COMMERCIAL TRAINING TOOLBOX TIPS

Economizer Setup for KG/KC/KH and ZG/ZC/ZH Units with a Siemens Climatix ECO Economizer Controller

Applies to Lennox Landmark and Raider Rooftop Units that have a factory or field installed economizer with a Siemen’s Climatix ECO controller

Helpful Resources

  1. Installation and service literature on LennoxCommercial.com or LennoxPros.com COM-01-045
    An economizer uses a combination of sensible and enthalpy sensors to determine when outside air is suitable for free cooling. The type and number of sensors depends on the controller.
    Commercial Training
  • View Service Videos Lennox Commercial YouTube Channel

  • Download all Training Toolbox Tips

  • Register for Technical Training Webinars

Self-Service Technical Support with No Wait Times
Click on the black logos below to download these apps




Apps


Siemens Climatix ECO Economizer Control Sensors

Type Sensor Cat # Action
Enthalpy Return Air 23G26 Measures return air enthalpy for dual

enthalpy(differential enthalpy) functions. Compares with Outside Air enthalpy sensor for control.
Sensible| Return Air| 59W63| Measures return air temperature for differential sensible control.
Enthalpy| Outside Air| 23G26| Measures outside air enthalpy for dual enthalpy(differential enthalpy) functions.
Sensible| Outside Air| 59W63| Compares with Outside Air enthalpy sensor for control.
Sensible| Discharge Air| 59W63| Used to connect to mobile device apMeasures discharge air after the cooling coil.
WLAN Stick| Wi-Fi dongle| 23K58| Used to connect to mobile device app