LUMEL RE11 Temperature Controller Owner’s Manual
SAFETY PRECAUTIONS
All safety related codifications, symbols and instructions that appear in this
operating manual or on the equipment must be strictly followed to ensure the
safety of the operating personnel as well as the instrument.
If the equipment is not handled in a manner specified by the manufacturer it
might impair the protection provided by the equipment.
Read complete instructions prior to installation and operation of the unit.
WARNING : Risk of electric shock.
WIRING GUIDELINES
WARNING :
- To prevent the risk of electric shock power supply to the equipment must be kept OFF while doing the wiring arrangement. Do not touch the terminals while power is being supplied.
- To eliminate electromagnetic interference use short wire with adequate ratings; twists of the same in equal size shall be made. For the input and output signal lines, be sure to use shielded wires and keep them away from each other.
- Cable used for connection to power source, must have a 2 cross section of 1mm or greater. These wires shall have insulation capacity made of at least 1.5kV.
- When extending the thermocouple lead wires, always use thermocouple compensation wires for wiring. For the RTD type, use a wiring material with a small lead resistance (5Ω max per line) and no resistance differentials among three wires.
- A better anti-noise effect can be expected by using standard power supply cable for the instrument.
MAINTENANCE
- The equipment should be cleaned regularly to avoid blockage of ventilating parts.
- Clean the equipment with a clean soft cloth. Do not use Isopropyl alcohol or any other cleaning agent.
SPECIFICATIONS
|
---|---
Display
| 4 digits (White) + 4 digits (Green) Display Height:-
White Display:- 15.3 mm Green Display:- 8 mm
7 segment digital display
LED Indications
| 1 : Output 1 ON
2 : Output 2 ON T : Tune
S : Dwell Timer
Keys| 3 keys for digital setting
INPUT SPECIFICATIONS
Input Signal| Thermocouple (J,K,T,R,S) / RTD (PT100)
Sampling time| 250 msec
Input Filter (FTC)| 0.2 to 10.0 sec
Resolution| 0.1 / 1° for TC/RTD input
(Fixed 1° for R & S type TC input)
Temperature Unit| oC / °F selectable
Indication Accuracy
| For TC inputs : 0.25% of F. S ±1°C
For R & S inputs : 0.5% of F. S ±2°C
( 30 min of warm up time for TC input )
For RTD inputs : 0.1% of F. S ±1°C
FUNCTIONAL SPECIFICATIONS
Control Method
| 1) PID control with Auto or Self Tuning
2) ON-OFF control
Proportional Band(P)| 1.0 to 400.0°C, 1.0 to 752.0°F
Integral Time(I)| 0 to 9999 sec
Derivative Time(D)| 0 to 9999 sec
Cycle Time| 0.1 to 99.9 sec
Hysteresis Width| 0.1 to 99.9°C
Dwell Timer| 0 to 9999 min
Manual Reset Value| -19.9 to 19.9°C / °F
HEAT COOL PID SPECIFICATIONS
Control Method| PID
Proportional Band-Cool| 1.0 to 400.0°C
1.0 to 752.0°F
Cycle Time-Cool| 0.1 to 99.9 sec
Dead Band| SPLL to SPHL(Programmable)
OUTPUT SPECIFICATIONS
Control Output (Relay or SSR user selectable)| Relay Contact : 5A
resistive@250V AC / 30V DC SSR Drive Output (Voltage Pulse): 12V DC, 30 mA
Auxiliary Output| Relay Contact : 5A resistive@250V AC / 30V DC
POWER SUPPLY SPECIFICATIONS
Supply Voltage| 85 to 270V AC / DC (AC : 50 / 60 Hz )
Power Consumption| 6 VA max@270V AC
Temperature| Operating : 0 to 50°C Storage : -20 to 75°C
Humidity| 95% RH (non-condensing)
Weight| 116 g
INSTALLATION GUIDELINES
- This equipment, being built-in-type, normally becomes a part of main control panel and in such case the terminals do not remain accessible to the end user after installation and Internal wiring.
- Do not allow pieces of metal, wire clippings, or fine metallic fillings from installation to enter the product or else it may lead to a safety hazard that may in turn endanger life or cause electrical shock to the operator.
- Circuit breaker or mains switch must be installed between power source and supply terminals to facilitate power ‘ON’ or ‘OFF’ function. However this switch or breaker must be installed in a convenient position normally accessible to the operator.
- Use and store the temperature controller within the specified ambient temperature and humidity ranges as mentioned in this manual.
CAUTION
- When powering up for the first time, disconnect the output connections.
- Fuse Protection : The unit is normally supplied without a power switch and fuses. Make wiring so that the fuse is placed between the mains power supply switch and the controller. (2 pole breaker fuse – rating : 275V AC,1A for electrical circuitry is highly recommended)
- Since this is a built-in-type equipment (finds place in main control panel), its output terminals get connected to host equipment. Such equipment shall also comply with basic EMI/EMC and other safety requirements like EN61326-1 and EN 61010 respectively.
- Thermal dissipation of equipment is met through ventilation holes provided on chassis of equipment. Such ventilation holes shall not be obstructed else it can lead to a safety hazard.
- The output terminals shall be strictly loaded to the manufacturer specified values / range.
MECHANICAL INSTALLATION
- Prepare the panel cutout with proper dimensions as shown above.
- Fit the unit into the panel with the help of clamp given.
- The equipment in its installed state must not come in close proximity to any heating sources, caustic vapors, oils, steam or other unwanted process by-products.
- Use the specified size of crimp terminals (M3.5 screws) to wire the terminal block. Tighten the screws on the terminal block using the tightening torque within the range of 1.2 N.m.
- Do not connect anything to unused terminals.
EMC GUIDELINES
- Use proper input power cables with shortest connections and twisted type.
- Layout of connecting cables shall be away from any internal EMI source.
LOAD CONNECTIONS
- The service life of the output relays depends on the switching capacity and switching conditions. Consider the actual application conditions and use the product within the rated load and electrical service life.
- Although the relay output is rated at 5 amps it is always necessary to use an interposing relay or contactor that will switch the load. This avoids damage to the controller in the event of a fault short developing on the power output circuit.
- Always use a separate fused supply for the “power load circuit”and do not take this from the live and neutral terminals supplying power to the controller.
ELECTRICAL PRECAUTIONS DURING USE
Electrical noise generated by switching of inductive loads can create momentary disruption, erratic display, latch up, data loss or permanent damage to the instrument.
To reduce noise :
a) Use of snubber circuits across loads as shown above, is recommended.
b) Use separate shielded wires for inputs.
TERMINAL CONNECTIONS
Use only the correct thermocouple wire or compensating cable from the probe to
instrument terminals avoiding joints in the cable if possible.
Failure to use the correct wire type will lead to inaccurate readings.
Ensure that the input sensor connected at the terminals and the input type set
in the temperature controller configuration are the same.
FRONT PANEL DESCRIPTION
1
|
Process-value (PV) / Parameter name display
| 1) Displays a process value (PV).
2) Displays the parameter symbols
at configuration mode/online menu.
3) Displays PV error conditions.
(refer Table 2)
---|---|---
2| Parameter setting display| Displays the parameter settings at configuration
mode/online menu.
3| Control output 1 indication| The LED is glow when the control output 1 is
ON
4| Control output 2 indication| The LED is glow when the control output 2 is
ON
5| Tune| Auto tune : Blinking (With faster rate) Self tune : Blinking (With
slower rate)
6| Dwell timer| Blinking : Dwell timer is in progress. Continuous ON : Time
over.
FRONT KEYS DESCRIPTION
FUNCTIONS | KEY PRESS |
---|
ONLINE
To view Level 1| Press | key for 3 sec.
To view Level 2| Press | key for 3 sec.
To view Protection Level| Press| + keys for 3 sec.
To view online parameters| Lower display selectable between SET1/SET2/TIME
using key.
NOTE : Elapsed time / Remaining time dependent on the selection of ONL
parameter in level1.
To change online parameter values| Press to change parameter value.
PROGRAMMING MODE
To view parameters on the same level.| or key once to view the next or
previous function in operational menu.
To increase or decrease the value of a particular parameter.| + to
increase and + to decrease the function value.
Note : Parameter value will not alter when respective level is locked.
NOTE : The unit will auto exit programming mode after 30 sec. of inactivity.
OR By pressing the or or + keys for 3 sec.
Table 1 : INPUT RANGE
FOR RTD
INPUT TYPE | RANGE |
---|---|
PT100 | Resolution: 1 |
-150 to 850 | -150.0 to 850.0 |
-238 to 1562 | -199.9 to 999.9 |
FOR THERMOCOUPLE
INPUT TYPE| RANGE|
---|---|---
J
| Resolution: 1
-199 to 750
| Resolution: 0.1
-199 to 750
| UNIT|
°C|
-328 to 1382| -199 to 999| °F|
K| -199 to 1350| -199 to 999| °C|
-328 to 2462
-199 to 400
| -199 to 999
-199 to 400
| °F
°C
|
T|
-328 to 750| -199 to 750| °F|
R, S| 0 to 1750| N/A| °C|
32 to 3182| N/A| °F|
Table 2 : ERROR DISPLAY
When an error has occurred, the upper display indicates error codes as given below.
Error | Description | Control Output Status |
---|---|---|
S.bj | Sensor break / |
Over range condition
| OFF
S.jE| Sensor reverse / Under range condition| OFF
Programming online parameters
Setpoint 1/Default : 50
Range : SPLL to SPHL
If upper display is selected as SEEI then, Pressing key will show on Upper
display : SEEI
Lower display : <50>
Press keys to increment / decrement SEEI value.
Setpoint 2 / Dead band/Default : 0
Range : SPLL to SPHL
If upper display is selected as / then, Pressing key will show on Upper
display : SEE2/ db
Lower display: <0>
Press keys to increment / decrement SEE2/db value.
Dwell Timer/Default : OFF
Range : OFF, 1 to 9999 min
If upper display is selected as then, Pressing key will show on Upper display
: EInE
Lower display :
Press keys to increment / decrement time value.
USER GUIDE
-
Display Bias : This function is used to adjust the PV value in cases where it is necessary for PV value to agree with another recorder or indicator, or when the sensor cannot be mounted in correct location.
-
Filter Time Constant : The input filter is used to filter out quick changes that occur to the process variable in a dynamic or quick responding application which causes erratic control.
The digital filter also aids in controlling processes where the electrical noise affects the input signal.
Larger the value of FTC entered, greater the filter added and the slower the controller reacts to the process and vice versa. -
Auto tune (AT) : The Auto-tuning function automatically computes and sets the proportional band (P), integral time (I), Derivative time (D), ARW% and cycle time (CY.T) as per process characteristics
-
Tune LED blinks at faster rate when auto-tuning is in progress.
-
At the completion of Auto-tuning, Tune LED stops blinking.
-
If the power goes OFF before auto-tuning is completed, auto-tuning will be restarted at next power ON.
-
If auto-tuning is not completed after 3-4 cycles, the autotuning is suspected to fail. In this case, check the wiring & parameters such as the control action, input type, etc.
-
Carry out the auto-tuning again, if there is a change in setpoint or process parameters.
-
-
ON/OFF control action (For Reverse Mode) :
The relay is ‘ON’ up to the set temperature and cuts ‘OFF’ above the set temperature. As the temperature of the system drops, the relay is switched ‘ON’ at a temperature slightly lower than the set point
HYSTERESIS :
The difference between the temperature at which relay switches ‘ON’ and at which the relay switches ‘OFF’ is the hysteresis or dead band. -
Manual Reset (for PID control & I = 0) : After some time the process temperature settles at some point and there is a difference between the set temperature & the controlled temperature. This difference can be removed by setting the manual reset value equal & opposite to the offset.
-
Self Tune (ST) : It is used where modification of PID parameters is required repeatedly due to frequent change in process condition eg. Setpoint.
-
Tune LED blinks at slower rate when Self-tuning is in progress.
-
At the completion of self-tuning, Tune LED stop blinking.
-
Self-tuning is initiated under the following conditions :
-
-
When setpoint is altered.
-
When tune mode is altered. (TUNE=ST)
- ST will start only if PV < 50% of setpoint.
- ST will work only when ACT=RE.
CONFIGURATION INSTRUCTIONS
LUMEL S.A.
ul. Słubicka 4, 65-127 Zielona Góra, Poland
tel.: +48 68 45 75 100, fax +48 68 45 75 508
www.lumel.com.pl
Technical support:
tel.: (+48 68) 45 75 143, 45 75 141, 45 75 144, 45 75 140
e-mail: export@lumel.com.pl
Export department:
tel.: (+48 68) 45 75 130, 45 75 131, 45 75 132
e-mail: export@lumel.com.pl
Calibration & Attestation:
e-mail: laboratorium@lumel.com.pl