Dextra Opus 3 LED Flood Light Installation Guide
- June 9, 2024
- Dextra
Table of Contents
Opus 3 LED Flood Light
Installation Guide
Opus 3 LED Flood Light
220-240V / 50-60Hz IP65
Terminal Labelling:
Power
L1 | Switched Live |
---|---|
E **** | Earth |
N | Neutral |
Emergency
L2 | Unswitched Live |
---|---|
DA/AT3 | DALI Autotest |
DA/AT3 | DALI Autotest |
Dimming
-/D1/DA | Analogue/DSI/DALI |
---|---|
+/D2/DA | Analogue/DSI/DALI |
L3 | Switch Dim / Corridor Function |
WARNING: Luminaire must be earthed. Risk of electric shock from LED
boards if operated with cover removed. Installation / operation outside of
luminaires intended scope invalidates warranty. Suitable only for domestic /
light industrial / industrial applications within the scope of EN55015.
Tested to compliance with BSEN 60598: specification for general requirements
and tests. Must be installed by a suitably qualified person in accordance with
all relevant legislation. Ambient operating temperature of 0°C to 25°C. If
maximum operating temperature is exceeded luminaire will automatically dim /
switch off. Terminal blocks are rated to 16A unless stated otherwise. The
light source is non replaceable.
LUMINAIRES WITH EMERGENCY PACK:
When supply is isolated battery output terminals may be live if battery is
connected. Isolate mains and battery before servicing. Emergency luminaires
require Unswitched live connection taken from same phase as switched supply.
When Unswitched supply is connected status indicator illuminates green, when
Unswitched supply is disconnected indicator extinguishes and luminaire
operates in emergency mode. 24 hour charge period required before undertaking
full discharge test. Emergency test sheets provided should be used to record
all emergency tests. Batteries should be replaced when 3 hour duration is not
met. Excessive switching of permanent live may result in premature battery
failure. Battery electrolyte can be harmful to eyes / open wounds, do not
puncture, if electrolyte touches skin / eyes flush with water. Do not
incinerate batteries.
-
Remove screws securing the frame and retain.
Carefully remove the frame and glass and store safely.
-
Secure saddle bracket to a suitable surface making sure that all limitations have been observed.
To adjust the angle of the saddle bracket, use an Allen key to loosen the Hex bolts in the sides. Retighten once at desired angle.
-
If mounting in an orientation shown, ensure fitting is angled by 10° to prevent water pooling on the front cover
-
Feed mains cable into body and wire into respective terminals. Ensure the cable clamp bar is used to secure the cable.
-
Ensure the cable gland is fully tightened. Under tightening may result in failure of IP65 rating.
-
Reverse step 1 to replace frame and glass.
Do not exceed 1.5NM torque when securing front frame screws.
DIL-0269-0001
Revision – E