HOCHIKI Firenet 4127 Digital Analog Addressable Fire Alarm Control Panel Instructions
- June 4, 2024
- HOCHIKI
Table of Contents
FileNet
4127 – DIGITAL ANALOG ADDRESSABLE FIRE ALARM
CONTROL PANEL WITH PLEXIGLASS WINDOW
DESCRIPTION
This alternate build of the FireNET® 4127 control panel is equipped with a Plexiglass window to meet the requirements of major cities including the City of Denver. Access level 2 is enabled as soon as the outer door of the enclosure is opened (CAT 30 Key).
The FireNET® 4127 control panel is a digital analog addressable fire alarm
panel containing 2 or 4 SLC loops with each loop supporting 127 devices of any
combination (sensors or modules), and 127 digital analog sounder bases, for a
possible total of 254 points. Communication between devices is transferred
through standard cable (shielded or twisted pair is not required). Each panel
includes a 5.25 amp power supply and has 4 onboard NAC circuits. An RS-485 bus
provides communication to the panel network, while the RS-232 interface allows
the convenience of programming via a PC. The system will support a variety of
Hochiki devices: photo, ion, and heat sensors, which contain a
unique, patented sensor design incorporating automatic drift compensation and
day/night sensitivity mode. Additional devices include contact monitors, relay
controllers, supervised auxiliary output, and short circuit isolator modules.
In addition, interfaces to conventional detection systems can be established
by using a conventional zone monitoring module. The Loop Explorer Windows®
Software interface provides the installer with fingertip access to
installation programming and diagnostic tools. An Auto-learn feature offers
the convenience of quick-start applications. Add to this a reputation for high
quality and dedicated service makes this an exceptional product both in
performance and value.
PRODUCT LISTINGS
| UL 864, Local Signaling Unit.
Types: Automatic, manual, waterflow,
sprinkler supervisory, Auxiliary Service (local energy), Central Station
Service, Remote Station Service, and Proprietary
Service (DACT) Non-coded signaling. NFPA 70, 72 &13 Compliant| | California
State Fire Marshal
7165-0410:159
Specifications subject to change without notice.
STANDARD FEATURES
- UL 864 9th Edition Listed
- Seismic certified
- Digital analog design using Hochiki’s advanced DCP protocol for fast and robust communication
- Up to 127 sensors & modules, plus 127 digital analog sounder bases, for a total of 254 points possible per loop
- Uses standard wire, no shielded or twisted pair is required on SLC loops
- Supports Class B (style 4) and Class A (style 6 or 7) SLC loops
- 4 onboard Class B (Style Y) NAC circuits rated at 2.5 Amps each
- Programmable sensitivity levels per device & automatic day/night sensitivity modes
- Automatic daily calibration & drift compensation routine
- Large 8-line x 40-character LCD (320 char.)
- 2 loop (FN-2127 Series) or 4 loops (FN-4127 Series) versions (800 addresses/sub-address. max.)
- Dual RS-485 bus for panel network
- 2 built-in RS-232 interfaces for programming via a PC and serial printer interface
- 5 on board programmable Form C relays rated at 1 amp at 30VDC (Fire1, Fire2, trouble, supervisory, aux.)
- 500mA of auxiliary power available rated at 24 VDC
- Loop Explorer Windows® configuration utility
- 500 network-wide software zones
- The network capability of up to 64 panels
- RS485 slave bus for expansion – up to 32 FN-4127-IO boards or up to 15 FN-LCD-S serial annunciators and up to 17 FN-4127-IO boards
- Auto-learn feature
- Fire Drill test function
- Walk test function
- Alarm verification feature
- FireNET® is UL listed for Central Station Service, Remote Station Service, and Proprietary Service
- Operates on 120VAC or 240VAC input voltage
- Powerful & versatile Cause & Effect programming (up to 500 maximum, network-wide) including:
Cause & Effect action
Disable function configuration
*Test mode configuration
SPECIFICATIONS
Primary AC | 120VAC @ 2.1 Amps 60hz or 220VAC @ 1.1Amps 50hz |
---|---|
Output DC | 24VDC @ 5.25 Amps (4 Amps available for system power) |
Power Supply | 5.25 Amps integrated |
Charger Current | 1.5 Amps max. |
Dimensions | 14.5″ W x 24″ H x 5″ D |
Weight | 31 lbs. (without batteries) |
Color | Red (optional gray) |
Material | ABS/steel enclosure |
Display | 8 line x 40 character LCD (320 characters total) |
Network | Dual RS485 ports (64 panels max.) |
Zones | 500 network-wide software zones per system |
SLC loops | 2 or 4 (class A, “style 6 or 7” or class B, “style 4”) |
Devices per loop | 127 sensors & modules, plus 127 digital analog sounder |
bases, 254 total
Addresses per panel| (800 addresses+sub-addresses max. per panel)
NAC Outputs| (4) 2.5 Amps @ 24VDC (class B)
Relay Outputs| (5) Form C 1 Amp @ 30VDC
Voltage Outputs| (3) 500mA @ 24VDC
Aux. Power| 500mA @ 24VDC
Aux. Inputs| (8) digital pull-downs
PC Port / Printer| RS232
FIRENET® ORDERING MODELS
MODEL | DESCRIPTION |
---|---|
FN-2127-DDW | FACP (2 Loop/5.25 Amps) |
FN-2127-DDWN | FACP (2 Loop/5.25 Amps) (w/Network) |
FN-4127-DDW | FACP (4 Loop/5.25 Amps) |
FN-4127-DDWN | FACP (4 Loop/5.25 Amps) (w/Network) |
SLC COMPATIBLE DEVICES & SYSTEM ACCESSORIES
CONTROL PANEL EXPANDERS
FN-4127-SLC | Dual SLC Loop Expansion Card |
---|---|
FN-4127-NIC | Network Interface Card |
FN-4127-IO 16 | 16 Channel Input/Output Board |
FN-DAC | Digital Alarm Communicator |
FN-CTM | City-Tie Module (Local Energy Type) |
ANNUNCIATOR
FN-LCD-N | Network LCD Annunciator |
---|---|
FN-LCD-S | Serial LCD Annunciator |
SLC LOOP DEVICES
ALG-V, ALK-V, ALN-V | Digital Analog Addressable Photoelectric Sensor |
---|---|
AIE-EA | Digital Analog Addressable Ionization Sensor |
ATG-EA, ATJ-EA | Digital Analog Addressable Heat Sensor |
ACA-V, ACC-V | Multi-criteria Sensor |
NSA-4 & NSA-6 | Four Inch Sensor Base and Six Inch Sensor Base |
SCI-B4 & SCI-B6 | Four Inch Short Circuit Isolator Digital Analog Sensor Base & |
Six Inch Circuit Isolator Digital Analog Sensor Base
ASB| Digital Analog Sounder Base
ASBL| Digital Analog Low Frequency Sounder Base
DH-98A, DH-98AR, DH-99A, DH-99AR| Digital Analog Addressable Duct Detector
Unit (DH-98AR and DH-99AR have relays built-in)
MS-RA, MS-RA/R, MS-KA/R| Remote Test Station for DH-98AR & DH-99AR
DCP-FRCME-M| Contact Monitoring Module (mini w/terminal blocks)
DCP-FRCME-P| Contact Monitoring Module (mini w/pigtail leads)
DCP-FRCME-4| Contact Monitoring Module (with faceplate/indicating LED)
DCP-FRCMA, DCP-FRCMA-I| Class A Contact Monitoring Module (FRCMA-I has built-
in SCI)
DCP-DIMM| Dual Input Monitor Module (with faceplate/indicating LED)
DCP-CZM| Conventional Zone Module
DCP-R2M| Dual Relay Module
DCP-R2ML/H Series| Dual Relay Module (R2ML-I & R2MH-I has built-in SCI)
DCP-SOM| Supervised Output Module
DCP-SOM-A, DCP-SOM-AI| Class A Supervised Output Module (SOM-AI has built-in
SCI)
DCP-SOM-R| Supervised Output Module for Releasing Pre-action System
DCP-SCI| Short Circuit Isolator Module
DCP-AMS Series| Addressable Manual Pull Station
ACCESSORIES
TCH-B100 | Hand Held Programmer (portable device addresser) |
---|---|
FN-ACC | Battery/Accessory Enclosure (houses up to 33AH size batteries) |
FNP-ETR | Enclosure Trim Ring for panel flush mount |
Hochiki America Corporation FireNET DIGITAL ANALOG ADDRESSABLE FIRE ALARM CONTROL PANEL Specifications are subject to change without notice.
Hochiki America Corporation
7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714-522-2246 Fax:
714-522-2268
Technical Support: 800-845-6692 or
technicalsupport@hochiki.com
Find the latest revision at www.hochiki.com
F0093 Rev.1 07/2017