PASSIVE SEPARATOR SUPPLIED BY A CURRENT LOOPDER PASSIVE USER’S MANUAL
Application
The P17G passive separator in a housing of 6.2 mm width and supplied from a current loop, serves to the electric isolation and filtration of the 0(4)…20 mA standard signal value without an additional supply voltage.
Operational safety
In the security scope, the separator meets the requirements of the EN 61010-1
standard.
Remarks concerning the safety:
-
All operations concerning transport, installation, and commissioning as well as maintenance must be carried out by qualified, skilled personnel and national regulations for the prevention of accidents must be observed.
According to this basic safety information, qualified, skilled personnel are persons who are familiar with the installation, assembly, commissioning, and operation of the product and who have qualifications necessary for their occupation. -
The removal of the separator housing during the guarantee period may cause its cancellation.
Separator set
The set of the P17G separator is composed of:
- P17G separator
- user’s manual
When unpacking the instrument, please check whether the type and execution code on the data plate correspond to the order.
Installation
4.1. Assembly – (see p. 13)
4.2. Principle of operation – (see p. 14)
The input signal of the passive separator, after converting into a signal of
high frequency, is separated by means of a transformer and next, after
rectifying and filtration, is directed to the output system.
The required energy for separation needs is collected from the current loop of
the input signal.
4.3. Electrical connections – (see p. 14)
The connection diagram of the passive separator is presented on the fig. 5.
In case of separator operation in a environment with high interference, one
must apply shielded wires.
Technical data
Basic parameters:
– conversion error | ± 0.2% |
---|---|
– limit frequency (-3 dB) | 70 Hz |
– response time (10…90%), Ro=500 Ω | 5 ms |
– voltage fastness (testing) inp/out | 500 V, 50 Hz, 1 min. |
– preheating time of the separator | not occurs |
– ambient temperature | -20…23…65°CC |
– storage temperature | -40…+85°C |
– relative air humidity | <95% (condensation inadmissible) any |
– operating position | any |
– guaranteed protection class | IP 50 (housing) IP 20 (electrical connections) |
– dimensions | (6.2 ´ 77.5 ´ 100) mm |
– kind of terminals | screw terminals |
– diameter of connecting wires | 0.2…2.5 mm 2 (AWG24-12) |
– length of wire without isolation | 6 mm |
– housing material | polyester PBT, black |
– weight | 80 g |
– fixing | acc. to EN 60715 |
Input:
– range of the input signal| 0…20 mA, (4…20 mA)
– response current| ca. 150 mA
– maximal input current/overload| 40 mA
– maximal voltage current/overload| 30 V
– voltage drop| ≤ 1.7 V at20 mA
Output:
– range of the output signal| 0…20 mA, (4…20 mA)
– load resistance RLoad| 0…100…500 Ω
– ripples| ≤ 10 mV
Additional errors:
– from load resistance changes| ≤ 0.15% / 100 Ω
– from ambient temperature changes| ≤ 0.05% / 10 °C
Electromagnetic compatibility:
– noise immunity, acc. to EN 61000-6-2| 1
– noise emissions, acc. to EN 61000-6-4| 1
Safety requirements acc. to EN 61010-1
– installation category| III
– pollution grade| 2
– phase-to-earth working voltage:| 50 V
Order codes
Code | Description |
---|---|
P17G 000 | Passive separator P1 7G |
input: 0/4…20mA;
output: 0/4…20mA;
supplied from a current loop;
multilanguage service manual (polish, english,german, russian) test
certificate
Fig.1. View of the P17G passive separator
Fig.2. Assembly/disassembly way on the rail
Fig.3. Way of wire fixing
Fig.4. Principle of the P17G separator operation
Note: P17G separators consume the energy necessary for their operation
from the input signal current loop (passive separators!).
The voltage at the separator input is a function of the load and is described
by the equation:
UIn = 1.7() V + Iou x RLoad eg. for IIn=20 mA and RLoad=500 W: UIn = 1.7 V +
20 mA x 500 W =11.7 V. () Voltage drop: ≤ 1.7 V at 20 mA
Fig.5. Electrical connections of the P17G separator
Technical support:
tel.: (+48 68) 45 75 143, 45 75 141, 45 75 144, 45 75 140
e-mail:export@lumel.com.pl
Export department:
tel.: (+48 68) 45 75 130, 45 75 131, 45 75 132
e-mail:export@lumel.com.pl
Calibration & Attestation:
e-mail:laboratorium@lumel.com.pl
P17G-07B_R1
60-006-00-00843
Documents / Resources
|
LUMEL P17G Passive Separator
Supplied
[pdf] User Manual
P17G Passive Separator Supplied, P17G, Passive Separator Supplied, Separator
Supplied, Supplied
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>