Lumos CONTROLS Cyrus AM AC Powered Wireless Microwave Motion and Light Sensor User Guide

June 10, 2024
Lumos CONTROLS

CONTROLS Cyrus AM AC Powered Wireless Microwave Motion and Light Sensor
User GuideLumos CONTROLS Cyrus AM AC Powered Wireless Microwave Motion
and Light Sensor - ce

CONTROLS Cyrus AM AC Powered Wireless Microwave Motion and Light Sensor

WARNING AND GUIDELINES!!!
Read and follow all safety instructions!!
DO NOT INSTALL DAMAGED PRODUCT! This product has been properly packed so that no parts should have been damaged during transit. Inspect to confirm. Any  part damaged or broken during or after assembly should be replaced.
WARNING : TURN THE POWER OFF AT THE CIRCUIT BREAKER BEFORE WIRING

WARNING: Risk of Product Damage
Electrostatic Discharge (ESD): ESD can damage product(s). Personal grounding
equipment should be worn during all installation or servicing of the unit
Do not stretch or use cable sets that are too short or are of insufficient length
Do not modify the product
Do not mount near gas or electric heater
Do not change or alter internal wiring or installation circuitry
Do not use product for anything other than its intended use

WARNING – Risk of Electric Shock
Verify that supply voltage is correct by comparing it with the product information
Make all electrical and grounded connections in accordance with the National
Electrical Code (NEC) and any applicable local code requirements
All wiring connections should be capped with UL approved recognized wire connectors
All unused wiring must be capped

PRODUCT OVERVIEW

Cyrus AM is a BLE5.2 controllable high bay Microwave motion and daylight sensor. This sensor operates on a 90-277VAC input voltage range adopts a 5.8GHz Microwave  sensing technology for accurate motion detection. It can be mounted at a maximum height of 12m(39.4ft) and provides a maximum detection range of 17m(55.8ft) diameter.  The sensor can be mounted to the ceiling or at the surface using ceiling or surface mount accessories. It can be quickly commissioned, configured, and controlled from any  mobile device and can be connected to Lumos Controls cloud for data analytics and configuration managementLumos CONTROLS Cyrus AM AC Powered Wireless Microwave Motion and
Light Sensor - overview

Do’s Dont’s
Installation should be performed by a qualified electrician Don’t use outdoors
Installation shall be in accordance with all applicable local and NEC codes

Avoid input voltage exceeding
maximum rating
Turn the power OFF at circuit breakers before wiring| Don’t disassemble the products
Observe the correct polarity of output terminal|
Specifications| Value| Remarks
---|---|---
Input voltage| 90-277VAC| Rated input voltage
Input current| 9mA@230VAC 1SmA@9OVAC| –
Inrush current| 4A|
Surge rating| 4kV|

Operating temperature| 0-80°C (32 to 176W)| –
Dimensions
(Excludes accessories)| 23 x 2.Sin
(59.8 X 63.1mm)| Diameter x Height
Net weight
(Excludes accessories)| 85g (3.0oz)| In grams
Case temperature| 70°C (158°F)| _
Case material| ABS Plastic| White
Dimensions
(Ceiling mount accessories)
WMAM-CMK| 3.53 x 2.62in (89.7 x 668mm)| Diameter x Height
Dimensions
(Surface mount accessories)
WMAM-SMK| 4.32 x 2.80In (109.8 x 71.2mm)| Diameter x Height

REQUIRED TOOLS & SUPPLIES

Lumos CONTROLS Cyrus AM AC Powered Wireless Microwave Motion and Light
Sensor - TOOLS

INSTALLATION INSTRUCTIONS

Wiring the sensor
Turn off the power before wiring and installing the device
Power the sensor by connecting the AC Line and Neutral wires from the mains supply to the Line (Black color), and Neutral (White color) from the sensor.

CEILING MOUNT
Mounting sensor on false ceiling
Ceiling mount: Sensor can be installed in the false ceiling using the flush mounted accessory, such as the clips, as given in the steps below

  1. Make a hole of 78mm diameter in the false ceiling where the sensor is to be installed and take out the main supply wires
    Lumos CONTROLS Cyrus AM AC Powered Wireless Microwave Motion and Light
Sensor - CEILING

  2. Connect the Line (Black) and Neutral (White) wires from the device with the external mains supply wires using wire connectors and terminate the same inside the junction box.
    Lumos CONTROLS Cyrus AM AC Powered Wireless Microwave Motion and Light
Sensor - MOUNT 1

  3. Press and hold the spring clips (on both sides of the device) and insert the sensor into the mounting hole. Release the spring clips so that the sensor will fit in and remain intact.
    Lumos CONTROLS Cyrus AM AC Powered Wireless Microwave Motion and Light
Sensor - MOUNT 2

Note
To remove the sensor from the ceiling, hold and pull the sensor down

Removing Lens
Rotate the lens clockwise to connect to the case and rotate anti-clockwise to dismantle from the case

SURFACE MOUNT

Mounting sensor on false ceiling

  1. Position the sensor mounting base to fix and take out the mains wire through the hole given at the mounting base.

  2. Mount the base on the selected position using screws
    Head: CSK Slotted

  3. To power the sensor, connect the AC Line and Neutral wires from the mains supply to the sensor Line (Black) and Neutral (White) wires using wire connector.  Terminate the wires within the sensor mount.
    Lumos CONTROLS Cyrus AM AC Powered Wireless Microwave Motion and Light
Sensor - mount 3

  4. Connect the sensor unit case with the Mount base (that is already fixed in step 2) by rotating the case clockwise.

Note
To remove the sensor unit case from the mount base, apply pressure towards ceiling and rotate the sensor case anti-clockwise.Lumos CONTROLS Cyrus AM AC
Powered Wireless Microwave Motion and Light Sensor -
clockwise

WIRING DIAGRAMLumos CONTROLS Cyrus AM AC Powered Wireless Microwave
Motion and Light Sensor - DIAGRAM

APPLICATION

Lumos CONTROLS Cyrus AM AC Powered Wireless Microwave Motion and Light
Sensor - APPLICATION

TROUBLESHOOTING

Lights are not responding to Motion| Check whether the Sensor is powered ON
Check whether the Sensor association configured in the Group is correct
---|---
Lights are not responding to Daylight| Check whether the Sensor is powered ON
Check whether the Sensor association configured in the Group is correct
Check whether the Daylight Sensor Settings (for the Sensor displayed under Devices tab) configured is correct

WARRANTY

5-year limited warranty
Please find warranty terms and conditions
Note: Specifications may change without notice
Actual performance can vary due to end-user environment and application

COMMISSIONING

Once powered up, the device will be ready to be commissioned via the Lumos Controls mobile app, available for free download on iOS and Android. To begin commissioning, click the ‘+’ icon from the top of the ‘Devices’ tab. The app allows you to preset certain configurations which will be loaded after the device is added. The  pre-configurations made using ‘Commissioning Settings’ will be sent to the devices being commissioned.
Once commissioned, the device will be displayed in the ‘Devices’ tab and you can configure Sensitivity from the device settings.

https://knowledgebase.lumoscontrols.com/knowledge

Please visit Help center for more details

LUMOS CONTROLS APPLICATION
Download the ‘Lumos Controls’ application from Play Store or App Store OR Scan the QR codes to download the ‘Lumos Controls’ application

https://play.google.com/store/apps/details?id=com.wisilica.Home&hl=en_IN&gl=US
https://apps.apple.com/us/app/wisilica-lighting/id1098573526

The Bluetooth® word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use of such marks by WiSilica Inc. is under license. Other trademarks and trade names are those of their respective owners.

www.lumoscontrols.com
20321 Lake Forest Dr D6,
Lake Forest, CA 92630
+1 949-397-9330

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals