LENNOX M0STAT64Q-2 Indoor Unit Programmable Controller Instruction Manual
- September 5, 2022
- Lennox
Table of Contents
M0STAT64Q-2 Indoor Unit Programmable Controller
©2021 Lennox Industries Inc. Dallas, Texas, USA
INSTALLATION/ OPERATION INSTRUCTIONS
M0STAT64Q-2 Indoor Unit Programmable Controller (22U20)
CONTROLS
507644-03 10/2021 Supersedes 507644-02
IMPORTANT
This manual must be left with the owner for future reference.
WARNING
Improper installation, adjustment, alteration, service or maintenance can
cause property damage, personal injury or loss of life. Installation and
service must be performed by a licensed professional HVAC installer (or
equivalent) or service agency.
Specifications
Input voltage
5 VDC
Ambient temperature 23~110°F (-5~43°C)
Frequent changes to operating mode may cause system malfunction. Allow at
least one minute between mode changes to allow the system to stabilize.
Shipping and Packing List
Package 1 of 1 catalog number 22U20 contains:
1 Wired Controller 1 Lithium battery 3 Screws (mount to wall) 2 Screws
(mount to J-box) 2 Plastic spacers (J-box) 1 Connection Cable A with
connector for all indoor
units 1 Connection Cable B with connector for MMDA/B,
MCFA/B, M22A and M33A/B/C indoor units 1 Connection Cable C with connector
for MWMA/B
indoor units
1 Connection Cable D for MWMC indoor unit
1 Installation and operation manual
Ambient humidity
RH40%~RH90%
1
General
The M0STAT64Q is a wired programmable local controller for mini-split indoor
units with convenient timed schedules for daily operation. These instructions
are intended as a general guide and do not supersede local codes in any way.
Consult authorities having jurisdiction before installation.
Dimensions
Requirements
Be sure that power supply has been turned off before beginning installation.
This controller should be used only as described in this manual. Do not
install the controller on outside walls (where there is unconditioned space on
opposite side of wall) or in locations where direct sunlight may be present.
120mm (4.7″)
18.5mm (0.7″)
46mm (1.8″)
123mm (4.8″)
83.5mm (3.3″)
62mm (2.4″)
Figure 1. M0STAT64Q Dimensions
Wiring Connections
WARNING
Be sure that power supply has been turned off before beginning installation.
CAUTION
Clean controller using a clean, damp cloth. Do not spray cleanser on or around
controller.
WARNING
Do not operate controller with wet hands.
CAUTION
Do not install controller in areas where heavy oil, vapor, or gases containing
sulfur may exist or the controller may be damaged.
2
IMPORTANT
Read all of the information in this manual before using this controller. All
wiring must conform to local and national building and electrical codes and
ordinances. This is a 5 VDC controller. Do not install on voltages higher than
5 VDC.
· This manual provides the installation instructions for this controller.
Refer to the included wiring diagrams to connect the controller to the indoor
unit.
· The controller uses low voltage. Keep a minimum distance of 12″ (305 mm)
between low voltage control wire and high voltage power wires.
· Ground the shielded control wiring.
IMPORTANT
The provided cables must be used. Do not use excessive force while pulling the
cable or when making the connections.
· Do not use a megger to test insulation. · The controller cable length should
not exceed
164 ft (50 m).
1. Use the wiring connections illustrations (Figures 2 and 6) to connect the
controller to the indoor unit. NOTE – Connection details for wall-mounted
units differ from the other indoor unit types.
2. Select the cable exit route from the back of the controller.
3. Include a drip loop in the cable.
4-conductor shielded wire on the controller
Cable A
Indoor unit main board
Cable B 3 ft. 7 in. (1.1m)
CN40
Receiver board (Gray cable with blue tag for all units
that require the WYE cable.)
Figure 2. Wiring Connections MMDA/B, MCFA/B, M22A and M33A/B/C
3
CN 40
Connect to controller
CN 40 Connect to controller
Figure 3. MMDA/B Main Board
Figure 4. M22A and M33A/B/C Main Board
Connect the Programmable Wired Controller to the factory installed CN4 port
cable
CN 40
Connect to controller
Figure 6. MFMA Main Board
Figure 5. MCFA/B Main Board
4
Cable A
Cable C
Receiver board CN403
4-conductor shielded wire on the controller
Figure 7. Wiring Connections MWMA/B
CN 403
Connect to controller
Factory-connected to Display Board
NOTE – CN 403 is used to connect either the M0STAT64Q local controller OR a
centralized control. It is not possible to connect both the M0STAT64Q
controller and a centralized control to this unit.
Figure 8. MWMA/B Receiver Board
Receiver board The connection cable D
Display board
The connection cable A 4-core shielding wire on the controller
CN40 X Y E 5V
CN1
White
Red
Yellow Brown
Figure 9. Wiring Connections MWMC
5
MWMC receiver board uses terminals for the programmable wired controller.
Figure 10. MWMC Receiver board
Optional Programmable Wired Controller
Factory installed CN4 Adapter Cable
Indoor unit main board
Factory installed Adapter Board
CN4
CN20 CN1
Wire Controller Cable
20 Foot Cable provided with Programmable Wired Controller
Figure 11. Wiring Connections to MFMA
6
4. Seal the cable entrance to the controller casing and any wall penetrations to prevent water
1
PCB
3
1
PCB
1
2
PCB
¹Use snips to notch the controller casing to allow the cable to pass through.
Figure 12. Select Cable Route
from entering the controller. 5. Reattach the controller to the back plate. Be
careful not to pinch or bind the wires.
Figure 14. Reattach Controller to Back Plate
Sealant
Drip Loop
Sealant
Sealant
Drip Loop
Drip Loop
Figure 13. Prevent Water from Entering Controller Casing
7
Installation 1. Remove the controller from the back plate us-
ing a flat-head screwdriver.
3. J-box installation – Adjust the length of the two plastic spacers as
needed to allow the controller to be mounted flush with the wall.
NOTE Be sure to provide for future maintenance by allowing enough slack in
the wiring to allow the controller to be removed from the wall if needed.
Back plate
Switch box
Screw (M4×20)
Slots
Figure 15. Remove Back Plate
Screws (M4×25)
2. Mount the back plate as appropriate for your
Figure 17. Attach Back Plate to J-box
application.
4. Insert the provided battery into controller,
Back plate
positive side out. The battery stores the day and time in case of power outage. Replace
the battery when it’s charge is depleted.
5. Reattach the controller to the back plate. Be
careful not to pinch or bind the wires.
Screws (M4×20)
Figure 16. Attach Back Plate to Wall
8
Display
Operation Mode
Fan Speed
Horizontal and Vertical Swing (not available for all indoor unit models)
Faceplate Not Follow me Function Used Function
Turbo/PTC
Schedule
On/Off Timer
¹ Displays cooling set point, heating set point or room temperature
°F or °C
¹Temperature display Lock Indication Room Temperature
Clock
9
Description of Buttons
Swing button (Swing function not available for all indoor unit
models)
Timer Day Off/
Delete
Decrease
Swing
Timer
Day off/Del
Confirm
Back/Turbo
Copy/ Follow me
Mode
–
Fan speed (Lock)
Copy/ Follow me Back/Turbo Confirm Mode
Power Increase
Fan speed (Lock)
10
Setup Set the Current Day and Time 1. Press and hold the Timer button for 3
sec-
onds. 2. Use the + and – buttons to select the day. The
selected day will flash. 3. Press the Timer button to complete the date
setting. 4. Use the + and – buttons to set the current time.
NOTE the controller uses a 24-hour clock. 5. Press the Timer button to
complete the time
setting.
Select Fahrenheit or Celsius for display Press and hold the Back/Turbo button
and the Copy/Follow me button simultaneously for 3 seconds to toggle between
displaying degrees Fahrenheit or degrees Celsius.
To Set Room Temperature Sensor Location Press the Copy/Follow me button to
toggle between having the room temperature sensed by the indoor unit or by the
controller. NOTE – The Follow me indicator will display on the screen when the
room temp is being sensed by the controller.
Key Pad Tone (beep) 1. Press and hold the Swing button and the Tim-
er button simultaneously for 3 seconds to turn off the key pad tone. 2. Press
and hold the Swing button and the Timer button simultaneously for 3 seconds
again to turn on the key pad tone.
11
Operation To Start/Stop Operation Press the Power button.
To set the operation mode 1.Press the Mode button to set the operation
mode. 2.Use the + and – buttons to scroll through the
mode selections. · Auto System will automatically switch be-
tween heating and cooling depending on the temperature sensed. · Cool System
operates in cooling mode. · Dry System removes humidity according to preset
conditions (fan speed and set point temperature, not a humidistat sensor).
Cannot adjust fan speed. · Heat System operates in heating mode. · Fan Fan
only, no heating or cooling.
To Set (or change) the Set point Press the + and – buttons to set the
setpoint. NOTE – the set point range is 62-86°F (17-30°C).
To Set the Fan Speed Press the Fan speed (Lock) button to scroll through the
fan speeds. Auto Low Med High
To Set Child Lock Function 1. Press and hold the Fan speed (Lock) button
for 3 seconds to lock all of the controller buttons. 2. Press and hold the Fan
speed (Lock) button again for 3 seconds to unlock all of the buttons.
Turn ON/OFF Turbo Function Press the Back/Turbo button to activate and
deactivate the turbo functionality. · Cooling Mode – Turbo sets the indoor
unit
fan speed to high for a factory-set period of time.
Set Swing Function Press the Swing button to adjust louver direction and
oscillation. 3. Press the Swing button to adjust the louver
position. Each press moves the louvers 6°. 4. Press and hold the Swing button
for two sec-
onds to begin continuous louver oscillation. The Swing icon displays on the
screen. Swing functionality not available for all indoor unit types. 5. For
cassette units only, adjust each of the four louvers independently. Press and
hold the Swing button for two seconds. The Swing icon will flash. Press the
increase or decrease buttons to select the louver to adjust (the -0 setting
makes all louvers move at the same time). After selecting the louver to
adjust, press the Swing button to adjust the louver angle. Each press moves
the louver 6°.
12
Timer and Schedules
Use the Timer button to setup Weekly schedules Create Schedules (up to 8 events per day)
or to setup timed operation for the indoor unit. 1. Press the Timer button until Week is high-
Timers are used to schedule On/Off operation only. Schedules are used to change operational settings for defined periods of time (events).
lighted. 2. Press the Confirm button. 3. Use the + and – buttons to select the
day of the
week to setup the scheduled events.
Setup Timed Operation Start Time
4. Press the Confirm button.
1. Press the Timer button until Day On is high- 5. Setup the first event of the schedule.
lighted.
2. Press the Confirm button.
Create and Setup Scheduled Events (up to 8
3. Use the + and – buttons to set the time to start events per day)
operation.
1. After selecting the scheduled day.
4. Press the Confirm button.
2. Use the + and – buttons to set the start time of the event. The display will show the event’s
Setup Timed Operation Stop Time
start time, mode, set point and fan speed.
1. Press the Timer button until Day Off is high- 3. Press the Confirm button to confirm the start
lighted.
time and move to the operation mode selec-
2. Press the Confirm button.
tion.
3. Use the + and – buttons to set the time to stop 4. Use the + and – buttons to select the opera-
operation.
tion mode for the event.
4. Press the Confirm button.
5. Press the Confirm button to confirm the op-
eration mode and move to the set point se-
Setup Timed Operation Start and Stop Time
lection.
1. Press the Timer button until Day On/Off is 6. Use the + and – buttons to set the set point
highlighted.
for the event.
2. Press the Confirm button.
7. Press the Confirm button to confirm the set-
3. Use the + and – buttons to set the time to start
point and move to the fan speed selection.
operation.
Not available when operation mode is set to
4. Press the Confirm button
Fan or Off.
5. Use the + and – buttons to set the time to stop 8. Use the + and – buttons to select the fan
operation.
speed for the event.
6. Press the Confirm button.
9. Press the Confirm button to confirm the fan
speed and complete the settings for this
event. Not available when operation mode is
13
set to Auto, Dry or Off. 10. Follow steps 2 through 9 to setup the next
event. Each event ends at the start time of the next event. NOTE – Use the
Back/Turbo button to return to the previous step during event setup.
Activate and Deactivate Timed Operation 1. Press the Timer button to activate
timed op-
eration. 2. Press the Power button to deactivate timed
operation.
Setup Days Off Setup a day, or multiple days, within the scheduled week for
which the indoor unit will not operate. When the day arrives, the unit will be
powered off and will not operate until the next day’s first event. Once the
set day has passed, the Day Off setting is automatically removed. 1. Press the
Timer button. 2. Press the Confirm button. 3. Use the + and – buttons to
select the day of
the week. 4. Press the Day off/Del button. 5. Press the Back/Turbo button. 6.
Follow steps 3 and 4 for every day off required.
Copy a Schedule to a New Day All events for the scheduled day will be copied.
- Press the Timer button until Week is high-
lighted. 2. Press the Confirm button. 3. Use the + and – buttons to select the day to
copy from.
4. Press the Copy/Follow Me button. The letters “CY” will be displayed on the
screen.
5. Use the + and – buttons to select the day to copy to.
6. Press the Copy/Follow Me button to confirm. 7. Press the Back/Turbo button
to return to the
weekly timer. 8. Follow steps 3 through 7 to copy a schedule
for additional days.
Edit a Scheduled Event 1. Press the Timer button until Week is high-
lighted. 2. Press the Confirm button. 3. Use the + and – buttons to select the
day of
the week. 4. Press the Confirm button. 5. Use the + and – buttons to select
the event to
edit. The display will show the event’s start time, mode, set point and fan
speed. 6. Use the + and – buttons to change the start time of the event. 7.
Press the Confirm button to confirm the start time and move to the operation
mode selection. 8. Use the + and – buttons to change the operation mode for
the event. 9. Press the Confirm button to confirm the operation mode and move
to the set point selection. 10. Use the + and – buttons to change the set
point for the event.
14
11. Press the Confirm button to confirm the setpoint and move to the fan
speed selection. Not available when operation mode is set to Fan or Off.
12. Use the + and – buttons to change the fan speed for the event.
13. Press the Confirm button to confirm the fan speed and complete the
changes for this event. Not available when operation mode is set to Auto, Dry
or Off.
NOTE – Use the Back/Turbo button to return to the previous step.
Delete an Event from a Scheduled Day This action cannot be undone. 1. Press
the Timer button until Week is high-
lighted. 2. Press the Confirm button. 3. Use the + and – buttons to select the
day of
the week. 4. Press the Confirm button. 5. Use the + and – buttons to select
the event to
delete. The display will show the event’s start time, mode, set point and fan
speed. 6. Press the Day off/Del button.
15
Troubleshooting Fault Codes
Programmable
Wired
Indoor Unit Error Codes Description
Controller
E1
Communication error between indoor unit and outdoor units
E2
Indoor room temperature sensor error (T1)
E3
Indoor coil temperature sensor error (T2)
E4
Indoor coil outlet temperature sensor error (T2B)
E5
Outdoor ambient temperature sensor error (T4)
E5
Outdoor coil temperature sensor error (T3)
E5
Compressor discharge temperature sensor error (T5)
E7
Indoor unit EEPROM error
E8
Indoor fan speed error (DC motor)
EA
Outdoor current overload protection
Ed
Outdoor unit EEPROM error
Ed
Outdoor unit fan speed error (DC fan motor)
EE
High water level alarm
EF
Refrigerant leakage detection (Cooling mode only)
EF
Outdoor IGBT temperature sensor error
F0
Communication error between wired controller and indoor unit
F1
The cassette panel is abnormal
16