Dextra R25W Reacta Wave Sensor User Manual
- June 10, 2024
- Dextra
Table of Contents
React-Wave Sensor (R25W)
User Manual
R25W Reacta Wave Sensor
| WARNING – THIS LUMINAIRE MUST BE EARTHED
This luminaire has been tested and is manufactured to comply with BS EN 60598
: specification for general requirements and tests. It should be installed by
a suitably qualified person in accordance with IEE.
CAUTION: there is a potential risk of electric shock from the LED boards
when the product is operational with the cover removed.
NOTE: INSTALLATION AND OPERATION OF THE LUMINAIRE BEYOND ITSSCOPE OF
SUPPLY WILL INVALIDATE THE WARRANTY.
---|---
WARNING
Once a site has been commissioned the customer should export their network,
this can be done via email from the device used to commission and will export
the network settings and access rights in a file to any email address that
they want, this can then be saved to a safe location for future access and
sent to other devices with the app installed so that they can be given access
rights to the network. Please refer to the Micas AUto Light Smart DALI User
Manual when backing up the network.
FAILURE TO EXPORT NETWORK SETTINGS AFTER COMMISSIONING WILL RESULT IN THE
CUSTOMER BEING UNABLE TO ACCESS THE SENSOR
SETTINGS FROM ANY OTHER DEVICE OTHER THAN THAT FROM WHICH IT WAS COMMISSIONED.
If commissioning is undertaken more than 24 hours after first installation,
mains power must first be cycled to ensure the sensors communicate with the
commissioning tablet.
Please note that detection ranges may vary depending on type of luminaire in
which the sensor is installed and other environmental factors.
Technical Data
Operating voltage | 230 V ± 10 %, 50 Hz |
---|---|
Standby power | < 1.0 W |
Interfaces | Wireless (Bluetooth) |
Sensor principle | HF motion detector |
Frequency range | 5.8 GHz +/- 75 MHz |
HF power | < 5 mW (< 14 dBm EIRP) |
Detection range | up to 15 m (frontal, wall mounted) |
up to 10 m (diameter, ceiling mounted)
Detection angle| approx. 120° (depending on diffusor)
Motion detection| 0.3 … 3 m/s (1 … 10 km/h)
Adjustable functions| via App on a smart device
Sensitivity| 0 … 100 % in 10 % steps
Hold time| 5 seconds … 60 minutes
Daylight sensor| 1 Lux … 350 Lux; 00; teach in
DIM level| 0 … 100 %
Program Modes| On / Off, Permanent, Corridor, Soft-DIM: active / inactive
Mounting height| max. 2.70 m (wall mounting), max. 4.00 m (ceiling mounting)
Operating temperature| -20 … +60 °C
IP rating| IP 20 (mounting inside the luminaire)
Size| 84 x 30 x 21 mm
(L x W x H, incl. mounting lugs)
Certificates| CE (additional certificates on request)
Installation Considerations
- Detection ranges above assume bare sensor, please reduce diameter by 2M when installed in luminaire.
- Do not install above the maximum recommended height.
- Close proximity to metal objects could cause the sensor to repeatedly retrigger, avoid installation in such situations or reduce the sensitivity of the sensor until retriggering stops, please note that the detection range of the sensor will be reduced by doing so.
- Microwaves can penetrate certain materials such as plasterboard, wood and glass, causing unwanted sensor triggering for example through partition walls. Position sensors and luminaires to account for this possibility.
- Avoid installation close to obstructions that will interfere with the sensor detection range. The sensor must have line of sight to the area to be controlled.
- The luminaire must be rigidly fixed. Suspended luminaires that are subject to motion may cause unwanted sensor triggering.
- Machinery in motion or strong air currents in the detection area may cause unwanted sensor triggering.
- Sensors should not be installed in close proximity to one another or unwanted triggering may occur.
- Sensors should not be positioned directly next to other switching light sources as on / off cycling may cause unwanted sensor triggering.
- Sensors and luminaires should be positioned to avoid “dead” areas between luminaires without detection to ensure that the moving target is always adequately lit.
DIL-0300-0058
Revision – F
02/02/2023