HOCHIKI SOC-24VN Conventional Photoelectric Smoke Detector Instruction Manual
- June 4, 2024
- HOCHIKI
Table of Contents
HOCHIKI SOC-24VN Conventional Photoelectric Smoke Detector
STANDARD FEATURES
- Computer-designed non-directional smoke chamber
- 360° view of detector status LED
- Low profile, 2″ high (with base)
- 2 or 4 wire base compatibility, relay bases available
- Highly stable operation, RF/Transient protection
- Low standby current, 59μA at 24VDC
- One built-in power/sensitivity supervision/alarm LED
- Automatic Sensitivity window verification function meets outlined requirements in NFPA 72, Chapter 2 & 7, Inspection, Testing and Maintenance.
- Without Magnetic Test Feature
SPECIFICATIONS
- Light Source GaAIAs Infrared Emitting Diode
- Nominal Rated Voltage 24 VDC
- Working Voltage 8 – 35.0 VDC
- Maximum Voltage 42 VDC
- Supervisory Current 59µA @ 24 VDC
- Surge Current 160µA max. @ 24VDC
- Alarm Current 150mA max. @24 VDC
- Air Velocity Range 0-4000 fpm
- Maximum Humidity 95% RH Non-Condensing
- Ambient Temperature 32°F to 120°F (0°C to 49°C)
- Color & Case Material Bone PC/ABS Blend
- Sensitivity Test Feature Automatic Sensitivity window verification test
- Sensitivity Range 1.36%/FT ~ 3.12%/FT
- Mounting Refer to NS Conventional Detector Base Data Sheet
APPLICATIONS
The SOC-24VN is a reliable, high-quality Photoelectric Smoke Detector. It can be used in all open areas where Photoelectric Smoke Detectors are required, including in-duct applications. The computer-designed smoke chamber makes the SOC24VN well suited for detecting smoldering fires as well as fast flaming fires. NS-4 Series, NS-6 Series, HSC-4R or HSC-R Style bases may be used with the SOC-24VN.
OPERATION
The SOC-24VN photoelectric smoke detector utilizes one bicolored LED for indication of status. In a normal standby condition the LED flash Green every 3 seconds. When the detector senses that its sensitivity has drifted outside the UL listed sensitivity window the LED will flash Red every 3 seconds. When the detector senses smoke and goes into alarm the status LED will latch on Red. The detector utilizes an infrared LED light source and silicon photodiode receiving element in the smoke chamber. In a normal standby condition, the receiving element receives no light from the pulsing LED light source. In the event of a fire, smoke enters the detector smoke chamber and light is reflected from the smoke particles to the receiving element. The light received is converted into an electronic signal. Fire Judgement signals are processed and compared to a reference level, and when five consecutive signals exceeding the reference level are received within a specified period of time, the time delay circuit triggers the SCR switch to activate the alarm signal. The status LED light continuously during the alarm period.
SENSOR SPACING
Smoke sensor spacing shall be in compliance with NFPA 72. For smooth ceilings and in the absence of specific performance-based design criteria, the distance between smoke sensors shall not exceed a nominal spacing of 30 ft. (9.1m) or all points on the ceiling shall have a sensor within a distance equal to or less than 0.7 times the nominal 30 ft. (9.1m) spacing. Sensors shall be located within a distance of one-half the nominal spacing, measured at right angles from all walls or partitions extending upward to within the top 15 percent of the ceiling height. For additional instructions see NFPA 72.
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, Hochiki America Model SOC-24VN photoelectric smoke detectors. The combination detector head and twist-lock base shall be UL listed compatible with a UL listed fire alarm panel. The base shall permit direct interchange with Hochiki America SOC-24VN photoelectric smoke detector. The base shall be appropriate twist- lock base NS-4 Series, NS-6 Series, HSC-4R, or HSC-R. In the event of partial or complete retrofit, the SOC-24VN maybe used in conjunction with, or as a replacement for, Hochiki America detectors (SLR-24V, SLR-24VN, SLK-24 and the SLR24H) on most HSB and HSC base applications. The smoke detector shall have one flashing status LED for visual supervision. When the detector is in standby condition the LED will flash Green. When the detector is outside the UL listed sensitivity window the LED will flash Red. When the detector is actuated, the flashing LED will latch on Red. The detector may be reset by actuating the control panel reset switch. The sensitivity of the detector shall be capable of being measured. The sensitivity of the detector shall be monitored automatically and continuously to verify that it is operating within the listed sensitivity range. To facilitate installation, the detector shall be non-polarized. Voltage and RF transient suppression techniques shall be employed to minimize false alarm potential. Auxiliary SPDT relays shall be installed where indicated.
SOC-24VN SENSITIVITY TEST FEATURE
The SOC-24VN Photoelectric Smoke Detector has a built-in automatic sensitivity test feature.
- In normal condition, the status LED flashes green.
- When the sensitivity drifts outside of its sensitivity limits, the status LED flashes red.
- In the alarm state, the status LED is red continuously.
- When the sensitivity drifts outside of its sensitivity limits and the LED flash red, the device needs to be cleaned or returned to the factory for cleaning or calibration. Refer to HA Technical Bulletin HA-97 for cleaning information.
Hochiki America Corporation
7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Phone: 714-522-2246 Fax:
714-522-2268
Technical Support: 800-845-6692 or
technicalsupport@hochiki.com