LUMEL LCTM Transformer User Manual
- June 9, 2024
- LUMEL
Table of Contents
TRANSFORMER SERIES
LCTM, LCTR, LCTB, LCTS, LCTP
Operating Manual
LCTM Transformer
Low Voltage-Current Transformer –
- LCTM
- LCTR
- LCTB
- LCTS
- LCTP
Functional description
Current transformers of the model range mentioned above are inductive single conductor-current transformers operating according to the transformer principle. Due to the applicated measuring principle, current transformers of this type may only be installed in alternating current (AC) networks.
Safety instructions
** In order to avoid personal and material damage the following assembling
steps must by performed only by authorised, qualified and trained personnel.
If the secondary circuit is operated without a burden/load (open) high
voltages may appear. These voltage values are dangerous for persons as well as
for the functional reliability of the current transformer.
It is forbidden to operate the current transformer without a secondary
circuit (open)!**
Technical parameters
Primary current: | 30A to 6000A |
---|---|
Secondary current: | 1A or 5A |
Accuracy class: | 0.2, 0.2s, 0.5, 0.5s & 1 |
Over current limiting factor: | FS5, FS10, FS15 |
Rated frequency: | 50Hz or 60Hz |
Rated continues thermal current (standard): | 1,2 x In |
Rated short time thermal current Ith: | 60 x In, 1 s (Max 40kA) |
Rated isolation level: | 0,6/3/-kV or 0,6/4/-kV |
Place of installation: | Indoor |
Altitude: | up to 2000 m |
Degree of protection: | IP20 |
Ambient temperature: | -5ºC …+50ºC |
Storage temperature: | -25ºC …+70ºC |
Applied standards: | IEC 60044-1 / IEC 61869-1/2 IEC 61010-2 |
Assembly
-
Ensure a safe work environment during assembly, maintenance and inspection operations. If necessary interrupt the current supply of the primary conductor and take precautions against unintentional switching.
-
(i) For Split core CT : Open the current transformer and fix it on the primary conductor using the fixing clamps (mounting material).
(ii) For Window type CT : Bar or cable primary insert through primary cable or bus bar & fix it using mounting screw assembly.
P1: Direction of power supply
P2: Direction of power source
Attention: (i) Do not close the current transformer, high voltages may appear on the open secondary leads.
(ii) Check for cleanness of the cut surfaces of the split core. -
Connect the secondary wires of the current transformer with the measuring device (ampere meter, energy meter).
Pay attention to the installation guide of the measuring device. -
Now fasten the current transformer, press until the lock engage.
-
If necessary, start the current supply again.
-
Check whether the current transformer is assembled correctly and the secondary leads are connected properly.
-
For split core CT, use “lock pin” supplied along with CT to protect accidental opening of CT, during in use.
Wiring diagram
Mounting of CT
CABLE MOUNTING| BUS BAR MOUNTING
BUS BAR MOUNTING| WALL MOUNTING
DINRAIL MOUNTING HORIZONTAL| DINRAIL MOUNTING VERTICAL
BUS BAR MOUNTING 3PH CT| CABLE MOUNTING 3PH CT
DINRAIL MOUNTING
HORIZONTAL 3PH CT| DINRAIL MOUNTING
VERTICAL 3PH CT
WALL MOUNTING 3PH CT
Environmental instruction
When the product has reached it´s “end of life“, it must be recycled. Pass it
to an electrical waste disposal. Do not dispose as unsorted municipal waste!
LUMEL S.A.
ul. Słubicka 4, 65-127 Zielona Góra, Poland
tel.: +48 68 45 75 100
www.lumel.com.pl
Technical support:
tel.: (+48 68) 45 75 143, 45 75 141, 45 75 144, 45 75 140
e-mail: export@lumel.com.pl
Export department:
tel.: (+48 68) 45 75 130, 45 75 131, 45 75 132
e-mail: export@lumel.com.pl
Calibration & Attestation:
e-mail: laboratorium@lumel.com.pl
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>