the peak values
for 90 days. If you record a peak value of 0.25%FT or higher during the 90
days, do not use the 0.5%/FT setting.
5. To determine if an area is suitable for the 0.9%/FT or 1.0%/FT setting,
set the sensitivity for the installed sensor at 1.3%/FT (Ion) 1.5/FT (Photo)
and monitor the peak values for 90 days. If you record a peak value of 0.5% or
higher during the 90 days, do not use the 0.9%/FT (Ion) or 1.0%/FT (Photo)
settings.
All sensors identified in Table 3-2 mount to a sensor base (refer to the “4098
TrueAlarm Sensor Bases” section of this chapter for more information). Use the
following information and Figure 2-1 when mounting TrueAlarm sensors.
3-2
firealarmresources.com
4098 TrueAlarm Sensor Bases
Introduction
TrueAlarm smoke/heat sensor bases are connected to a 2120 Multiplex Communicating Device Transponder (CDT), 4020, 4100+, 4100U, 4100ES, 4120, 4008, or 4010 panel by a single wire pair (MAPNET II/IDNet). The 4098-9792, -9789, 9793, 9796, 9797, and 9798 bases and their sensors obtain both power and data over MAPNET II/IDNet wiring. The 4098-9791 sensor base requires 24VDC power for relay operation and the 4098-9794 and 4098-9795 sensor base with sounder requires 24 VDC or Notification Appliance Circuit (NAC) power. The 4098-9791, -9794, -9795, and 9796 are NOT compatible with the 2120 CDT. The 4098-9793 is only compatible with the 4010, 4008, 4100U and 4100ES (except with 4100-3103 Quad Panel Isolator).
Specifications
The table below contains specifications for TrueAlarm Sensor Bases. Table 3-3. TrueAlarm Sensor Bases Specifications
Sensor Base PID
Working Voltage (MAPNET II/IDNet)
24V Working Voltage (Relay or Sounder Power)
MAPNET II/IDNet Current *
24V Standby Current (Relay or Sounder)
24V Current (Relay or Sounder Activated)
LED Output
Sounder Output
4098-9789 (w/
Remote LED)
4098-9791 (w/ Relay
and Remote
LED)
4098-9792
4098-9793 (Isolator Base)
4098-9794 (Sounder
Base)
4098-9795 (MultiSensor
Sounder Base)
24-40 VDC
24-40 VDC
24-40 VDC
24-40 VDC 24-40 VDC 24-40 VDC
18 32 VDC
18 32 VDC
18 32 VDC
400 A
400 A
400 A
500 A
400 A
500 A
270 A
270 A
270 A
28 mA
17 mA
20 mA
Yes
Yes
Yes
Yes
88 dBA minimum
88 dBA minimum
- MAPNET II/IDNet current with Photo Sensor plugged into Base
4098-9796 (Multi-
Sensor w/ Remote
LED) 24-40 VDC
500 A
Yes
4098-9797 (CO Sensor
Base)
24-40 VDC
450 A
4098-9798 (CO Sounder
Base)
24-40 VDC
18 32 VDC
500 A
270 A
17 mA Yes
88 dBA minimum
Setting the Base’s Address
Each sensor base has a unique address. This address is associated with a
custom label that identifies its physical location within a building. The
base’s address and location must match up with the address listed in the
specification sheets of the 2120 Job Configuration Report or the Programmer’s
Report for the 4020, 4100+, 4100U, 4100ES, 4120, 4008, or 4010 System. See
Figure 3-1 for DIP Switch location for 4098-9789, -9791, -9792, -9793, and
-9796, Sensor Bases. See Figure 3-2 for DIP Switch location for 4098-9794,
4098-9795, -9797 and -9798.
Continued on next page
3-3
firealarmresources.com
4098 TrueAlarm Sensor Bases, Continued
Setting the Base’s Address
128 64 32 16 8 4 2 1
ON
OFF
DIP Switches
12345678
Figure 3-1. 4098-9789, -9791, -9792, -9793, -9796, Sensor Bases Location of DIP Switches
“ON” Position
DIP Switch Position 9 “ON” for NAC Power Input
DIP Switches
“OFF” Position
DIP Switch Position 9 “OFF” for 24 VDC Power Input
Figure 3-2. 4098-9794, 4098-9795, , 4098-9798 Sensor Bases Location of DIP
Switches
Note: The 4098-9794 Sounder Base, 4098-9795 Multi-Sensor Sounder Base, and
4098-9798 Sounder Base have a 9-position DIP Switch. The first eight DIP
Switches set the sounder base address. DIP Switch Position 9 is set to OFF or
ON depending upon the sounder base power source. When the sounder base is
connected to a 24 VDC power source, DIP Switch Position 9 is set to “OFF” and
the 24 VDC power is supervised by the sounder base. When the sounder base is
powered by the panel’s Notification Appliance Circuit (NAC), DIP Switch
Position 9 is set to “ON” and the power is supervised by the NAC and not the
sounder base. The -9797 Base has the same layout, but doesn’t offer sounder
functionality. It uses only an 8-way DIP switch.
Continued on next page
3-4
firealarmresources.com
4098 TrueAlarm Sensor Bases, Continued
Address Setting for the 2120 CDT System
Address Setting for the 4010, 4020, 4100+, 4100U, 4100ES, 4008, or 4120 System
1. Using the 2120 Job Configuration Report, find the entry for the sensor
base (4098-9792 and 4098-9789 only) you are about to install. The CUSTOM LABEL
column provides the location while the DEVICE ADDRESS column provides the
switch setting data.
2. Using the switch setting data for the base you are installing, set the
base’s address. See Figure 3-1 for location of switches. Use a small
screwdriver or pen to set the switches.
3. Double-check the location of the sensor base and its address before
proceeding to electrical installation (see Figure 2-1).
1. Using the Programmer’s Report for the 4020 (Figure 3-3), 4100+, 4100U,
4100ES, 4120, 4008, or 4010 (Figure 3-4), find the entry for the sensor base
you are about to install. The device ADDRESS and CUSTOM LABEL are located in
the SYSTEM POINT SUMMARY under “M.”For example, Address M1-7 (for the 4100+,
4100U, 4100ES, 4120, 4008, or 4010 system) is circled in Figure 3-4. M1 is the
addressable channel while -7 is the device address on the channel. For a base
with Address M1-7, Address 7 must be set on the base’s DIP Switches (SW1).
2. Using the example given in Step 1 as guideline, set the base’s address
using the information in Figure 3-5. See Figure 3-1 and 3-2 for location of
DIP Switches. Use a small screwdriver or pen to set the switches.
3. Mark an address label with the appropriate address for your base by
shading a label box for each base DIP Switch in the ON position. Then apply
the label to the base near the base’s DIP Switch.
4. Double-check the location of the sensor base and its address before
proceeding to electrical installation.
Device Address
Figure 3-3. 4020 Programmer’s Report
Device Address
Figure 3-4. 4100+, 4100U, 4100ES, 4120, 4008, or 4010 Programmer’s Report
Continued on next page
3-5
firealarmresources.com
4098 TrueAlarm Sensor Bases, Continued
Address Setting for the 4010, 4020, 4100+, 4100U, 4100ES, 4008, or 4120 System
LSB
The figure below shows the address DIP Switch settings for the 4010, 4008, 4020, 4100+, 4100U, 4100ES and 4120 Systems. Refer to the “Compatibility and Testing” chapter of this publication for information on which devices are compatible with the various FACPs.
Note: The 4020, 4100+, 4100U, 4100ES, 4008, and 4120 systems support up to 127 devices on
each of their MAPNET II channels. The 4010 supports up to 250 devices on its IDNet
channel.
FigureTag FD4-709-08
MSB
DIPSWITCH IS SHOWN SET AT ADDRESS 7.
1 2 34 56 78 ON
OFF
1 = ON
0 = OFF
DIP SWITCHES 5 THRU 8
0000 1000 0100 1100 0010 1010 0110 1110 0001 1001 0101 1101 0011 1011 0111 1111
0000 1000 0100 1100 0010 1010 0110 1110 0001 1001 0101 1101 0011 1011 0111 1111 0 16 32 48 64 80 96 112 128 144 160 176 192 208 224 240 1 17 33 49 65 81 97 113 129 145 161 177 193 209 225 241 2 18 34 50 66 82 98 114 130 146 162 178 194 210 226 242 3 19 35 51 67 83 99 115 131 147 163 179 195 211 227 243 4 20 36 52 68 84 100 116 132 148 164 180 196 212 228 244 5 21 37 53 69 85 101 117 133 149 165 181 197 213 229 245 6 22 38 54 70 86 102 118 134 150 166 182 198 214 230 246 7 23 39 55 71 87 103 119 135 151 167 183 199 215 231 247 8 24 40 56 72 88 104 120 136 152 168 184 200 216 232 248 9 25 41 57 73 89 105 121 137 153 169 185 201 217 233 249 10 26 42 58 74 90 106 122 138 154 170 186 202 218 234 250 11 27 43 59 75 91 107 123 139 155 171 187 203 219 235 251 12 28 44 60 76 92 108 124 140 156 172 188 204 220 236 252 13 29 45 61 77 93 109 125 141 157 173 189 205 221 237 253 14 30 46 62 78 94 110 126 142 158 174 190 206 222 238 254 15 31 47 63 79 95 111 127 143 159 175 191 207 223 239 255
Figure 3-5. 4010, 4020, 4100+, 4100U, 4100ES, 4008, or 4120 MAPNET/IDNet Addresses Continued on next page
3-6
firealarmresources.com
4098 TrueAlarm Sensor Bases, Continued
Multi-Sensor Bases 4098-9795 and 4098-9796
The 4098-9795 and 4098-9796 Multi-Sensor Bases are only for use with the
4098-9754 multi-sensor and are not compatible with the 2120 CDT. Both bases
have remote LED output and the 4098-9795 also has an integrated sounder
similar to the 4098-9794 Sounder Base. The 4098-9795 and 4098-9796 Multi-
Sensor Bases must be used with the 4098-9754 multi-sensor when connected to a
4010, 4020, 4100+, 4008, or 4120 system. When connected to a 4100U or a 4100ES
the 4098-9754 multi-sensor can also be used with the 4098-9789, -9791, -9792,
-9793, 9794, -9797, and -9798 bases.
The Multi-Sensor Base answers to two addresses, therefore the DIP Switch must
be set for even addresses only. The even address is a photo sensor/sounder
base (4098-9795) or a photo sensor/standard base (4098-9796), and the odd
address (DIP Switch + 1) is a heat sensor/standard base. The figure below
shows the allowable addresses for the Multi-Sensor Bases.
IMPORTANT: Switch Position 1 is not used and must always be OFF (0) for the
Multi-Sensor Bases to function properly. The odd address immediately after the
DIP Switch setting must not be used by any other sensor base or MAPNET/IDNet
device.
Wiring
LSB
MSB
SEE NOTE 1
ON
1 2 34 56 78 9
OFF
DIPSWITCH IS SHOWN SET AT ADDRESS 4.
1 = ON
SEE NOTE
0 = OFF
RESERVED FOR FUTURE USE
DIP SWITCHES 5 THRU 8
DIP SWITCHES 1 THRU 4
0000 1000 0100 1100 0010 1010 0110 1110 0001 1001 0101 1101 0011 1011 0111 1111
0000 0 0100 2
16 32 48 64 80 96 112 128 144 160 176 192 208 224 240 18 34 50 66 82 98 114 130 146 162 178 194 210 226 242
0010 4 0110 6
20 36 52 68 84 100 116 132 148 164 180 196 212 228 244 22 38 54 70 86 102 118 134 150 166 182 198 214 230 246
0001 8 24 40 56 72 88 104 120 136 152 168 184 200 216 232 248 0101 10 26 42 58 74 90 106 122 138 154 170 186 202 218 234 250
0011 12 28 44 60 76 92 108 124 140 156 172 188 204 220 236 252
0111 14 30 46 62 78 94 110 126 142 158 174 190 206 222 238 254
SWITCH 1 MUST BE SET TO OFF FOR PROPER OPERATION
RESERVED FOR FUTURE USE
Figure 3-6. 4098-9795, -9796, 9798 Multi-Sensor Base DIP Switch Address
Settings
Note: The 4098-9795 Multi-Sensor Sounder Base has a 9-position DIP Switch that
is used for setting base address and selecting the sounder power source. See
Figure 3-2 for DIP Switch location.
Sensor bases are connected to the fire alarm control panel via a single wire
pair for the 4098-9789, -9792, -9793, -9796, and -9797 and two pairs of wires
for the 4098-9791, -9794, -9795, and -9798. Using Figure 3-7 as a reference,
connect the bases to the MAPNET II/IDNet wire pair and 24V power (if used).
IMPORTANT: For additions to existing installations, remove power from the
panel
before wiring any bases to avoid damage to equipment.
Continued on next page
3-7
firealarmresources.com
4098 TrueAlarm Sensor Bases, Continued
Wiring
FigureTag FD4-709-09
FROM PANEL
+24V OR NAC +ALM 0V OR NAC -ALM
FROM PANEL
+24V 0V
+24V 0V
TO OTHER 24V DEVICES
TO NEXT 24V OR NAC
CIRCUIT
2098-9808
REMOTE LED
OR 4098-9822
–
RELAY (IF USED)
(SEE NOTE 1)
+ WHITE BLUE
(SEE NOTES 8 & 10)
+S
+COMM
4098-9794, -9795 -9797 , -979 8
-S
4098-9792 SENSOR BASE
-COMM
+COMM
-COMM
SHIELD (SEE NOTE 3)
SHIELD (SEE NOTE 3)
FROM PANEL
+ MAPNET II/IDNet – MAPNET II/IDNet
+COMM -COMM
BLUE WHITE
(SEE
NOTE 6)
–
(SEE NOTE 5)
BLUE WHITE
RED RED BLACK
4098-9822 RELAY
MODULE
(SEE NOTE 6)
4098-9789, -9796 SENSOR BASE
BLACK
CENTER N.C. N.O.
BROWN VIOLET GREY
ORANGE YELLOW GREEN
CENTER N.C. N.O.
SHIELD (SEE NOTE 3)
CONTACT B (SEE NOTE 4)
CONTACT A (SEE NOTE 4)
BLUE WHITE BLACK/WHITE BLACK
(SEE NOTE 9)
CENTER N.C. N.O.
BLACK BLACK
BLUE
2098-9737 RELAY (SEE
NOTE 9)
VIOLET
GREY
ORANGE YELLOW GREEN
CENTER N.C. N.O.
4098-9791 SENSOR BASE
CONTACT B (SEE NOTE 7)
SHIELD (SEE NOTE 3)
CONTACT A (SEE NOTE 7)
4098-9793 SENSOR BASE (SE NOTE 8)
+COMM -COMM
+ MAPNET II/IDNet – MAPNET II/IDNet
TO OTHER MAPNET II/ IDNet DEVICES (SEE NOTE 2)
FROM 4010 PANEL
IDNet IDNet
COMM
COMM
COMM
COMM
TO OTHER IDNET DEVICES
(SEE NOTE 2)
Figure 3-7 Smoke/Heat Sensor Base Connections
SHIELD IS OPTIONAL (SEE NOTE 3)
SHIELD
Notes:
1. Remote LED and relay wires are not supervised.
2. Maximum quantity of devices per circuit is 127 for 4020, 4100+, 4100U/4100ES (MAPNET), or 4120, 128 for the 2120 CDT panel, 200 for the 4008 panel, and 250 for the 4010 and 4100U/4100ES (IDNET) panel. Maximum quantity of 4098-9795 -9796 and -9797 Multi-Sensor bases is 63 with 4020, 4100+, 4100U, 4100ES and 4120, 100 for 4008 panel, and 124 for the 4010 panel. If the sounder output is coded (Temporal code, etc.) via MAPNET II/IDNet control see Note 10.
3. If shield is used, twist shield wires together and cap with wire nut. Shield should be insulated from electrical box.
4. Contact A or B: Dry, Form C – each rated 2 amperes at 24 VDC/0.5 amperes at 110 VAC, resistive.
5. 18 to 32 VDC, .008 amperes typical/.013 amperes max.
6. Do not use remote LED if the 4098-9822 relay module is used.
7. Contact A or B: Dry, Form C Each rated at 3 amperes at 28 VDC/115 VAC, resistive.
8. Remove the protective tape over the CO Sensor on the 4098-9797 and -9798 bases only after the sensor head has been installed.
9. Maximum wire length between 4098-9791 sensor base and 2098-9737 relay module is 100 feet.
10. Maximum quantity of sensors with 4098-9794, -9795, and -9798 sounder bases limited to 43 if output is coded (Temporal code, etc.) via MAPNET II/IDNet control. If coding is performed via 24VDC or NAC circuit, see Note 2.
Continued on next page
3-8
firealarmresources.com
4098 TrueAlarm Sensor Bases, Continued
Wiring
Figure 3-8 shows the wiring connections for the isolator sensor base. All
screw terminals accept 14 to 18-gauge AWG solid or stranded. Maximum torque
should not exceed 12-inch-pounds.
CAUTION: Do not loop wire under terminals. Break wire runs to provide
supervision.
COMM COMM COMM COMM COMM COMM COMM COMM COMM COMM COMM COMM
FROM 4010 PANEL
IDNet IDNet
IDNet IDNet
TO OTHER IDNet DEVICES (SEE NOTE 2)
SHIELD IS OPTIONAL (SEE NOTE 3)
SHIELD
SHIELD
SHIELD
Figure 3-8. 4098-9793 Isolator Sensor Base Connections
Notes: 1. Isolator base compatible with 4010, 4100U, 4100ES or 4008 panel
ONLY. 2. Maximum quantity of devices per circuit is 250 for 4010, 4100U and
4100ES panels. 3. If shield is used, twist shield wires together and cap with
wire nut. Shield should be insulated
from electrical box.
3-9
firealarmresources.com
4098 TrueAlarm Sensor Bases, Continued
CRS Replacement Instructions
This section contains the instructions for the end-of-life replacement of the 4098-9746 CO Replacement Cartridge (CORC), in the CO SSD Bases (Carbon Monoxide Smoke Sensor and Detector Bases). Replacement is necessary due to normal component degradation over time. It is standard maintenance for the CO SSD Bases in order to prolong normal function without requiring base replacement.
Note: During installation, you may be exposed to live circuits – attention required to ensure personal safety and to avoid product damage.
Model number reference:
Model 4098-9746 4098-9797 4098-9798
Name CORC Replacement CO SSD Sensor Base CO SSD Sounder Base
Removing the expired CORC
1. Remove sensor head (not shown) and set aside for later re-installation. 2.
Insert a fine blade screwdriver into the slot, as shown below.
3. Gently free the CORC from the sensor base by pushing straight in. Do not pry. Remove the CORC and dispose.
Figure 3-9. Removing the CORC from the Sensor Base
Continued on next page
3-10
firealarmresources.com
4098 TrueAlarm Sensor Bases, Continued
CRS Replacement Instructions
Installing the replacement CORC (refer to photo below) 1. Remove the
replacement CORC from its packaging. 2. Hook the loop of the CORC on the tab
in the outer rim of the base (center of the CORC below
the CO sensor cylinder) 3. Gently rotate the CORC inward until it snaps onto
the CO SSD Sensor Base. 4. Re-install the detector head. 5. Remove the dust
cover from the CORC (shown to the side below). 6. The CORC replacement is
complete.
Figure 3-10. Installing the replacement CORC
3-11
firealarmresources.com
4098 TrueAlarm QuickConnect Smoke Sensors
Overview Specifications
This section contains general notes, specifications, and mounting information for the TrueAlarm QuickConnect Smoke Sensor shown in Table 3-4.
WARNING:
Ensure that the location of each smoke sensor has been planned per local and national fire codes (see NFPA 72).
1. Smoke sensor sensitivities are set and continuously monitored by the
control panel. This functionality complies with NFPA 72. When functional
testing of these sensors is required per NFPA 72, use the test methods
described in the “Compatibility and Testing” chapter of this publication. The
sensitivity range (settings) of the 4098-9757 is 1.5%/ft to 3.7%/ft smoke
obscuration.
2. Refer to NFPA 72 for application, test, and maintenance requirements.
Table 3-4. TrueAlarm QuickConnect Smoke Sensor Specifications
Sensor PID
Type of Sensor
Operating Current
Humidity Range (Non-Condensing)
Air Velocity Range Working Voltage (MAPNET II and IDNet) 24V Working Voltage
(Sounder Power
Sounder Output 24V Standby Current (Sounder) 24V Current (Sounder Activated)
Remote LED Output
4098-9757 Photoelectric 500 A max. 10-95% RH 0-2000 FPM 24-40 VDC
NO
Continued on next page
3-12
firealarmresources.com
4098 TrueAlarm QuickConnect Smoke Sensors, Continued
Specifications
Setting the Sensor’s Address
The 4098-9757 QuickConnect2 sensor requires the 4098-9788 base.
The 4098-9757 QuickConnect2 sensor is only compatible with the 4010, 4100U and
4100ES (with 4100-3106). The sensors obtain both power and data over IDNet
wiring.
Each QuickConnect sensor has a unique address. This address is associated with
a custom label that identifies its physical location within a building. The
sensor’s address and location must match up with the address listed in the
Programmer’s Report for the 4010, 4100U or the 4100ES.
Use the method described in the “4098 TrueAlarm Sensor Bases” section of this
chapter to complete the sensor setup. Refer to the figure below for the
location of the DIP Switches. Double-check the location of the QuickConnect
sensor and its address before proceeding to electrical installation (see
Figures 3-12 and 3-13).
Address DIP Switches
4098-9757
Figure 3-11. Location of DIP Switches on QuickConnect Sensor Continued on next
page
3-13
firealarmresources.com
4098 TrueAlarm QuickConnect Smoke Sensors, Continued
Wiring
Use the following to wire the QuickConnect smoke sensors.
CAUTION:
Do not loop wire under terminals. Break wire runs to provide supervision.
4098-9788
4098-9788 (SEE NOTE 1)
4098-9788
FROM PANEL
-IDNet +IDNet
SHIELD IS OPTIONAL (SEE NOTE 3)
SHIELD
SHIELD
SHIELD
-IDNet TO OTHER IDNet DEVICES
+IDNet (SEE NOTE 2)
Figure 3-12. QuickConnect Sensor Connections
FigureTag FD4-709-10 Notes:
1. 4098-9757 QuickConnect sensor uses the 4098-9788 base. 2. Maximum quantity
of devices per IDNet circuit is 250 for the 4010, 4100U and 4100ES (with
4190-3106) panel. 3. If shield is used, twist shield wires together and cap
with wire nut. Shield should be insulated
from electrical box.
3-14
firealarmresources.com
Chapter 4 Accessories
Introduction In this Chapter
This chapter covers relay module accessories.
Refer to the page number listed in this table for information on a specific topic.
Topic Relay Module Accessories
See Page # 4-2
4-1
firealarmresources.com
Relay Module Accessories
2098-9737 Relay Module Wiring
The 2098-9737 Relay module is used with 4098-9791 sensor base. Install the relay module using Figure 3-7 and the figure below as a reference.
FROM PANEL
+24VDC
+24VDC
TO OTHER 24VDC DEVICES OR
SUPERVISORY MODULE
SEE NOTE 1
BLACK/WHITE
BLACK BLACK
2098-9737 RELAY
TO 4098-9791 SENSOR BASE
SEE NOTE 3
CONTACT B SEE NOTE 2
CENTER N.C. N.O.
BLUE VIOLET GREY
ORANGE YELLOW GREEN
CENTER N.C. N.O.
CONTACT A SEE NOTE 2
Figure 4-1. 2098-9737 Relay Module Wiring
Notes: 1. 18 to 32 VDC 24 mA typical/35 mA maximum. 2. Contact A or B: dry,
Form C, each rated 3 amps at 28 VDC/115 VAC, resistive. 3. Maximum wire length
between sensor and relay module is 100 feet.
Continued on next page
4-2
firealarmresources.com
Relay Module Accessories, Continued
4098-9822 Relay Module Wiring
The 4098-9822 Relay Module is used with the 4098-9789, -9791, -9794, -9795, and -9796 Sensor Bases. Install the relay module using Figure 3-7 and the figure below as a reference.
IMPORTANT: Do not use a remote LED if using the 4098-9822 relay module.
The 4098-9822 relay module is not supervised and should only be
used for non-critical supplementary functions. There is a limit of
ten control outputs activated on a MAPNET II/IDNet channel. If the
channel capacity is exceeded, the relay module may not function
properly.
FigureTag FD4-709-10
FROM PANEL (IF USED)
+24VDC 0V
+24VDC 0V
TO OTHER 24VDC DEVICESOR
SUPERVISORY MODULE
(SEENOTE2)
CONTACT B (SEENOTE3)
CENTER N.C. N.O.
WHITE BLUE RED RED BLACK BLACK BROWN VIOLET GREY
4098-9822 RELAY
(SEENOTE1) -BLUE +WHITE
From 4098-9789, -9791, -9794,-9795, -9796 Sensor Base
ORANGE YELLOW GREEN
CENTER N.C. N.O.
CONTACT A (SEENOTE3)
Figure 4-2. 4098-9822 Relay Module Wiring
Notes:
1. Do not use remote LED. 2. 18 to 32 VDC, .008 amps typical / .013 amps.
Maximum. 3. Contact A or B: Dry, Form “C” – each rated 2 amps resistive at 24
VDC/0.5 amps at
110 VAC, resistive.
Continued on next page
4-3
firealarmresources.com
Relay Module Accessories, Continued
Relay Module Installation
Install the relay module using the following steps:
1. Mount a 1-1/2 inch (3.81 cm) extension ring (not supplied) to an octagonal
or square electrical box (not supplied). The extension ring is required to
meet the minimum box volume requirement (32.3 cu. inch/529.4 cu. cm) for relay
module installation.
2. Mount relay module inside extension ring directly behind base and sensor.
Do not mount remotely. See Figure 4-1 or 4-2 for relay module connections.
Note: Use the exact configuration of electrical box (square or octagonal) with
extension to mount sensor base when installing the relay module.
Remote LED Module
The 2098-9808 Remote LED Module is available for the 4098-9789 ,-9791, -9794,
-9795, -9796 Sensor Bases.
Use the figure below as a reference when installing the Remote LED Module to a
sensor base.
RED
BLACK
2098-9808
To 4098-9789, -9791, -9794, -9795, -9796 Sensor Base
LED
Figure 4-3. 2098-9808 Remote LED Module Wiring
4-4
firealarmresources.com
Chapter 5 Compatibility and Testing
Introduction In this Chapter
This chapter covers the compatibility of 4098 Sensors, Detectors, and Bases. Maintenance and testing are also covered.
Refer to the page number listed in this table for information on a specific topic.
Topic Compatibility Maintenance and Testing Cleaning Trouble Indications Fire Alarm Trouble and Maintenance Log
See Page # 5-2 5-4 5-8 5-9 5-11
5-1
firealarmresources.com
Compatibility
Compatibility for 4098 Detectors and Detector Bases
This section describes the compatibility between FACPs, detectors, and detector bases. Table 5-1. 4098 Detector and Detector Base Compatibility
Detectors
4098-9601 4098-9602 4098-9603 4098-9605 4098-9612 4098-9613 4098-9614
4098-9615
Compatible 2Wire Detector
Base 4098-9788 4098-9684 (LED base for Heat Detectors
Only)
4098-9683
System
2120 ET/FADM 2120 FABT/VPBT 2120/4100+ ZAM
4001 4002 4020 4100ES/4100U/4100+/4120/UT 4004/4005 4006 4004/4005 High
Current (Relay base not used with 4004 and 4005 Low Current systems)
Max. Quantity of Bases per
Initiating Circuit
25 18 20 18 30 30 30 20 30 30
1 (See Note 1)
Notes:
Relay operation cannot be guaranteed unless it is the only device on that zone.
Panel compatibility identification marker is model number of the module or panel.
Detector compatibility identification marker is model number found on detector label.
For detailed interconnection data, see wiring diagrams for specific panels.
For additional compatibility listings see 579-832 for 2-wire detector compatibility charts.
Continued on next page
5-2
firealarmresources.com
Compatibility, Continued
Compatibility for 4098 Detectors and Detector Bases
This section describes the compatibility between FACPs, sensors, and sensor bases. Table 5-2. 4098 Sensor and Sensor Base Compatibility
Notes:
1. For detailed interconnection data, see wiring diagrams for specific
panels.
2. Panel compatibility identification marker is model number of the module or
panel.
3. Sensor compatibility identification marker is model number found on sensor
label.
4. 4098-9754 sensor NOT compatible with bases that have a RED DOT located in
sensor mounting area.
5. Maximum quantity of 4098-9794
Sounder Bases, 4098-9795 Multi-Sensor Sounder Bases, and CO Sounder bases
(4098-9798) when output is coded via MAPNET II/IDNet control (Temporal Code)
is 43. If coding is performed via 24 VDC or NAC circuit, use limits specified
in Table 5-2.
Sensors 4098-9714 4098-9717 4098-9733 4098-9714 4098-9717 4098-9733
4098-9714 4098-9717 4098-9733
4098-9714 4098-9733
4098-9714 4098-9717 4098-9733
4098-9754
4098-9754
4098-9757 4098-9746
Compatible Bases
4098-9789 4098-9791 4098-9792
4098-9789 4098-9792
4098-9789 4098-9791 4098-9792 4098-9793 4098-9797 (4100U/4100ES
only) 4098-9789 4098-9791 4098-9792 4098-9793
4098-9794 (See Note 5) 4098-9798 (See Note 5) (4100U/4100ES, IDNet only)
4098-9795 (See Note 5) 4098-9796
4098-9792 4098-9789 4098-9791 4098-9794 (See Note 5) 4098-9797 4098-9798 (See
Note 5)
4098-9788
4098-9797 4098-9798 (See Note 5)
Max. Quantity of Devices Per Circuit
MAPNET II: 127 (4020), 127 (4100+) 127 (4120), 127 (4100U), 127 (4100ES)
Addresses 1-127
128 (CDT TrueAlarm) Addresses 0-127
IDNET:
250 (4010), 250 (4100U), 250 (4100ES) Addresses 1-250
IDNET: 200 (4008) Addresses 1-200
MAPNET II: 127 (4020), 127 (4100+) 127 (4100U), 127 (4100ES), 127 (4120)
Addresses 1-127
IDNET: 250 (4010), 250(4100U), 250 (4100ES)
Addresses 1-250 MAPNET II:
63 (4020, 4100+, 4100U, 4100ES, 4120) Addresses 2 to 126
IDNET: 124 (4010), 124 (4100U), 124 (4100ES)
Addresses 2 to 248
IDNET: 250 (4100U), 250 (4100ES)
Addresses 1-250
IDNET: 250 (4100U/4100ES with 4100-3106)
250 (4010) Addresses 1-250
IDNET: 250 (4100U), 250 (4100ES)
Addresses 1-250
5-3
firealarmresources.com
Maintenance and Testing
Maintenance
The minimal requirement for detector and sensor maintenance should consist of
clearing surface dust by using a vacuum cleaner. Cleaning programs should
comply with NFPA and local environments. Cleaning of the internal chamber
should only be done by a qualified technical representative.
For service, return to your local branch office.
Testing
Smoke sensor sensitivities are set and continuously monitored by the control
unit. Dirty or out-or-range sensors are annunciated by the control unit. This
functionality complies with NFPA 72.
Note: When testing detectors/sensors, refer to NFPA 72, or contact your local
branch office.
CAUTION: Before functionally testing the detectors/sensors, be sure to
disconnect the city connection, releasing devices, and extinguishing systems
(or for the 4020, 4010, 4100+, 4100U, 4100ES, 4006, 4008, or 4120 panel, put
the panel in the Walk Test mode).
Preferred Method of Testing Smoke Detectors/Sensors
NFPA minimally requires annual functional testing of smoke detectors/sensors
at their installed location. To perform this annual test, use the Solo 336
Aerosol Smoke Dispenser.
IMPORTANT: After testing detectors, reset the fire alarm panel to restore the
fire alarm system to normal status. After testing sensors, you must clear the
peak values.
Test Equipment Available
The following test equipment is available:
553-760:
553-761: 553-635: 553-805: 553-810:
553-832:
Test and Removal Tool attached to Mr. Longarm 4 ft. pole (Item #7508) or 6 ft. pole (Item #7512). Heat Detector/Sensor Removal Adapter (use with 553-760). Aerosol spray, Simplex Dry Smoke. Removal Adapter Head Attachment (attaches to the 553-760 tool). Magnet Tester attached to Mr. Longarm 4 ft. pole (Item #7508) or 6 ft. pole (Item #7512). Ion Detector Test Cable.
Also available are the:
Gemini Sensitivity Tester (Model 501 or 502).
Solo 336 Aerosol Smoke Dispenser attached to either the Solo 100 (15 ft.)
telescopic fiberglass pole or the Solo 101 (4 ft.) fiberglass pole.
Solo A4 Aerosol Spray.
Solo Red Cup (709-024). Use to hold the 553-635 Aerosol Spray Can.
Solo (708-021) Adapter for Solo Poles. Use to adapt 553-760 Test and Removal
Tool to the Solo Pole.
TrueTest 801 Smoke Detector Sensitivity Test Equipment.
Smoke 400 Smoke aerosol for TrueTest.
Note: The TrueTest 801 is the only tester to be used with the 4098-9797 and 4098-9798 bases.
5-4
firealarmresources.com
Continued on next page
Maintenance and Testing, Continued
Alternate Method for Testing Sensors
The following test method is suitable for functional checks of sensor bases or
QuickConnect sensors during installation; however, testing with smoke must be
performed to comply with NFPA requirements.
For all sensor bases, position the 553-810 Magnet Tester ½” to ¾”
counterclockwise from the visible LED found on the sensor base, (see the
figure below).
For the 4098-9757 QuickConnect2 photo sensor, position the 553-810 Magnet
Tester as shown in Figure 5-2.
Testing a sensor with a magnet reports a value of 255 for actual / peak
(exception 4010 panel, 4100U panel and 4100ES panel). Clear the peak value
after testing.
Note: For 4098-9795 and 4098-9796 Multi-Sensor Bases both photo and heat
address (even and odd) must alarm.
Magnetic Test for Photoelectric Detectors
Figure 5-1. Magnet Test Location for 4098-9789, -9791, -9792, -9793, and -9796
Sensor Bases using 553-810 Magnet Tester
The 4098 photoelectric detectors may be tested by placing a magnet above the
location indicated by a “” mark embossed on the cover (see Figure 5-2) for
four (4) seconds. Use the Magnetic Tester (Part No. 553-810), Table 5-3, and
the following information to test detectors.
Table 5-3 describes the LED reaction during Normal and MAG TEST modes to the
Normal, More Sensitive, Less Sensitive, and Non-Functional states of the
detector.
Continued on next page
5-5
firealarmresources.com
Maintenance and Testing, Continued
Magnetic Test for Photoelectric Detectors
Figure 5-2. Magnet Test Location for 4098-9601, -9602, -9603, -9605 Smoke
Detectors using 553-810 Magnet Tester
Table 5-3. MAG TEST/Normal Modes – States and Reactions
STATE
Normal More Sensitive Less Sensitive Non-Functional
Normal Mode
(LED flashes every 4 secs.)
X X X
LED Flashes Quickly 6 Times
X
MAG TEST Mode
LED Flashes Slowly 4 Times
X X
Latches in Alarm Mode/LED stays “ON”
X X X
When placing the magnet at the location indicated by a “” mark embossed on the cover, the visible LED flashes indicating the detector’s condition. The following are descriptions of what you should see when using the MAG TEST.
NORMAL – When in MAG TEST, the detector latches into alarm if the detector is within calibration range and the visible LED stays ON.
MORE SENSITIVE – When in MAG TEST, if the detector is more sensitive than the maximum calibration, the visible LED quickly flashes, twice a second. Following the sixth flash, the detector latches into alarm and the visible LED stays ON.
LESS SENSITIVE – When in MAG TEST, if the detector is less sensitive than the
minimum calibration, the visible LED slowly flashes four times, once every two
seconds. Following the fourth flash, the detector latches into alarm and the
visible LED stays ON.
NON-FUNCTIONAL DETECTOR – If the detector is less sensitive than the minimum
allowable sensitivity or if there is a fault in the temperature sensing
circuit (4098-9602), the visible LED does not flash normally. When in MAG
TEST, the visible LED slowly flashes four times, once every two seconds. After
the fourth flash, the detector does NOT latch into alarm and the LED stops
flashing and turns OFF.
If the detector is out of the normal operating range, it should be cleaned. If
the detector still indicates as other than normal sensitivity, replace the
detector.
Continued on next page
5-6
firealarmresources.com
Maintenance and Testing, Continued
Magnetic Test for Ionization Detectors
The 4098 Ionization Detectors may be tested with a magnet to verify proper
operation of the Fire Alarm Control Panel.
Note: When ionization detectors alarm, the red LED indicator activates and
latches into the ON position.
Place a magnet against the detector’s side (over the location marked by a “”
on the head of the ionization detector) and hold for ten seconds to activate
an internal reed switch. Use the Magnet Tester (Part No. 553-810).
Ion Detector Sensitivity Test
Plug the 553-832 Ion Detector Test Cable into the Detector’s sensitivity
voltage pins located on the Ion Detector Head. Perform the following steps to
test the Ion detector’s sensitivity:
1. Connect a 10M/V digital voltmeter to the 553-832 test cable, connect the
negative terminal of the voltmeter to the red wire of the test cable and
connect the positive terminal of the voltmeter to the white wire of the test
cable. The black wire of the 553-832 test cable is not used.
2. The voltage measured by the voltmeter should be within 0.2 and 0.8 volts.
Detectors outputting a voltage outside this range should be cleaned or
replaced.
3. If the Ion Detector voltage output is outside of the range, it should be
removed and cleaned as described in the cleaning section. Re-check the voltage
measurement on the Ion Detector; if the Ion Detector is still outside the
voltage range after cleaning, replace the device.
5-7
firealarmresources.com
Cleaning
Introduction
If the device’s sensitivity is other than what is marked on the device’s
label, clean the device using a source of oil-free, filtered, compressed air
such as Dust-Off, Tech Duster, etc.
CAUTION: Notify appropriate building personnel prior to removing any
detectors/sensors from service.
Photoelectric Smoke Detector/Sensor Cleaning
Blow the compressed air through the open vents around the device so that air
enters and cleans the black chamber cover/insect screen assembly (Part No.
677-224) located beneath the white protective cover.
If the device’s sensitivity is still other than what is marked on the device’s
label, replace the device.
Special Considerations for Ion Detectors and Sensors
Note: Do not remove the Ion Detector/ Sensor protective cover.
Blow compressed air through the open vents around the device so that air
enters and cleans the black chamber cover assembly located beneath the white
protective cover. If the device sensitivity is still outside the marked range
replace the device and return the failed device to 130 Perinton Parkway,
Fairport, NY 14450-9199.
IMPORTANT: Once cleaned, the detector/sensor should be tested with smoke per
NFPA 72.
5-8
firealarmresources.com
Trouble Indications
Trouble Indications for TrueAlarm Sensors
The TrueAlarm smoke sensor is a measuring device that sends data regarding
smoke density to the 4010, 4020, 4100, 4100+, 4100U, 4100ES, 4008, and 2120
fire alarm control panels (FACPs). The TrueAlarm heat sensor operates in a
similar fashion, but sends temperature data instead of smoke density data. The
FACP uses this data to determine whether a trouble has occurred.
The TrueAlarm sensor has two automatic trouble indications:
Dirty Excessively Dirty
A “Smoke Sensor Dirty” trouble condition is reported any time the average
value on an individual sensor reaches a set threshold value. At this time, the
FACP is still compensating for environmental factors and is holding the set
sensitivity level.
A “Smoke Sensor is Excessively Dirty” trouble condition is reported anytime
the average value of an individual sensor reaches a slightly higher set
threshold level. At this point, the FACP can no longer compensate for
environmental factors, and the sensitivity level may begin to drift. Although
an “excessively dirty” trouble is reported, the sensor continues to operate
and reports an alarm condition when one is detected.
In addition to the two automatic trouble conditions, the FACPs have digital
pseudo points that must be turned ON to allow a TrueAlarm sensor that is close
to being a dirty sensor to report as if it is “almost dirty.” This is useful
when maintenance is being scheduled for dirty sensors, as it provides a means
of seeing if other sensors are approaching a dirty state.
The table below shows your responsibilities when certain trouble indications
occur.
Table 5-4. TrueAlarm Troubles and Descriptions
Trouble Indication
Description
Almost Dirty
Using the front panel keys, it is possible for a technical representative to turn ON a digital pseudo point in the FACP that allows an “almost dirty” sensor to report a trouble. Although the “almost dirty” sensor is holding its sensitivity level, you can schedule maintenance for the sensor before the dirty sensor trouble occurs.
Dirty
A “dirty” indication means that the sensor is holding its sensitivity level, but that you should schedule maintenance for the sensor. Clean the sensor as required and, when necessary, call your local branch office for service.
Excessively Dirty
The “excessively dirty” indication means that the sensor is no longer compensating for dirt and dust. Because nuisance alarms are possible with this condition, sensors must be cleaned or replaced immediately. When necessary, call your local branch office for service.
Self-Test Abnormal
All FACP system sensors are automatically tested once every minute. When a sensor fails to report properly to the FACP, a “Self-Test Abnormal” condition occurs. Since the sensor is not working properly, it must be replaced. Replace it, or call your local branch office for service.
Expired
The FACP panel generates an Expired trouble to notify the user that a replacement sensor is required. To clear the trouble, a new CRS with a valid date must be installed, and a hardware reset of the FACP panel must be performed.
5-9
firealarmresources.com
Continued on next page
Trouble Indications, Continued
Table 5-5. Sensor’s Analog Value
The panel will automatically indicate when a sensor is out of its sensitivity calibration. If
the sensor has an analog value below what is listed in the table, the sensor is within its
sensitivity setting.
Sensor’s Analog Value
Type
Almost Dirty Dirty
Excessively Dirty
Photo
115
120
135
Ion
135
140
155
To view a Sensor’s analog value, refer to your panels operating instructions
5-10
firealarmresources.com
Fire Alarm Trouble and Maintenance Log
Fire Alarm Trouble and Maintenance Log
Date
Time
Event/Description
Initials
5-11
firealarmresources.com
firealarmresources.com
Index
2 2120 CDT System
address setting, 3-5 2-Wire Relay Base Connections, 2-12 4 4010 System
address setting, 3-5 4020 System
address setting, 3-5 4100+ System
address setting, 3-5 4100U/ 4100ES System
address setting, 3-5 4120 System
address setting, 3-5 4-Wire Base Connections, 2-13 A Accessories, 4-1
Authorities Having Jurisdiction, 2-2 B Base compatibility, 5-2 Bases
4098, 2-8 wiring, 2-10 C Cautions and Warnings, iv Cleaning, 5-8 CO Sensor
Bases, 1-8 CRS, replacing, 3-10, 3-11 Common Code Requirements, 2-8
Compatibility, 5-1 Copyrights, iii CRS replacing, 3-10, 3-11 D Detector
compatibility, 5-2 Detectors placement, 1-5 Wall and Ceiling Mounted, 1-4
where not to place, 1-6 where to place, 1-3 E Environmental conditions, 1-6 H
Heat Detectors 4098, 2-5 fixed temperature, 2-5 LED Base Connections, 2-14
models, 2-6 ROR Temperature, 2-5 specifications, 2-6 types, 2-5 HVAC Systems,
1-3 I IDNet Addresses, 3-6 Ionization Detectors testing, 5-7
1 IN-1
Isolator Sensor Bases connections, 3-9
M Magnetic Test, 5-5 Maintenance, 5-4 MAPNET Addresses, 3-6 Mulit-Sensor Bases
DIP Switch settings, 3-7 Multi-Sensor Bases, 3-7 N NFPA 70, 1-3 NFPA 72, 1-2,
1-3, 1-4, 2-2, 2-8, 3-1 NFPA 90A, 1-3 O Operation
principles of, 1-8 P Photoelectric Detectors
testing, 5-5 Programmer reports, 3-5 Q QuickConnect Smoke Sensors, 3-12
DIP Switch settings, 3-13 specifications, 3-12 R Rate-of-rise, 1-8 Relay
module 2098-9737 wiring, 4-2 4098-9822 wiring, 4-3 accessories, 4-1
installation, 4-4 Remote LED module, 4-4 S Sensor base compatibility, 5-3
Sensor Compatibility, 5-3 Sensors Wall and Ceiling Mounted, 1-4 where not to
place, 1-6 where to place, 1-3 Smoke Detector Application, 1-2 Smoke Detectors
4098, 2-2 limitations, 2-2 mounting, 2-4 photoelectric, 1-8 specifications,
2-3 Smoke Sensor Application, 1-2 Smoke Sensors photoelectric, 1-8 Style B or
D Initiating Circuits, 2-11 T Test Equipment, 5-4 Testing, 5-4 detectors and
sensors, 5-4 thermistors, 1-8 Trademarks, iii Trouble and Maintenance Log,
5-10
firealarmresources.com
Trouble Indications, 5-9 TrueAlarm Concepts, 1-8 TrueAlarm QuickConnect Smoke
Sensors,
3-12 TrueAlarm Sensor Bases
4098, 3-3 setting the address, 3-4
specifications, 3-3 wiring, 3-8 TrueAlarm Sensors DIP Switch location, 3-4 special applications, 3-2 TrueAlarm Sensors, mounting, 3-2
IN-2 2
firealarmresources.com
firealarmresources.com
574-709 Rev. T
© 2008-2011 SimplexGrinnell LP. Specifications and other information were
current as of publication and are subject to change without notice.
4
firealarmresources.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>