HOCHIKI FireNET Plus 1127 Analog Addressable Fire Alarm Control Panel Owner’s Manual
- June 9, 2024
- HOCHIKI
Table of Contents
FireNET™ Plus 1127 – ANALOG
ADDRESSABLE FIRE ALARM CONTROL PANEL
Owner’s Manual
DESCRIPTION
The FireNET™ Plus 1127 series control panel is an analog addressable fire
alarm panel with build options containing 1 or 2 SLC loops, a Digital Alarm
Communicator/ Transmitter (DACT), and an RS-485 bus for network communication.
Each SLC loop supports 127 devices of any combination (sensors or modules),
and 127 analog sounder bases, for a possible total of 254 points per loop.
Communication between devices is accomplished by use of standard cable
(shielded or twisted pair is not required). Each panel includes a 4-amp power
supply and has 2 onboard NAC circuits. The RS-485 bus provides communication
to the panel network while another RS-485 bus provides communication for
peripheral devices. The RS-232 interface allows the convenience of programming
via a PC. The system will support a variety of Hochiki devices; photo, ion and
heat sensors, which contain a unique, patented sensor design incorporating
automatic drift compensation and day/night sensitivity modes. Additional
devices include contact monitors, relay controllers, supervised auxiliary
output and short circuit isolator modules. In addition, interfaces to
conventional detection systems can be established by using a conventional
zonemonitoring module. The Loop Explorer Windows® Software interface provides
the installer with fingertip access to installation programming and diagnostic
tools. An Auto Learn feature offers the convenience for quick start
applications. Add to this a reputation for high quality and dedicated service
which makes this an exceptional product both in performance and value.
Specifications subject to change without notice.
STANDARD FEATURES
- Analog design using Hochiki’s advanced DCP protocol for fast communication
- Up to 127 sensors & modules, plus 127 analog sounder bases, for a total of 254 points possible per loop
- Uses standard wire, no-shielded or twisted pair required on SLC loops
- Integrated digital alarm communicator (DACT) with Contact ID and SIA reporting formats
- Programmable sensitivity levels by device
- Alarm Verification feature
- Automatic daily calibration & drift compensation routine
- Large 8-line x 40-character LCD display (320 char.)
- 1 or 2 loop (option)
- RS-485 bus for panel network (option)
- Built-in RS-232 interface for programming via a PC
- 3 on board programmable Form C relays rated at 1 amp at 30VDC
- 2 auxiliary power outputs, each rated 360mA at 24 VDC
- Loop Explorer Windows® configuration utility
- Auto-learn feature
- 500 network wide software zones
- Network Capability of up to 64 panels (option)
- Built in help and alarm information screens
- 2 on-board Class B (style Y) NAC circuits rated at 2.3 amps each (Special Application) and 1.6 amps each (Regulated continuous)
- Gentex, System Sensor, Wheelock, and Amseco NAC sync protocol built-in
- Automatic day/night sensitivity modes
- Fire Drill test function
- Walk Test function
- Powerful & versatile Cause & Effect wizard including: Cause & Effect action Disable function configuration *Test mode configuration
PRODUCT LISTINGS
UL 864, Local Signaling Unit.
Types: Automatic, manual, waterflow, sprinkler supervisoryRemote Station
and Central Station Service (DACT) Non-coded signaling. NFPA 70, 72 &13
Compliant
California State Fire Marshal
7165-0410:180
SPECIFICATIONS
Primary AC | 120VAC @ 2.1 Amps 50/60hz or 220VAC @ 1.1Amps 50/60hz |
---|---|
Output DC | 24VDC @ 5.25 Amps |
Power Supply | 4 Amp integrated |
Charger Current | 1.5 Amps max. |
Dimensions | 14.5″ W x 19″ H x 3.5″ D |
Weight | 20 lbs. (without batteries) |
Color | Red (optional charcoal) |
Material | ABS/steel enclosure |
Display | 8 line x 40 character LCD (320 characters total) |
Network | Dual RS485 ports (64 panels max.) |
Zones | 500 network wide software zones per system |
SLC loops | 1 or 2 (class A, “style 6 or 7” or class B, “style 4”) |
Devices per loop | 127 sensors & modules, plus 127 analog sounder bases, 254 |
total
Addresses per panel| 800 addresses+sub-addresses max. per panel
NAC Outputs| (2)class B, 2.3 Amps (special application)
1.6 Amps Regulated (continuous)
Relay Outputs| (3)Form C 1 Amp @ 30VDC
Aux. Power| 2 outputs, 360mA @ 24VDC each
PC Port / Printer| RS232
DACT Formats| Contact ID and SIA
SLC COMPATIBLE DEVICES & SYSTEM ACCESSORIES
MODEL | DESCRIPTION |
---|
CONTROL PANEL EXPANDERS
FNP-1127-SLC| SLC One Loop Expansion Card
FN-4127-NIC| Network Interface Card
FN-4127-IO| 16 Channel Input/Output Board
ANNUNCIATOR
FN-LCD-S| Serial LCD Annunciator
FNP-LED| Graphix Display
SLC LOOP DEVICES
ALG-V, ALK-V| Analog Addressable Photoelectric Sensor
AIE-EA| Analog Addressable Ionization Sensor
ATG-EA| Analog Addressable Heat Sensor
NSA-6| Six inch Sensor Base
NSA-4| Four inch Sensor Base
ASB| Analog Sounder Base
DH-98A| Analog Addressable Duct Detector Unit
DH-98AR| Analog Addressable Duct Detector Unit (with relays)
MS-RA, MS-RA/R, MS-KA/R| Remote Test Station for DH98AR
FRCME-S| Contact Monitoring Module (mini w/terminal blocks)
FRCME-P| Contact Monitoring Module (mini w/pigtail leads)
FRCME-4| Contact Monitoring Module (with faceplate/indicating LED)
FRCMA, FRCMA-I| Class A Contact Monitoring Module (FRCMA-I has Built-in SCI)
DIMM| Dual Input Monitor Module (with faceplate/indicating LED)
CZM| Conventional Zone Module
R2M| Dual Relay Module
R2ML/H Series| Dual Relay Module (R2ML-I & R2MH-I has Built-in SCI)
SOM| Supervised Output Module
SOM-A, SOM-AI| Class A Supervised Output Module (SOM-AI has Built-in SCI)
SCI| Short Circuit Isolator Module
AMS Series| Addressable Manual Pull Station
ACCESSORIES
TCH-B100| Hand Held Programmer (portable device addresser)
FN-ACC| Battery/Accessory Enclosure (houses up to 33AH size batteries)
FNP-ETR| Enclosure Trim Ring for Panel Flush Mount
Hochiki America Corporation
7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246
Fax: 714/522-2268
Technical Support 800/845-6692
ortechnicalsupport@hochiki.com
Find latest revision at www.hochiki.com
F0087 03/2010
References
- Fire Alarm Resources | Download fire alarm documents
- Hochiki | Fire Protection Equipment and Systems
Read User Manual Online (PDF format)