Simplex 4010-9810 Common Event Reporting DACT Card Instruction Manual
- June 9, 2024
- Simplex
Table of Contents
4010-9810 Common Event Reporting DACT Card
Instruction Manual
4010-9810 Common Event Reporting DACT Card
Cautions and Warnings
DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED. Upon unpacking
your Simplex product, inspect the contents of the carton for shipping damage.
If damage is apparent, immediately file a claim with the carrier and notify
Simplex.
ELECTRICAL HAZARD – Disconnect electrical power when making any internal
adjustments or repairs. Servicing should be performed by qualified Simplex
Representatives.
STATIC HAZARD – Static electricity can damage components. Therefore,
handle as follows:
- Ground yourself before opening or installing components (use the 553-484 Static Control Kit).
- Keep uninstalled components wrapped in anti-static material at all times.
RADIO FREQUENCY ENERGY – This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for a Class A computing device pursuant to Subpart J of Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area may cause interference in which case the user at his own expense will be required to take whatever measures may be required to correct the interference.
Overview
This publication shows how to install the 4010-9810 Common Event Reporting or
4010-9816 Point Reporting Digital Alarm Communication Transmitter (DACT) Cards
into a 4010 Fire Alarm Control Panel (FACP). Only one of these option cards is
allowed per system. You cannot have a 4010 DACT card and a network interface
card in the same 4010 FACP. Refer to the Serial DACT Installation/Programming
Instructions (574-090) for configuration information. Refer to the 842-058
Field Wiring Diagram for additional wiring information.
In this Publication
This publication discusses the following topics:
Topic | See Page # |
---|---|
Overview | 1 |
FCC and IC Requirements | 2 |
4010-9810 DACT Card | 5 |
4010-9816 DACT Card | 6 |
Configuration | 7 |
Wiring | 8 |
Card Installation | 9 |
Compatible Receivers | 12 |
FCC and IC Requirements
FCC Requirements
- The Federal Communications Commission (FCC) has established Rules which permit this device to be directly connected to the telephone network. Standardized jacks are used for these connections. This equipment should not be used on party lines or coin lines.
- If this device is malfunctioning, it may also be causing harm to the telephone network; this device should be disconnected until the source of the problem can be determined and until repair has been made. If this is not done, the telephone company may temporarily disconnect service.
- The telephone company may make changes in its technical operations and procedures; if such changes affect the compatibility or use of this device, the telephone company is required to give adequate notice of the changes.
- If the telephone company requests information on what equipment is connected to their lines, inform them of:
a) The telephone number that this unit is connected to,
b) The Ringer Equivalence Number [0.1B] c) The USOC jack required [RJ31X], and
d) The FCC Registration Number [5QWUSA-32102-AL-E]
Items (b) and (d) are indicated on the label. The ringer equivalence number
(REN) is used to determine how many devices can be connected to your telephone
line. In most areas, the sum of the RENs of all device on any one line should
not exceed five (5.0). If too many devices are attached, they may not ring
properly.
Service Requirements
In the event of equipment malfunction, all repairs should be performed by
our Company or an authorized agent. It is the responsibility of users
requiring ervice to report the need for service to our Company or to one of
our authorized agents. Service can be facilitated through our office at:
Simplex Time Recorder 100 Simplex Drive Westminster, MA 01441 TEL:
978-731-2500
FCC and IC Requirements, Continued
Equipment Attachment Limitations
“NOTICE: The Industry Canada label identifies certified equipment. This
certification means that the equipment meets certain telecommunications
network protective, operational and safety requirements as prescribed in the
appropriate Terminal Equipment Technical Requirements document(s). The
Department does not guarantee the equipment will operate to the user’s
satisfaction.
Before installing this equipment, users should ensure that it is permissible
to be connected to the facilities of the local telecommunications company. The
equipment must also be installed using an acceptable method of connection. The
customer should be aware that compliance with the above conditions may not
prevent degradation of service in some situations.
Repairs to certified equipment should be coordinated by a representative
designated by the supplier. Any repairs or alterations made by the user to
this equipment, or equipment malfunctions, may give the telecommunications
company cause to request the user to disconnect the equipment. Users should
ensure for their own protection that the electrical ground connections of the
power utility, telephone lines and internal metallic water pipe system, if
present, are connected together. This precaution may be particularly important
in rural areas.
CAUTION: Users should not attempt to make such connections themselves,
but should contact the appropriate electric inspection authority, or
electrician, as appropriate.
The Ringer Equivalence Number (REN) assigned to each terminal device provides
an indication of the maximum number of terminals allowed to be connected to a
telephone interface. The termination on an interface may consist of any
combination of devices subject only to the requirement that the sum of the
Ringer Equivalence Numbers of all the devices does not exceed 5.”
Applying the FCC and/or Industry Canada Label
When a DACT card is installed in the 4010 Fire Alarm Control Panel, the
panel must be labeled accordingly. The label lets all persons servicing the
system know that the panel is configured with a DACT card and complies with
FCC Part 68 (519-748) and Industry Canada (519-750) listings. To apply the
label, do the following:
-
Refer to Figure 1 and locate the LCD Display and the touch pad keys below it.
Figure 1. Placement for FCC Part 68 and Industry Canada Labels
-
Notice the placement of the labels above and to the right of the LCD display and the touch pad keys in Figure 1.
-
Place the FCC and Industry Canada labels on the 4010 FACP door in the same position as that shown in Figure 1.
Note: Do not cover vent holes when applying the label.
Overview
The 4010-9810 DACT card (742-155) supports five categories of status
changes. The Central Station is notified of Alarm, Trouble, and Supervisory
status changes. AC Fail trouble is delayed from 6-24 hours before reporting to
the Central Station. The DACT supervises the system CPU via the N2
communications. In the event of a CPU failure, the card sends a “CPU Trouble”
message to the Central Station.
Figure 2 shows the location of connectors and switches. Specific information
that is available about which point in the system experiences a status change
is supported by the 4010-9816 Point Reporting ACT card (742-094). The eport
sent to the Central Station includes the specific CID Point address along
with the point status. The Point Reporting DACT supervises the system CPU via
N2 communication. In the event of a CPU failure, the DACT sends a “CPU
Trouble” message to the Central Station. Figure 3 shows the location of
connectors and switches.
Configuration
Switch Settings
Card Address Setting (SW1)
Option cards in the 4010 system have specific addresses. The card address
setting for both the DACT cards is Card 8. Set SW1-4 to the ON position and
set the remaining DIP switches to the OFF position.
To self-test the DACTs, set SW1-8 to the ON position. To return the DACTs to
normal panel operation, set SW1-8 to the OFF position.
Programmer (SW2)
When interfacing with the DACT programmer, set SW2 to the ON position. Set SW2
to the OFF position for normal panel operation.
Wiring
Telephone Wiring
Have the telephone company install two telephone lines, each terminated with
a UL-Listed RJ-31X jack immediately above or as close as possible to the FACP.
The connection to the RJ-31X MUST be made via the listed modular jack in
installations where the DACT shares the telephone line with premises phones,
or other equipment. Connect a UL-Listed RJ45 connector and cable (733-986)
from the DACT to the RJ31X jack.
Note: The two telephone line harnesses must take separate paths from the
host FACP to the RJ-31X blocks.
Card Installation
Mounting
Install a single DACT card in Expansion Slot 2 shown in Figure 5. When an
option card is already present, install the additional option card in
Expansion Slot 1. Each option card comes with all necessary harnesses and
mounting hardware. Use Steps 1 through 5 to install either card into the 4010
FACP.
-
Disconnect battery and then AC power from the FACP.
-
Set all appropriate DIP switch settings and terminate all wiring to their appropriate connectors.
-
Slide the option card into the appropriate expansion slot (see Figure 5).
-
Using the screw and lock washer provided, secure the mounting bracket to the system chassis (see Figure 6).
-
Slide the card lock bracket into the bottom hole in the option card. Secure the bottom of the option card by tightening the card lock bracket screw (see Figure 7).
N2 Communications/Power Connections
Each DACT card comes with two N2 Communications/Power Harnesses; the
733-953 is a long harness used to interface the option card with the FACP, the
733-956 is a short harness used to “daisy-chain” one option card to another.
Use Steps 1 through 4 to connect the N2 Communications from the option card to
the FACP.
-
Remove battery and then AC power from the FACP.
-
Verify that all switches are set correctly.
-
Using the 733-953 harness, connect one end from P1 of the option card to P1 of the 4010 FACP. P1 on the FACP is located between TB2 and TB3 (see Figure 5).
IMPORTANT: Pay careful attention to the routing for Power- Limited and Non Power-Limited wiring. You must maintain a 1/4-inch separation between these two types of wiring. Neatly dress all harnesses and wiring. (See Figure 8 below.) -
If another option card is installed that is already connected to the FACP, use the 733-956 harness to connect P2 of one option card to P2 of the other. You can now apply AC and then battery power.
Compatible Receivers
4010-9810 DACT
Table 1 lists compatible receivers for the 4010-9810 DACT.
Table 1. 4010-9810 Compatible Receivers
| | RECEIVER
---|---|---
Comm.Format| Osborne/Hoffman OuickalertModelII| ADEMCO 685
(Notes 2, 6)| Silent Knight
9000| Silent Knight
9800| FBI CP220FB
(Notes 5, 6)| RADIONICS
6500| SUR-GARD
MLR2-DG (Note 6)
1| 3/1 Standard 1800/2300 Hz (Note 1)| YES| YES| YES
(Note 3)| YES| YES| YES| YES
2| 3/1 Standard 1900/1400 Hz (Note 1)| YES| YES| YES
(Note 3)| YES| YES| YES| YES
3| 4/2 Standard 1800/2300 Hz (Note 1)| YES| YES| YES
(Note 3)| YES| YES| YES| YES
4| 4/2 Standard 1900/1400 Hz (Note 1)| YES| YES| YES
(Note 3)| YES| YES| YES| YES
5| SIA| YES| NO| YES
(Note 4)| YES| NO| NO| YES
6| RADIONICS BFSK 1800/2300 Hz| YES| YES| YES
(Note 3)| YES| YES| YES| YES
7| RADIONICS BFSK 1900/1400 Hz| YES| YES| YES
(Note 3)| YES| YES| YES| YES
Notes:
- 10 and 20 PPS (Pulses Per Second)
- With 685-8 Line Card
- With 9032 Line Card
- With 9004 Line Card
- With Rec-11 Line Card
- These receivers are also Factory Mutual approved
4010-9816 DACT
Table 2 lists compatible receivers for the 4010-9816 DACT.
Table 2. 4010-9816 DACT Compatible Receivers
| | RECEIVER
---|---|---
Comm. Format| Osborne/Hoffman Quickalert Model II| ADEMCO685
(Notes 2, 6)| Silent Knight
9000| Silent Knight
9800| FBICP220FB
(Notes 5, 6)| RADIONICS
6500| SUR-GARD
MLR2-DG
1| 3/1 (Note 1) Standard 1800/2300 Hz| YES| YES| YES (Note 3)| YES| YES| YES|
YES
2| 3/1 Standard 1900/1400 Hz (Note 1)| YES| YES| YES (Note 3)| YES| YES| YES|
YES
3| 4/2 Standard 1800/2300 Hz (Note 1) 4/2 Standard 1900/1400 Hz (Note 1)| YES
YES| YES
YES| YES (Note 3) YES (Note 3)| YES
YES| YES
YES| YES
YES| YES
YES
4
5| ADEMCO CONTACT ID| YES| YES| NO| YES| YES| NO| YES
6| SIA| YES| NO| YES (Note 4)| YES| NO| NO| YES
7| RADIONICS BFSK 1800/2300 Hz| YES| YES| YES (Note 3)| YES| YES| YES| YES
8| RADIONICS BFSK 1900/1400 Hz| YES| YES| YES(Note 3)| YES| YES| YES| YES
Notes:
- 10 and 20 PPS (Pulses Per Second)
- With 685-8 Line Card
- With 9032 Line Card
- With 9004 Line Card
- With Rec-11 Line Card
- These receivers are also Factory Mutual approved