LUMEL P20Z Transducer Of Rms Current Or Ac Voltage User Manual
- June 9, 2024
- LUMEL
Table of Contents
transducer **of rms current or ac voltage P20Z
user’s manual
**
APPLICATION
The P20Z transducer is destined for a continuous conversion of the RMS current
or ac voltage without a constant component into a constant-current or
constant-voltage standard signal.
The transducer output signal is galvanic isolated from the input signal and
supply. The transducer housing is made of a plastic. On the transducer
outside, there are inseparable screw or socket-plug terminal strips.
TRANSDUCER SET
The set of the P20 transducer is composed of:
- P20Z transducer 1 pc.
When unpacking the transducer, please check whether the type and execution code on the data plate correspond to the order.
BASIC REQUIREMENTS and OPERATIONAL SAFETY
In the safety service scope, the transducer meets the requirements of the EN
61010-1 standard.
Observations concerning the operational safety
- All operations concerning transport, installation, and commissioning as well as maintenance, must be carried out by qualified, skilled personnel, and national regulations for the prevention of accidents must be observed.
- Before switching the transducer on, one must check the correctness of connection to the network.
- Do not connect the transducer to the network through an autotransformer.
- Before removing the transducer housing, one must switch the supply off and disconnect measuring circuits.
- The removal of the meter housing during the guarantee contract period may cause its cancellation.
- The P20Z transducer is destined to be installed and used in industrial electromagnetic environment conditions.
- One must remember that in the building installation a switch or a circuit-breaker should be installed. This switch should be located near the device, easy accessible by the operator, and suitably marked.c
INSTALLATION
4.1 Fitting.
The P20Z transducer is adapted to be mounted on a 35 mm rail acc. to EN 60715.
The overall drawing and the fitting way are presented on the fig.1.
4.2. External connection diagrams
One must carry out external connections with wires of maximal diameters:
– 2,5 mm²for socket-plug executions,
– 1,5 mm² for screw executions.
TECHNICAL DATA
Basic parameters:
input voltage | 60, 100, 150, 250, 400, 500, 600 V~ |
---|---|
input current | 1 A (X/1 A~), 5 A (X/5 A~) |
output signal | 0… 5 mA Rload. ≤2000 Ω |
0… 20 mA Rload. ≤ 500 Ω
4… 20 mA Rload. ≤500 Ω
0…10 V Rload. ≥ 500 Ω
– response time| 0.3 sec
– accuracy class| 0.2
– transducer preheating time| 15 min.
Consumption:
– in supply circuit | ≤ 4 VA |
---|---|
– in voltage circuit | ≤0.6 VA |
– in current circuit | ≤0.2 VA |
Supply voltage | 85…253 V or 20…40 V d.c. or a.c. |
Protection level ensured by the housing | IP 50 |
Protection level ensured from the terminal side | IP 20 |
Weight | 0.125 kg |
Overall dimensions | 22.5x 120 x 100 mm |
Fitting | on a 35 mm rail |
Maximal wire section | 2.5 mm² for executions with screw terminals |
1.5 mm² for executions with self-locking terminals
Reference and rated operating conditions:
-input signal | 0…0.01…1.2 In; 0…0.01…1.2 Un |
---|---|
-frequency of the input signal | 45…65…500 Hz |
-supply | 85…253 V a.c.,90…300 V d.c. |
20…40 V a.c.,20…60V V d.c.
-admissible peak factor:|
-current| 2
-voltage| 2
-ambient temperature| – 20…23…55°C
-storage temperature| – 25… +85°C
-relative humidity| 95% (inadmissible condensation)
-external magnetic field| 0…40…400 A/m
-short duration overload (5 s):|
-voltage input| 2 Un (max.1000 V)
-current input| 10 In
-working position| any
Additional errors:
In multiplicity of the class index:
– from ambient temperature changes | < 0.5 k/10 K |
---|---|
– external magnetic field | < 1 k |
– frequency of the input signal | < 1 k/100 Hz |
Standards fulfilled by the transducer
Electromagnetic compatibility:
- immunity acc. to EN 61000-6-2
- emission acc. to EN 61000-6-4
Safety requirements:
Acc.to the EN 61010-1 standard
- Isolation ensured by the housing: double,
- Isolation between circuit: basic,
- Pollution degree 2,
For voltages in relation to earth, up to 300 V – installation category III,
For voltages in relation to earth, up to 600 V – installation category II,
Altitude above sea level < 2000 m
ExECUTION CODES
Execution codes of the P20Z transducer
* after agreeing with the manufacturer.
Example of order:
When ordering, please respect successive code numbers.
The code: P20Z-09 3 1 1 00 8 means:
P20Z – transducer of RMS current and a.c. voltage
09 – with current input:0… 5 A,
3 – output range: 4… 20 mA,
1 – supply voltage: 85…253 V a.c.,90…300 V d.c
1 – kind of terminals:inseparable screws,
00 – standard execution
8 – without extra quality requirements
MAINTENANCE and GUARANTEE
The P20Z transducer does not require any periodical maintenance.
In case of some incorrect operations:
After the dispatch date and in the period stated in the guarantee card:
One should return the instrument to the Manufacturer’s Quality Inspection
Dept. If the instrument has been used in compliance with the instructions, we
warrant to repair it free of charge.The disassembling of the housing causes
the cancellation of the granted guarantee.
After the guarantee period:
One should turn over the instrument to repair it in a certified service
workshop.
Spare parts are available for the period of five years from the date of
purchase.
Our policy is one of continuous improvement and we reserve the right to make
changes in design and specifications of any products as engineering advances
or necessity requires and revise the above specifications without notice.
LUMEL S.A.
ul. słubicka 4, 65-127 Zielona góra, Poland
tel.: +48 68 45 75 100, fax +48 68 45 75 508
www.lumel.com.pl
Informacja techniczna:
tel.: (68) 45 75 140, 45 75 141, 45 75 142, 45 75 145, 45 75 146
e-mail:sprzedaz@lumel.com.pl
Realizacja zamówień:
tel.: (68) 45 75 150, 45 75 151, 45 75 152, 45 75 153, 45 75 154,
45 75 155
Wzorcowanie:
tel.: (68) 45 75 163
e-mail:laboratorium@lumel.com.pl
Technical support:
tel.: (+48 68) 45 75 143, 45 75 141, 45 75 144, 45 75 140
e-mail:export@lumel.com.pl
Export department:
P20Z-09A
tel.: (+48 68) 45 75 130, 45 75 132
e-mail:export@lumel.com.pl
Calibration & Attestation:
e-mail:laboratorium@lumel.com.pl
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>