LENNOX Merit Series ML17XP1 Heat Pump Units Instruction Manual
- June 9, 2024
- Lennox
Table of Contents
- INSTALLATION INSTRUCTIONS
- STEP 1 – SETTING THE UNIT – Clearances
- UNIT DIMENSIONS – INCHES (MM)
- STEP 1 – SETTING THE UNIT (Continued) – Unit Placement
- PLACEMENT
- SLAB MOUNTING
- STEP 2 – REFRIGERANT PIPING
- CONNECT GAUGES AND EQUIPMENT FOR FLUSHING PROCEDURE
- REFRIGERANT PIPING – Brazing Procedures
- WRAP SERVICE VALVES
- FLOW NITROGEN
- BRAZE LINE SET
- PREPARATION FOR NEXT STEP
- STEP 2 – REFRIGERANT PIPING – Install Indoor Expansion Valve
- INDOOR EXPANSION VALVE INSTALLATION
- EQUALIZER LINE INSTALLATION
- SENSING BULB INSTALLATION
- EVACUATION
- STEP 4 – ELECTRICAL – Circuit Sizing and Wire Routing
- INSTALL THERMOSTAT
- OPERATING MANIFOLD GAUGE SET AND SERVICE VALVES
- OPERATING BALL-TYPE SERVICE VALVE
- OPERATING ANGLE-TYPE SERVICE VALVE
- ACCESS SERVICE PORT
- Reinstall Stem Cap
- Checking Refrigerant Charge
- Defrost System
- Homeowners Information
- Professional Maintenance
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
LENNOX Merit Series ML17XP1 Heat Pump Units
THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER FOR FUTURE REFERENCE
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC installer or equivalent, or service agency.
WARNING
To prevent serious injury or death:
- Lock-out/tag-out before performing maintenance.
- If system power is required (e.g., smoke detector maintenance), disable power to blower, remove fan belt where applicable, and ensure all controllers and thermostats are set to the “OFF” position before performing maintenance.
- Always keep hands, hair, clothing, jewelry, tools, etc. away from moving parts.
INSTALLATION INSTRUCTIONS
General
This ML17XP1 outdoor heat pump with all-aluminum coil is designed for use with HFC-410A refrigerant only. This unit must be installed with an approved indoor air handler or coil. For AHRI Certified system match-ups and expanded ratings, visit www.LennoxPros.com. These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
NOTICE!
Charging information is given on the charging procedure sticker on the unit access panel. For more in-depth information, consult the Installation and Service Procedures manual, available on LennoxPros.com or through the Technical Support department at 800-453-6669.
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.
IMPORTANT: Special procedures are required for cleaning the all-aluminum coil in this unit. See page 15 in this instruction for information.
STEP 1 – SETTING THE UNIT – Clearances
NOTES –
Service clearance of 30 in. (762 mm) must be maintained on one of the sides adjacent to the control box.
Clearance to one of the other three sides must be 36 in. (914 mm).
Clearance to one of the remaining two sides may be 12 in. (305 mm) and the final side may be 6 in. (152 mm).
A clearance of 24 in. must be maintained between two units.
48 in. (1219 mm) clearance required on top of unit.
UNIT DIMENSIONS – INCHES (MM)
Model Number | A | B |
---|---|---|
ML17XP1-018-230 | 28-1/4 (718) | 43-1/4 (1099) |
ML17XP1-024-230 | 28-1/4 (718) | 43-1/4 (1099) |
ML17XP1-030-230 | 28-1/4 (718) | 32-1/4 (819) |
ML17XP1-036-230 | 32-1/4 (819) | 32-1/4 (819) |
ML17XP1-042-230 | 32-1/4 (819) | 37-1/4 (946) |
ML17XP1-048-230 | 32‐1/4 (819) | 37-1/4 (946) |
ML17XP1-060-230 | 32‐1/4 (819) | 43-1/4 (1099) |
STEP 1 – SETTING THE UNIT (Continued) – Unit Placement
NOTICE!
Roof Damage!
This system contains both refrigerant and oil. Some rubber roofing material
may absorb oil, causing the rubber to degrade. Failure to follow this notice
could result in damage to roof surface.
IMPORTANT
This unit must be matched with an indoor coil as specified with AHRI. For AHRI Certified system match-ups and expanded ratings, visit www.LennoxPros.com. Coils previously charged with HCFC-22 must be flushed.
WARNING
To prevent personal injury, as well as damage to panels, unit or structure,
observe the following:
While installing or servicing this unit, carefully stow all removed panels so
that the panels will not cause injury to personnel, objects or nearby
structures. Also, take care to store panels where they will not be subject to
damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any weather conditions
(especially wind) that may cause panels to be blown around and damaged.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
IMPORTANT
Exhaust vents from dryers, water heaters and furnaces should be directed away from the outdoor unit. Prolonged exposure to exhaust gases and the chemicals contained within them may cause condensation to form on the steel cabinet and other metal components of the outdoor unit. This will diminish unit performance and longevity
PLACEMENT
SLAB MOUNTING
IMPORTANT
This model is designed for use in check / expansion valve systems only. An indoor expansion valve approved for use with HFC-410A refrigerant must be ordered separately and installed prior to operating the system.
NOTE – An optional Unit Stand-Off Kit (94J45) is available for this unit. Black high-density polyethylene feet raise unit off of mounting surface away from damaging moisture. Four feet are furnished per order number.
STEP 2 – REFRIGERANT PIPING
IMPORTANT
If this unit is being matched with an approved line set or indoor unit coil
that was previously charged with mineral oil, or if it is being matched with a
coil which was manufactured before January of 1999, the coil and line set must
be flushed prior to installation. Take care to empty all existing traps.
Polyol ester (POE) oils are used in Lennox units charged with HFC-410A
refrigerant.
Residual mineral oil can act as an insulator, preventing proper heat transfer.
It can also clog the expansion device and reduce system performance and
capacity. Failure to properly flush the system per this instruction and the
detailed Installation and Service Procedures manual will void the warranty.
Flush the existing line set per the following instructions. For more information, refer to the Installation and Service Procedures manual available on LennoxPros.com. CAUTION – DO NOT attempt to flush and re-use existing line sets or indoor coil when the system contains contaminants (i.e., compressor burn out).
If a new line set is being installed, size the piping per table 1.
TABLE 1
REFRIGERANT LINE SET – INCHES (MM)
Model| Valve Field Connections| Recommended Line Set
Liquid Line| Vapor Line| Liquid Line| Vapor Line| L15
Line Sets
-018| 3/8 in. (10 mm)| 3/4 in. (19 mm)| 3/8 in. (10 mm)| 3/4 in. (19 mm)| L15-41 15 ft. – 50 ft. (4.6 m – 15 m)
-024
-030
-036| 3/8 in. (10 mm)| 7/8 in. (22 mm)| 3/8 in. (10 mm)| 7/8 in. (22 mm)| L15-65 15 ft. – 50 ft. (4.6 m – 15 m)
-042
-048
-060| 3/8 in. (10 mm)| 1-1/8 in. (28 mm)| 3/8 in. (10 mm)| 1-1/8 in. (28 mm)| Field Fabricated
NOTE – Some applications may require a field-provided 7/8″ to 1-1/8″ adapter.
NOTE – When installing refrigerant lines longer than 50 feet, refer to
the Refrigerant Piping Design and Fabrication Guidelines manual available on
LennoxPros.com (Corp. 9351-L9), or contact the Technical Support Department
Product Application group for assistance.
NOTE – For new or replacement line set installation, refer to Service and
Application Note – Corp. 9112-L4 (C-91-4).
WARNING
WARNING
| When using a high pressure gas such as nitrogen to pressurize a
refrigeration or air conditioning system, use a regulator that can control the
pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and
recovered responsibly. Failure to follow this warning may result in personal
injury or death.
WARNING
| Fire, Explosion and
Personal Safety hazard. Failure to follow this warning could result in damage,
personal injury or death.
Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when
exposed to a spark or open flame, can cause fire and/ or an explosion, that
could result in property damage, personal injury or death.
WARNING
Polyol ester (POE) oils used with HFC-410A refrigerant absorb moisture very
quickly. It is very important that the refrigerant system be kept closed as
much as possible. DO NOT remove line set caps or service valve stub caps until
you are ready to make connections.
IMPORTANT
Some scroll compressors have an internal vacuum protector that will unload scrolls when suction pressure goes below 20 psig. A hissing sound will be heard when the compressor is running unloaded. Protector will reset when low pressure in system is raised above 40 psig. DO NOT REPLACE COMPRESSOR.
1A TYPICAL EXISTING FIXED ORIFICE REMOVAL PROCEDURE (UNCASED COIL SHOWN)
A – On fully cased coils, remove the coil access and plumbing panels.
B – Remove any shipping clamps from the liquid line and distributor as
sembly.
C – Using two wrenches, disconnect liquid line from liquid line orifice
housing. Take care not to twist or damage distributor tubes during this
process.
D – Remove and discard fixed orifice, valve stem assembly (if present)
and Teflon® washer as illustrated above.
E – Use a field-provided fitting to temporarily reconnect the liquid line
to the indoor unit’s liquid line orifice housing.
1B TYPICAL EXISTING EXPANSION VALVE REMOVAL PROCEDURE (UNCASED COIL SHOWN)
A – On fully cased coils, remove the coil access and plumbing panels.
B – Remove any shipping clamps from the liquid line and distributor
assembly.
C – Disconnect the equalizer line from the check expansion valve
equalizer line fitting on the vapor line.
D – Remove the vapor line sensing bulb.
E – Disconnect the liquid line from the check expansion valve at the
liquid line assembly.
F – Disconnect the check expansion valve from the liquid line orifice
housing. Take care not to twist or damage distributor tubes during this
process.
G – Remove and discard check expansion valve and the two Teflon® rings.
H – Use a field-provided fitting to temporarily reconnect the liquid line
to NEW the indoor unit’s liquid line orifice housing.
CONNECT GAUGES AND EQUIPMENT FOR FLUSHING PROCEDURE
A – HCFC-22 cylinder with clean refrigerant (positioned to deliver liquid
refrigerant) to the vapor service valve.
B – HCFC-22 gauge set (low side) to the liquid line valve.
C – HCFC-22 gauge set center port to inlet on the recovery machine with
an empty recovery tank connected to the gauge set.
D – Connect recovery tank to recovery machine per machine instructions.
REFRIGERANT PIPING – Brazing Procedures
-
CUT AND DEBUR Cut ends of the refrigerant lines square (free from nicks or dents) and debur the ends. The pipe must remain round. Do not crimp end of the line.
DO NOT CRIMP SERVICE VALVE CONNECTOR WHEN PIPE IS SMALLER THAN CONNECTION
-
CAP AND CORE REMOVAL Remove service cap and core from both the vapor and liquid line service ports.
-
ATTACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND VAPOR LINE SERVICE VALVES
Flow regulated nitrogen (at 1 to 2 psig) through the low-side refrigeration gauge set into the liquid line service port valve, and out of the vapor line service port valve.
A – Connect gauge set low pressure side to liquid line service valve (service port).
B – Connect gauge set center port to bottle of nitrogen with regulator.
C – Remove core from valve in vapor line service port to allow nitrogen to escape.
CAUTION
Brazing alloys and flux contain materials which are hazardous to your health. Avoid breathing vapors or fumes from brazing operations. Perform operations only in well-ventilated areas. Wear gloves and protective goggles or face shield to protect against burns. Wash hands with soap and water after handling brazing alloys and flux.
WARNING
| Danger of fire. Bleeding the refrigerant charge from only the high side may result in pressurization of the low side shell and suction tubing. Application of a brazing torch to a pressurized system may result in ignition of the refrigerant and oil mixture. Check the high and low pressures before applying heat.
WRAP SERVICE VALVES
To help protect service valve seals during brazing, wrap water-saturated cloths around service valve bodies and copper tube stubs. Use additional water-saturated cloths underneath the valve body to protect the base paint.
FLOW NITROGEN
Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve and out of the vapor valve stem port. See steps 3A, 3B and 3C on manifold gauge set connections.
BRAZE LINE SET
Wrap both service valves with water-saturated cloths as illustrated here and as mentioned in step before brazing to line set. Cloths must remain water- saturated throughout the brazing and cool-down process.
IMPORTANT — Allow braze joint to cool. Apply additional water-saturated cloths to help cool brazed joint. Do not remove water-saturated cloths until piping has cooled. Temperatures above 250ºF will damage valve seals.
WARNING
FIRE, PERSONAL INJURY, OR PROPERTY DAMAGE may result if you do not wrap a
water-saturated cloth around both liquid and suction line service valve bodies
and copper tube stub while brazing the line set! The braze, when complete,
must be quenched with water to absorb any residual heat.
Do not open service valves until refrigerant lines and indoor coil have been
leak-tested and evacuated. Refer to Installation and Service Procedures manual
found on LennoxPros.com.
PREPARATION FOR NEXT STEP
After all connections have been brazed, disconnect manifold gauge set from service ports. Apply additional water saturated cloths to both services valves to cool piping. Once piping is cool, remove all water-saturated cloths.
STEP 2 – REFRIGERANT PIPING – Install Indoor Expansion Valve
This outdoor unit is designed for use in systems that include an expansion valve metering device (purchased separately) at the indoor coil. See the ML17XP1 Product Specifications bulletin (EHB) for approved expansion valve kit match ups and application information. The check expansion valve unit can be installed internal or external to the indoor coil. In applications where an uncased coil is being installed in a field-provided plenum, install the check/expansion valve in a manner that will provide access for future field service of the expansion valve. Refer to below illustration for reference during installation of expansion valve unit.
INDOOR EXPANSION VALVE INSTALLATION
EQUALIZER LINE INSTALLATION
-
Remove and discard either the flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port on the vapor line as illustrated in the figure below.
-
Remove the field-provided assembly.
-
Install one of the provided Teflon® rings around the stubbed end of the check expansion valve and lightly lubricate the connector threads and expose surface of the Teflon® ring with refrigerant oil.
-
Attach the stubbed end of the check expansion valve to the liquid line orifice housing. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above, or tighten to 20 ft-lb.
-
Place the remaining Teflon® washer around the other end of the check expansion valve. Lightly lubricate connector threads and expose surface of the Teflon® ring with refrigerant oil.
-
Attach the liquid line assembly to the check expansion valve. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above or tighten to 20 ft-lb.
SENSING BULB INSTALLATION
-
Attach the vapor line sensing bulb in the proper orientation as illustrated to the right using the clamp and screws provided.
NOTE – Though it is preferred to have the sensing bulb installed on a horizontal run of the vapor line, installation on a vertical run of piping is acceptable if necessary.
NOTE – Confirm proper thermal contact between vaporline and check/expansion bulb before insulating the sensing bulb once installed. -
Connect the equalizer line from the check expansion valve to the equalizer vapor port on the vapor line. Finger tighten the flare nut plus 1/8 turn (7 ft-lbs) as illustrated below.
NOTE – NEVER MOUNT THE SENSING BULB ON BOTTOM OF LINE.
STEP 3 – LEAK TEST AND EVACUATION
LEAK TEST
-
CONNECT GAUGE SET
A – Connect the high pressure hose of an HFC-410A manifold gauge set to the vapor valve service port.
NOTE – Normally, the high pressure hose is connected to the liquid line port. However, connecting it to the vapor port better protects the manifold gauge set from high pressure damage.
B – With both manifold valves closed, connect the cylinder of HFC-410A refrigerant to the center port of
the manifold gauge set. CONNECT GAUGE SET
NOTE – Later in the procedure, the HFC-410A container will be replaced by the nitrogen container. -
TEST FOR LEAKS
After the line set has been connected to the indoor and outdoor units, check the line set connections and indoor unit for leaks. Use the following procedure to test for leaks:
A – With both manifold valves closed, connect the cylinder of HFC-410A refrigerant to the center port of the manifold gauge set. Open the valve on the HFC-410A cylinder (vapor only).
B – Open the high pressure side of the manifold to allow HFC-410A into the line set and indoor unit. Weigh in a trace amount of HFC-410A. [A trace amount is a maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure.] Close the valve on the HFC-410A cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the HFC-410A cylinder.
C – Connect a cylinder of nitrogen with a pressure regulating valve to the center port of the manifold gauge set.
D – Adjust nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit.
E – After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector.
F – After leak testing, disconnect gauges from service ports.
EVACUATION
CONNECT GAUGE SET
NOTE – Remove cores from service valves (if not already done).
A – Connect low side of manifold gauge set with 1/4 SAE in-line tee to
vapor line service valve
B – Connect high side of manifold gauge set to liquid line service valve
C – Connect available micron gauge connector on the 1/4 SAE in-line tee.
D – Connect the vacuum pump (with vacuum gauge) to the center port of the
manifold gauge set. The center port line will be used later for both the HFC-
410A and nitrogen containers.
EVACUATE THE SYSTEM
A – Open both manifold valves and start the vacuum pump.
B – Evacuate the line set and indoor unit to an absolute pressure of
23,000 microns (29.01 inches of mercury).
NOTE – During the early stages of evacuation, it is desirable to close
the manifold gauge valve at least once. A rapid rise in pressure indicates a
relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE – The term absolute pressure means the total actual pressure above
absolute zero within a given volume or system. Absolute pressure in a vacuum
is equal to atmospheric pressure minus vacuum pressure.
C – When the absolute pressure reaches 23,000 microns (29.01 inches of
mercury), perform the following: Close manifold gauge valves. Close valve on
vacuum pump. Turn off vacuum pump. Disconnect manifold gauge center port hose
from vacuum pump. Attach manifold center port hose to a nitrogen cylinder with
pressure regulator set to 150 psig (1034 kPa) and purge the hose. Open
manifold gauge valves to break the vacuum in the line set and indoor unit.
Close manifold gauge valves.
D – Shut off the nitrogen cylinder and remove the manifold gauge hose
from the cylinder. Open the manifold gauge valves to release the nitrogen from
the line set and indoor unit.
E – Reconnect the manifold gauge to the vacuum pump, turn the pump on,
and continue to evacuate the line set and indoor unit until the absolute
pressure does not rise above 500 microns (29.9 inches of mercury) within a
20-minute period after shutting off the vacuum pump and closing the manifold
gauge valves.
F – When the absolute pressure requirement above has been met, disconnect
the manifold hose from the vacuum pump and connect it to a cylinder of HFC-
410A positioned to deliver liquid refrigerant. Open the manifold gauge valve 1
to 2 psig in order to release the vacuum in the line set and indoor unit.
G – Perform the following: Close manifold gauge valves. Shut off HFC-410A
cylinder.
Reinstall service valve cores by removing manifold hose from service valve.
Quickly install cores with core tool while maintaining a positive system
pressure. Replace stem caps and finger tighten them, then tighten an
additional one-sixth (1/6) of a turn as illustrated.
WARNING ! Possible equipment damage. Avoid deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuum can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty
STEP 4 – ELECTRICAL – Circuit Sizing and Wire Routing
In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC). Refer to the furnace or air handler installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.
24VAC TRANSFORMER Use the transformer provided with the furnace or air handler for low-voltage control power (24VAC – 40 VA minimum)
WARNING
| Electric Shock Hazard. Can cause injury or death. Unit must be properly grounded in accordance with national and local codes. Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.
SIZE CIRCUIT AND INSTALL SERVICE DISCONNECT SWITCH
Refer to the unit nameplate for minimum circuit ampacity, and maximum fuse or circuit breaker (HACR per NEC). Install power wiring and properly sized disconnect switch.
WARNING
Fire Hazard. Use of aluminum wire with this product may result in a fire, causing property damage, severe injury or death. Use copper wire only with this product.
WARNING
Failure to use properly sized wiring and circuit breaker may result in property damage. Size wiring and circuit breaker(s) per Product Specifications bulletin (EHB) and unit rating plate.
WARNING
ELECTROSTATIC DISCHARGE (ESD) Precautions and Procedures| Electrostatic discharge can affect electronic components. Take care during unit installation and service to protect the unit’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the unit, the control and the technician at the same electrostatic potential. Touch hand and all tools on an unpainted unit surface before performing any service procedure to neutralize electrostatic charge.
INSTALL THERMOSTAT
NOTE – 24VAC, Class II circuit connections are made in the control panel.
The following illustration provides an example of control wiring connections when using a standard thermostat.
ROUTING HIGH VOLTAGE, GROUND AND CONTROL WIRING
HIGH VOLTAGE / GROUND WIRES
Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring. To facilitate a conduit, a cutout is located in the bottom of the control panel. Connect conduit to the control panel using a proper conduit fitting.
TYPICAL CONTROL WIRING
Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit as illustrated.
A – Run 24VAC control wires through hole with grommet.
B – Make 24VAC thermostat wire connections to CMC1.
NOTE – Do not bundle any excess 24VAC control wires inside control panel.
NOTE – For proper voltages, select thermostat wire (control wires) gauge per table below.
WIRE RUN LENGTH AWG# INSULATION TYPE
LESS THAN 100′ (30 METERS) 18 TEMPERATURE RATING
MORE THAN 100′ (30 METERS) 16 35ºC MINIMUM.
IGH VOLTAGE FIELD WIRING
LOW VOLTAGE FIELD WIRING
FACTORY WIRING
NOTE – Wire tie provides low voltage wire strain relief and maintains separation of field-installed low and high voltage circuits.
STEP 5 – UNIT START-UP
IMPORTANT
If unit is equipped with a crankcase heater, it should be energized 24 hours before unit start-up to prevent compressor damage as a result of slugging.
- Rotate fan to check for binding.
- Inspect all factory- and field-installed wiring for loose connections.
- After evacuation is complete, open the liquid line and vapor line service valve stems to release the refrigerant charge (contained in outdoor unit) into the system.
- Replace the stem caps and tighten to the value listed in table 2.
- Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit’s nameplate. If not, do not start the equipment until you have consulted with the power company and the voltage condition has been corrected.
- Connect manifold gauge set for testing and charging.
- Set the thermostat for a cooling demand. Turn on power to the indoor indoor unit and close the outdoor unit disconnect switch to start the unit.
- Recheck voltage while the unit is running. Power must be within range shown on the unit nameplate.
- Check system for sufficient refrigerant using the procedures outlined under Checking Refrigerant Charge.
OPERATING MANIFOLD GAUGE SET AND SERVICE VALVES
The liquid and vapor line service valves are used for removing refrigerant,
flushing, leak testing, evacuating, checking charge and charging.
Each valve is equipped with a service port which has a factory-installed valve
stem. Figures 12 and 13 provide information on how to access and operate both
angle- and ball-type service valves.
Torque Requirements
When servicing or repairing heating, ventilating and air conditioning components, ensure the fasteners are appropriately tightened. Table 2 lists torque values for fasteners.
TABLE 2
TORQUE REQUIREMENTS
Parts | Recommended Torque |
---|---|
Service valve cap | 8 ft.-lb. |
Sheet-metal screws | 16 in.-lb. |
Machine screws #10 | 28 in.-lb. |
Compressor bolts | 90 in.-lb. |
Gauge port seal cap | 8 ft.-lb. |
IMPORTANT
To prevent stripping of the various caps used, the appropriately sized wrench should be used and fitted snugly over the cap before tightening.
Using Manifold Gauge Set
When checking the system charge, only use a manifold gauge set that features low loss anti-blow back fittings. Manifold gauge set used with HFC-410A refrigerant systems must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures of 0 – 800 psig on the high side and a low side of 30″ vacuum to 250 psig with dampened speed to 500 psi. Gauge hoses must be rated for use at up to 800 psig of pressure with a 4000 psig burst rating.
OPERATING BALL-TYPE SERVICE VALVE
- Remove stem cap with an appropriately sized wrench.
- Use an appropriately sized wrench to open. To open valve, rotate stem counterclockwise 90°. To close, rotate stem clockwise 90°.
OPERATING ANGLE-TYPE SERVICE VALVE
- Remove stem cap with an appropriately sized wrench.
- Use a service wrench with a hex-head extension (3/16″ for liquid line valve sizes and 5/16″ for vapor line valve sizes) to back the stem out counterclockwise as far as it will go.
When service valve is OPEN, the service port is open to line set, indoor and outdoor unit.
NOTE – A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
ACCESS SERVICE PORT
A service port cap protects the service port core from contamination and serves as the primary leak seal.
- Remove service port cap with an appropriately sized wrench.
- Connect gauge set to service port.
- When testing is completed, replace service port cap and tighten as follows: With torque wrench, finger tighten and torque cap per table 2. Without torque wrench, finger tighten and use an appropriately sized wrench to turn an additional 1/6 turn clockwise.
Reinstall Stem Cap
Stem cap protects the valve stem from damage and serves as the primary seal. Replace the stem cap and tighten as follows:
- With torque wrench, finger tighten and then torque cap per table 2.
- Without torque wrench, feigner and use an appropriately sized wrench to turn an additional 1/12 turn clockwise.
Checking Refrigerant Charge
The ML17XP1 unit is factory-charged with enough HFC410A refrigerant to accommodate a 15-foot length of refrigerant piping. Charge should be checked and adjusted using the tables provided on the charging procedure sticker on the unit access panel. Detailed information is given in the ML17XP1 Installation and Service Procedures manual, which is available on LennoxPros.com.
Defrost System
This section addresses:
- Emergency Heat
- Defrost System Overview
- Defrost Control Connections, Jumper Settings and Features
- Operational Mode Overview (Calibration, Normal and Defrost)
- Defrost Cycle Actuation
EMERGENCY HEAT (AMBER LIGHT)
An emergency heat function is designed into some room thermostats. This
feature is applicable when isolation of the outdoor unit is required, or when
auxiliary electric heat is staged by outdoor thermostats. When the room
thermostat is placed in the emergency heat position, the outdoor unit control
circuit is isolated from power and field-provided relays bypass the outdoor
thermostats. An amber indicating light simultaneously comes on to remind the
homeowner that he is operating in the emergency heat mode.
Emergency heat is usually used during an outdoor unit shutdown, but it should
also be used following a power outage if power has been off for over an hour
and the outdoor temperature is below 50°F (10°C). System should be left in the
emergency heat mode at least six hours to allow the crankcase heater
sufficient time to prevent compressor slugging.
DEFROST SYSTEM OVERVIEW
The control monitors ambient temperature, outdoor coil temperature, and total run time to determine when a defrost cycle is required. The coil temperature probe is designed with a spring clip to allow mounting to the outside coil tubing. The location of the coil sensor is important for proper defrost operation.
NOTE – The demand defrost control accurately measures the performance of the system as frost accumulates on the outdoor coil. This typically will translate into longer running time between defrost cycles as more frost accumulates on the outdoor coil before the demand defrost control initiates defrost cycles.
DEFROST CONTROL CONNECTIONS, JUMPER SETTINGS AND FEATURES
Defrost Temperature Termination Jumper Settings (P1)
The demand defrost control selections are: 50, 70, 90 and 100°F (10, 21, 32 and 38°C). The shunt termination pin is factory set at 50°F (10°C). If temperature shunt is not installed, default termination temperature is 90°F (32°C).
Test Pins (P1) Function
Placing the jumper on the field test pins (P1) allows the technician to:
- Clear short cycle lockout
- Clear five-strike fault lockout
- Cycle the unit in and out of defrost mode
- Place the unit in defrost mode to clear the coil
Compressor Delay Mode (P5)
The demand defrost control has a field-selectable function to reduce occasional sounds that may occur while the unit is cycling in and out of the defrost mode. When a jumper is installed on the DELAY pins, the compressor will be cycled off for 30 seconds going in and out of the defrost mode. Units are shipped with jumper installed on DELAY pins.
NOTE – The 30 second off cycle is NOT functional when jumping the TEST pins.
HIGH PRESSURE SWITCH (S4)
This unit is equipped with a high pressure switch which is located on the liquid line. The SPST, normally closed pressure switch opens when liquid line pressure rises above the factory setting of 590 + 15 psig and automatically resets at 418 + 15 psig.
LOW PRESSURE SWITCH (S87)
This unit is equipped with a low pressure switch which is located on the suction line. The SPST, normally open pressure switch opens when suction line pressure falls below the factory setting of 25 ± 5 psig and closes when pressure rises at 40 ± 5 psig.
DEMAND DEFROST CONTROL (A108) DIAGNOSTIC LEDS
The state (Off, On, Flashing) of two LEDs on the demand defrost control (DS1 [Red] and DS2 [Green]) indicate diagnostics conditions that are described in table 3.
TABLE 3
DEMAND DEFROST CONTROL (A108) DIAGNOSTIC LEDS
DS1 and DS2 System Status, Fault and Lockout Codes
DS2 Green| DS1 Red| Type| Condition/Code|
Possible Cause(s)| Solution
OFF| OFF| Status| Power problem| No power (24V) to demand defrost control
terminals R and C or demand defrost control failure.|
- Check control transformer power (24V).
- If power is available to demand defrost control and trol.
Simultaneous SLOW Flash| Status| Normal operation| Unit operating normally or
in standby mode.| None required.
Alternating SLOW Flash| Status| 5-minute anti-short cycle delay| Initial power
up, safety trip, end of room thermostat demand.| None required (jumper
TEST pins to override)
Simultaneous FAST Flash| Fault| Ambient Sensor Problem| Sensor being detected
open or shorted or out of temperature range. Demand defrost control will
revert to time/temperature defrost operation. (System will still heat or
cool).
Alternating FAST Flash| Fault| Coil Sensor Problem| Sensor being detected open
or shorted or out of temperature range. Demand defrost control will not
perform demand or time/temperature defrost operation. (System will still heat
or cool.)
ON| ON| Fault| Demand Defrost Control Failure| Indicates that demand defrost
control has internal component failure. Cycle 24VAC power to demand defrost
control. If code does not clear, replace demand defrost control.
OFF
|
SLOW
Flash
| Fault| Low Pressure Fault|
- Restricted air flow over indoor or outdoor coil.
- Improper refrigerant charge in system.
- Improper metering device installed or incorrect operation of metering device.
- Incorrect or improper sensor location or connection to system.
|
- Remove any blockages or restrictions from coils and/or fans. Check indoor and outdoor fan motor for proper current draws.
- Check system charge using sub cooling method.
- Check system operating pressures and compare to unit sub cooling tables in this instruction or located on unit access panel.
- Make sure all pressure switches and sensors have secure connections to system to prevent refrigerant leaks or errors in pressure and temperature measurements.
OFF
|
ON
|
Lockout
|
Low Pressure Lockout
SLOW Flash| OFF| Fault| High Pressure Fault
ON| OFF| Lockout| High Pressure Lockout
(Each fault adds 1 strike to that code’s counter; 5 strikes per code =
LOCKOUT)
Homeowners Information
CAUTION
Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch.
In order to ensure peak performance, your system must be properly maintained. Clogged filters and blocked airflow prevent your unit from operating at its most efficient level. The system should be inspected and serviced before each cooling and heating season by a licensed professional HVAC service technician (or equivalent).
Heat Pump Operation
Your new Lennox heat pump has several characteristics that you should be aware of:
- Heat pumps satisfy heating demand by delivering large amounts of warm air into the living space. This is quite different from gas- or oil-fired furnaces or an electric furnace which deliver lower volumes of considerably hotter air to heat the space.
- Do not be alarmed if you notice frost on the outdoor coil in the winter months. Frost develops on the outdoor coil during the heating cycle when temperatures are below 45ºF (7ºC). An electronic control activates a defrost cy cle lasting 5 to 15 minutes at preset intervals to clear the outdoor coil of the frost.
- During the defrost cycle, you may notice steam rising from the outdoor unit. This is a normal occurrence. The thermostat may engage auxiliary heat during the defrost cycle to satisfy a heating demand; however, the unit will return to normal operation at the conclusion of the defrost cycle.
Homeowner Maintenance
The following maintenance may be performed by the homeowner.
- Contact a licensed professional HVAC technician to schedule inspection and maintenance appointments for your equipment before each heating and cooling season.
- Check the indoor unit filter each month and replace the filter, if necessary.
- Have your Lennox dealer show you where your indoor unit filter is located. It will be either at the indoor unit (installed internal or external to the cabinet) or behind a return air grille in the wall or ceiling. Check the filter monthly and clean or replace it as needed. Disposable filters should be replaced with a filter of the same type and size.
- Check the indoor unit drain line for obstructions monthly. The indoor coil is equipped with a drain pan to collect condensate formed as your system removes humidity from the inside air. Have your dealer show you the location of the drain line and how to check for obstructions. (This would also apply to an auxiliary drain, if installed.)
- Check the area around the outdoor unit monthly and remove any obstructions that may restrict airflow to the outdoor unit. This would include grass clippings, leaves, or papers that may have settled around the unit.
- Trim shrubbery away from the unit and periodically check for debris which collects around the unit.
- During the winter months, keep the snow level below the louvered panels.
NOTE – The filter and all access panels must be in place any time the unit is in operation. If you are unsure about the filter required for your system, call your Lennox dealer for assistance.
IMPORTANT
Sprinklers and soaker hoses should not be installed where they could cause prolonged exposure to the outdoor unit by treated water. Prolonged exposure of the unit to treated water (i.e., sprinkler systems, soakers, waste water, etc.) will corrode the surface of the steel and aluminum parts, diminish performance and affect longevity of the unit.
Thermostat Operation
See the thermostat homeowner manual for instructions on how to operate your thermostat.
Pre-Service Check
If your system fails to operate, check the following before calling for service:
- Verify room thermostat settings are correct.
- Verify that all electrical disconnect switches are ON.
- Check for any blown fuses or tripped circuit breakers.
- Verify unit access panels are in place.
- Verify air filter is clean.
If service is needed, locate and write down the unit model number and have it handy before calling.
Extended Power Outage
The heat pump is equipped with a compressor crankcase heater which protects the compressor during cold weather operation.
If power to your unit has been interrupted for several hours or more, set the room thermostat selector to the EMERGENCY HEAT setting to obtain temporary heat without the risk of serious damage to the heat pump.
In EMERGENCY HEAT mode, all heating demand is satisfied by auxiliary heat; heat pump operation is locked out. After a six-hour compressor crankcase warm- up period, the thermostat can be switched to the HEAT setting and normal heat pump operation may resume.
Professional Maintenance
NOTICE !
Failure to follow instructions will cause damage to the unit.
This unit is equipped with an aluminum coil. Aluminum coils may be damaged by exposure to solutions with a pH below 5 or above 9. The aluminum coil should be cleaned using potable water at a moderate pressure (less than 50psi). If the coil cannot be cleaned using water alone, Lennox recommends use of a coil cleaner with a pH in the range of 5 to 9. The coil must be rinsed thoroughly after cleaning.
In coastal areas, the coil should be cleaned with potable water several times per year to avoid corrosive buildup (salt).
Your heating and air conditioning system should be inspected and maintained twice each year (before the start of the cooling and heating seasons) by a licensed professional HVAC technician. You can expect the technician to check the following items. These checks may only be conducted by a licensed professional HVAC technician.
Outdoor Unit
- Inspect component wiring for loose, worn or damaged connections. Also check for any rubbing or pinching of wires. Confirm proper voltage plus amperage of outdoor unit.
- Check the cleanliness of outdoor fan and blade condition (cracks) and clean or replace them, if necessary.
- Inspect base pan drains for debris and clean as necessary.
- Inspect the condition of refrigerant piping and confirm that pipes are not rubbing copper-tocopper. Also, check the condition of the insulation on the refrigerant lines. Repair, correct, or replace as necessary.
- Test capacitor. Replace as necessary.
- Inspect contactor contacts for pitting or burn marks. Replace as necessary.
- Check outdoor fan motor for worn bearings/ bushings. Replace as necessary.
- Inspect and clean outdoor coils, if necessary and note any damage to coils or signs of leakage.
Indoor Unit (Air Handler or Furnace)
- Inspect component wiring for loose, worn or damaged connections. Confirm proper voltage plus amperage of indoor unit.
- Inspect and clean or replace air filters in indoor unit.
- Check the cleanliness of indoor blower and clean blower, if necessary.
- Inspect the indoor coil drain pans and condensate drains for rust, debris, obstructions, leaks or cracks. Pour water in pans to confirm proper drainage from the pan through to the outlet of the pipe. Clean or replace as necessary.
- Inspect and clean indoor coil, if necessary.
- Inspect the condition of the refrigerant lines and confirm that pipes are not rubbing copper-tocopper. Also, ensure that refrigerant pipes are not being affected by indoor air contamination. Check condition of insulation on the refrigerant lines. Repair, correct, or replace as necessary.
- Inspect the duct system for leaks or other problems. Repair or replace as necessary.
- Check for bearing/bushing wear on indoor blower motor. Replace as necessary.
- If your heat pump is matched with a gas- or oil-fired furnace for auxiliary heating, indoor unit service will also include inspection and cleaning of the burners, and a full inspection of the gas valve, heat exchanger and flue (exhaust) system.
General System Test with System Operating
- Your technician should perform a general system test. He will turn on the air conditioner to check operating functions such as the startup and shutoff operation. He will also check for unusual noises or odors, and measure indoor/outdoor temperatures and system pressures as needed. He will check the refrigerant charge per the charging sticker information on the outdoor unit.
- Verify that system total static pressure and airflow settings are within specific operating parameters.
- Verify correct temperature drop across indoor coil.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>