LUMEL P20Z Transducer Of Rms Current Or Ac Voltage User Manual

June 9, 2024
LUMEL

LUMEL logo transducer **of rms current or ac voltage P20Z
user’s manual

**

APPLICATION

The P20Z transducer is destined for a continuous conversion of the RMS current or ac voltage without a constant component into a constant-current or constant-voltage standard signal.
The transducer output signal is galvanic isolated from the input signal and supply. The transducer housing is made of a plastic. On the transducer outside, there are inseparable screw or socket-plug terminal strips.

TRANSDUCER SET

The set of the P20 transducer is composed of:

  1. P20Z transducer 1 pc.
    When unpacking the transducer, please check whether the type and execution code on the data plate correspond to the order.

BASIC REQUIREMENTS and OPERATIONAL SAFETY

In the safety service scope, the transducer meets the requirements of the EN 61010-1 standard.
Observations concerning the operational safety

  • All operations concerning transport, installation, and commissioning as well as maintenance, must be carried out by qualified, skilled personnel, and national regulations for the prevention of accidents must be observed.
  • Before switching the transducer on, one must check the correctness of connection to the network.
  • Do not connect the transducer to the network through an autotransformer.
  • Before removing the transducer housing, one must switch the supply off and disconnect measuring circuits.
  • The removal of the meter housing during the guarantee contract period may cause its cancellation.
  • The P20Z transducer is destined to be installed and used in industrial electromagnetic environment conditions.
  • One must remember that in the building installation a switch or a circuit-breaker should be installed. This switch should be located near the device, easy accessible by the operator, and suitably marked.c

INSTALLATION

4.1 Fitting.
The P20Z transducer is adapted to be mounted on a 35 mm rail acc. to EN 60715.
The overall drawing and the fitting way are presented on the fig.1.

LUMEL P20Z Transducer Of Rms Current Or Ac Voltage -
Fitting

4.2. External connection diagrams
One must carry out external connections with wires of maximal diameters:
– 2,5 mm²for socket-plug executions,
– 1,5 mm² for screw executions.
LUMEL P20Z Transducer Of Rms Current Or Ac Voltage -
Fitting2

TECHNICAL DATA

Basic parameters:

 input voltage 60, 100, 150, 250, 400, 500, 600 V~
input current 1 A (X/1 A~), 5 A (X/5 A~)
output signal 0… 5 mA Rload. ≤2000 Ω

0… 20 mA Rload. ≤ 500 Ω
4… 20 mA Rload. ≤500 Ω
0…10 V Rload. ≥ 500 Ω
– response time| 0.3 sec
– accuracy class| 0.2
– transducer preheating time| 15 min.

Consumption:

– in supply circuit ≤ 4 VA
– in voltage circuit ≤0.6 VA
– in current circuit ≤0.2 VA
Supply voltage 85…253 V or 20…40 V d.c. or a.c.
Protection level ensured by the housing IP 50
Protection level ensured from the terminal side IP 20
Weight 0.125 kg
Overall dimensions 22.5x 120 x 100 mm
Fitting on a 35 mm rail
Maximal wire section 2.5 mm² for executions with screw terminals

1.5 mm²  for executions with self-locking terminals

Reference and rated operating conditions:

-input signal 0…0.01…1.2 In; 0…0.01…1.2 Un
 -frequency of the input signal 45…65…500 Hz
-supply 85…253 V a.c.,90…300 V d.c.

20…40 V a.c.,20…60V V d.c.
-admissible peak factor:|
-current| 2
-voltage| 2
-ambient temperature| – 20…23…55°C
-storage temperature| – 25… +85°C
-relative humidity| 95% (inadmissible condensation)
-external magnetic field| 0…40…400 A/m
-short duration overload (5 s):|
-voltage input| 2 Un (max.1000 V)
-current input| 10 In
-working position| any

Additional errors:

In multiplicity of the class index:

– from ambient temperature changes < 0.5 k/10 K
– external magnetic field < 1 k
– frequency of the input signal < 1 k/100 Hz

Standards fulfilled by the transducer
Electromagnetic compatibility:

  • immunity acc. to EN 61000-6-2
  • emission acc. to EN 61000-6-4

Safety requirements:

Acc.to the EN 61010-1 standard

  • Isolation ensured by the housing: double,
  • Isolation between circuit: basic,
  • Pollution degree 2,
    For voltages in relation to earth, up to 300 V – installation category III,
    For voltages in relation to earth, up to 600 V – installation category II,
    Altitude above sea level < 2000 m

ExECUTION CODES

Execution codes of the P20Z transducer

LUMEL P20Z Transducer Of Rms Current Or Ac Voltage -
tabel* after agreeing with the manufacturer.

Example of order:
When ordering, please respect successive code numbers.
The code: P20Z-09 3 1 1 00 8 means:
P20Z – transducer of RMS current and a.c. voltage
09 – with current input:0… 5 A,
3 – output range: 4… 20 mA,
1 – supply voltage: 85…253 V a.c.,90…300 V d.c
1 – kind of terminals:inseparable screws,
00 – standard execution
8 – without extra quality requirements

MAINTENANCE and GUARANTEE

The P20Z transducer does not require any periodical maintenance.
In case of some incorrect operations:
After the dispatch date and in the period stated in the guarantee card:
One should return the instrument to the Manufacturer’s Quality Inspection Dept. If the instrument has been used in compliance with the instructions, we warrant to repair it free of charge.The disassembling of the housing causes the cancellation of the granted guarantee.
After the guarantee period:
One should turn over the instrument to repair it in a certified service workshop.
Spare parts are available for the period of five years from the date of purchase.
Our policy is one of continuous improvement and we reserve the right to make changes in design and specifications of any products as engineering advances or necessity requires and revise the above specifications without notice.

LUMEL logo

LUMEL S.A.
ul. słubicka 4, 65-127 Zielona góra, Poland
tel.: +48 68 45 75 100, fax +48 68 45 75 508
www.lumel.com.pl
Informacja techniczna:
tel.: (68) 45 75 140, 45 75 141, 45 75 142, 45 75 145, 45 75 146
e-mail:sprzedaz@lumel.com.pl
Realizacja zamówień:
tel.: (68) 45 75 150, 45 75 151, 45 75 152, 45 75 153, 45 75 154,
45 75 155
Wzorcowanie:
tel.: (68) 45 75 163
e-mail:laboratorium@lumel.com.pl
Technical support:
tel.: (+48 68) 45 75 143, 45 75 141, 45 75 144, 45 75 140
e-mail:export@lumel.com.pl
Export department:
P20Z-09A
tel.: (+48 68) 45 75 130, 45 75 132
e-mail:export@lumel.com.pl
Calibration & Attestation:
e-mail:laboratorium@lumel.com.pl