Radiar AF10
2 channel AC powered 0-10V fixture controller with inbuilt relay
FCC ID: 2AG4N-WCA2CSFN
INSTALLATION AND QUICK START SHEET
AF10 2 Channel AC Powered 0-10V Fixture Controller
WARNING AND GUIDELINES!!!
Read and follow all safety instructions!!
DO NOT INSTALL DAMAGED PRODUCT!
This product has been properly packed so that no parts should have been
damaged during transit. Inspect to confirm. Any part damaged or broken during
or after assembly should be replaced.
WARNING : TURN THE POWER OFF AT THE CIRCUIT BREAKER BEFORE WIRING
WARNING: Risk of Product Damage
- Electrostatic Discharge (ESD): ESD can damage product(s). Personal grounding equipment should be worn during all installation or servicing of the unit
- Do not stretch or use cable sets that are too short or are of insufficient length
- Do not modify the product
- Do not mount near gas or electric heater
- Do not change or alter internal wiring or installation circuitry
- Do not use product for anything other than its intended use
WARNING – Risk of Electric Shock
- Verify that supply voltage is correct by comparing it with the product information
- Make all electrical and grounded connections in accordance with the National Electrical Code (NEC) and any applicable local code requirements
- All wiring connections should be capped with UL approved recognized wire connectors
- All unused wiring must be capped
Product Overview
Radiar AF10, the dual-channel dimming/ tunable AC fixture controller is a part
of the Lumos Controls ecosystem.
The device is easy to mount in an electrical junction box or compatible
fixtures. The device has dual channel 0-10V independent output to control
intensity and correlated color temperature(CCT) and it has a 0-3 VDC input
channel and 12VDC aux output to integrate with third-party sensors.
INSTALLATION INSTRUCTIONS
Mounting Steps- Standard
Install the electrical box as per the local, state & national electrical codes and requirements
- Turn the power OFF at circuit breaker and ensure the power is OFF before wiring
- Use electrical screw driver to remove three ½ inch Knock Out (KO) from the junction box
- Remove the locknut from the Radiar AF10 chase nipple
- Take in the wires and chase nipple of the Radiar AF10 through knock out(KO) hole
- Install the washer and locknut on to the chase nipple. Use a plier to additionally tighten and fix the device firmly with the junction box. (Note: Ensure the antenna faces towards the floor for better communication)
- Take the AC line and neutral mains wires through another KO hole of junction box connect the line(black) and neutral wires(white) of the fixture controller with the line and neutral wires from mains
- Take the line, neutral, dimming wires from the driver in to the J-box through another knockout hole
- To power the driver, connect the Load (Red color) of Radiar AF10 with Input Line of driver and common neutral (White color) with input neutral of driver
- Connect the dimming wires of the driver to the dimming wires of the controller Close the electrical box with cover plate Restore power to the circuit breaker
Do’s | Don’ts |
---|---|
Installation should be performed by a qualified electrician | Don’t use outdoors |
Installation shall be in accordance with all applicable local and NEC codes |
Avoid input voltage exceeding
maximum rating
Turn the power OFF at circuit breakers before wiring| Don’t disassemble the
products
Observe the correct polarity of output terminal|
Specifications | Value | Remarks |
---|---|---|
Input voltage | 120-277VAC | Rated input voltage |
Input current | 3.10A | @Max RF transmtting |
Load voltage | 120-277VAC | |
Load current | 3A | |
Aux voltage | 12VDC | |
Dimming output | 0-10VDC | 2channels , Tolerance + 2%, |
Dimming current | 10mA | Source current per channel |
Dimming range | 0-100% | 1000 steps resolution |
Sensor input | 0-3VDC | Current: 1mA |
Operating temperature | -30 to 55°C (-22 to 122°F) | |
Dimensions | 3.22 x 1.71 x 1.25 (inch) | |
81.79 x 43.43 x 31.75 (mm) | L x W x H | |
Case Temperature | 80°C (176°F) |
Required tools & supplies
Mounting Steps- Plenum Spaces
Install the electrical box as per the local, state & national electrical codes and requirements
- Turn power OFF at circuit breaker and ensure the power is OFF before wiring Use electrical screw driver to remove Knock Outs from the airtight junction box (In jurisdiction where airtight box is needed, use corresponding variants of airtight junction box)
- Remove the locknut from the Radiar AF10 chase nipple
- Place Radiar AF10 inside the junction box and feed the wires and chase nipple of the device through knock out(KO) hole
- Install the washer and locknut on to the chase nipple and hand tighten to the wall of junction box
- Open the connector and take out the wire antenna and insert in to the connector
- Take the AC line and neutral main wires through another KO hole of junction box and connect the line(black) and neutral wires(white) of the fixture controller with the line and neutral wires from mains
- Take the line, neutral, dimming wires from the driver in to the junction-box through another KO hole
- To power the driver, connect the Load (Red color) of Radiar AF10 with Input line of driver and common neutral (White color) with input neutral of driver
- Connect the dimming wires of the driver to the dimming wires of the controller
- Close the electrical box with cover plate
- Restore power to the circuit breaker
Wiring diagram **
**
Install the electrical box as per the local, state & national electrical codes and requirements
- Configuring Radiar AF10 for dimming, tuning and an external sensor control
| Line (Black)| | DIM – (Pink)
---|---|---|---
Neutral (White)| 0-10V DIM2+ (Orange)
Load (Red)| 0-10V DIM1+ (Purple)
12V DC (Yellow)| 0-3V Sensor input (Brown) - Configuring Radiar AF10 for dimming, tuning and an external sensor control (with additional surge protection)
Application
Troubleshooting
When returning from a Power Outage, lights go back to ON state.| This is
normal operation. Our device has a fail-safe feature forcing the device to go
to 50% or 100% and 0-10V at the full output on the loss of power.
Alternatively, the device will return to its previous state after the power is
restored, as configured using the Lumos Controls mobile app needs to be updated
to Alternatively, the device will return to the previous state or a custom
state as configured using the Lumos Controls mobile app after the power is
restored
---|---
There is a delay for the device to turn on/off/dim| Check whether you have set
up a transition time
Lights flickering| • Check whether connection is as per wiring diagram
• Check for loose connections
Lights did not turn ON| • Check whether circuit breaker has tripped
• Check whether fuse has blown
• Check for loose connections
Warranty
5-year limited warranty
Please find warranty terms and conditions
Note: Specifications may change without notice
Actual performance can vary due to end-user environment and application
Commissioning
Once powered up, the device will be ready to be commissioned via the Lumos
Controls mobile app, available for free download on iOS and Android. To begin
commissioning, click the ‘+’ icon from the top of the ‘Devices’ tab. The app
allows you to preset certain configurations which will be loaded after the
device is added. The pre-configurations made using ‘Commissioning Settings’
will be sent to the devices being commissioned.
Once commissioned, the device will be displayed in the ‘Devices’ tab and you
can perform individual operations like ON/OFF/dimming on it from this tab.
Note: The ‘Output Channel Configuration’ will be ‘Single Channel’ by default. To configure dual channel settings, go to ‘Additional Settings’ and click ‘Output Channel Settings’. Then select ‘Controller based color tuning’ or ‘Driver based color tuning’ based on the connected driver.
Please visit Help center for more details
https://knowledgebase.lumoscontrols.com/knowledge
Lumos Controls Application
Download the Lumos Controls’ application from Play Store or App Store OR Scan the QR codes to download the
Lumos Controls’ application
|
---|---
https://play.google.com/store/apps/details?id=com.wisilica.Home&hl=en_IN&gl=US
|
https://apps.apple.com/us/app/wisilica-lighting/id1098573526
The Bluetooth® word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use of such marks by WiSilica Inc. is under license. Other trademarks and trade names are those of their respective owners.
ISO/IEC 27001:2013
Information security certified
20321 Lake Forest Dr D6,
Lake Forest, CA 92630
www.lumoscontrols.com
+1 949-397-9330
All Rights Reserved WiSilica Inc
Ver 1.1 Jul 2022
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>