SIEMENS FSD901-U2 Floor Repeater Display for Fire Detection System User Manual

June 9, 2024
SIEMENS

FSD901-U2/ FSD901-R2/ FSD901-U3/FSD901-R3
Floor Repeater Display
Product ManualSIEMENS FSD901-U2 Floor Repeater Display for Fire
Detection System -

Overview

The floor repeater display is an indication and operation unit in a fire detection system with the following functions:

Indication of events Operation
  • Alarm
  • Trouble
  • Supervisory
  • Status

|

  • Scrolling through lists
  • Reset
  • Acknowledge
  • Unsilence
  • Silence

The display on the floor repeater terminal is synchronized with the fire control panel and displays the same event texts.

Characteristic

  • Small floor repeater operating, and display panels applied in FC2005/FC901 fire detection system
  • Large backlight LCD display(160X64)
  • Communication with controller via RS485 (individual addressing)
  • Additional 24 VDC power supply necessary
  • In total, up to 8 FSD can be connected to a fire control panel
  • Access control by key
  • Flat, elegant housing

Function

  • Display of alarms, troubles, supervisory and status event
  • Same message layout as the fire control panel
  • With the navigation keys an indicated list in the display can be scrolled through
  • The internal buzzer can be switched off manually by pressing button “Acknowledge”
  • Reset events displayed on the FSD
  • Silence and unsilence

Application

SIEMENS FSD901-U2 Floor Repeater Display for Fire Detection System - Fig.1
Front view

No. Name Function
1. LCD Display of alarms, troubles, supervisory and status
2. Alarm Light up in case of fire
3. Four-way button For menu navigation
4. Power Light up when power supply is normal
5. Trouble Light up in case of trouble event
6. Ground Fault Light up in case of ground fault event
7. Silenced All activated silenceable devices are silenced
8. Supervisory Light up in case of supervisory event
9. Audibles on Light up when NAC or silenceable device is activated
10. Clear all events
11. Acknowledges unacknowledged events
12. All silenced devices are activated again
13. Silence all activated silenceable devices
14. Lock Set user access level by key

User Level

FSD floor repeater display control access right through lock on door. There are two user levels for access right:

User level Lock key position
L0
L1

The operation items for L0/L1 are listed as below:

Items L0 L1
View real time events
Acknowledge
Reset
Silence
Unsilence
Lamp test

Operation

Task Operation
View real time events 1. Press “↓” / “↑” to navigate a real time event.

2. Press “←” to return to first event.
Lamp test| Press both “Silence” and “Unsilence” button for 5s to do lamp test.
Acknowledge or reset events| Press “Acknowledge” or “RESET”.
Unsilence devices| Press “Unsilence”, all silenced devices are activated again.
Silence devices| Press “Silence”, silence all activated silenceable devices.

Address and Baud Rate
8-digit Dip-switch S1 is used for setting the FSD901 address and Baud Rate Setting.
The first 1-4 digits is for setting the FSD901 address 1-8, the 7-8 digits is for setting RS485 communication baud rate. The 5 and 6 digits are reserved for future use.

Address DIP switch
1 2
1 On
2 Off
3 On
4 Off
5 On
6 Off
7 On
8 Off
Baud Rate DIP switch
--- ---
7 8
9600 bps Off
19200 bps On
38400 bps Off
115200 bps On

FC2005 and FC901 can only support 19200 bps, other options reserve for future usage.

EOL Resistor
2-digit Dip-switch S20 is used for setting EOL resistor of RS485.

1 and 2 On:Internal EOL resistor is connected
1 and 2 Off:Internal EOL resistor is disconnected

For RS485 Class A, loop mode, no EOL resistor is needed.
For RS485 Class B, stub mode, internal EOL resistor of the repeater display at the end of RS485 must be connected.

Installation

SIEMENS FSD901-U2 Floor Repeater Display for Fire Detection System - Fig 2
DimensionSIEMENS FSD901-U2 Floor Repeater Display for Fire
Detection System - Fig 3 Connection

Note:

  • Point G is not used for any connection.
  • Power in from the non-resettable auxiliary power output on panel.

SIEMENS FSD901-U2 Floor Repeater Display for Fire Detection System - Fig
4

  1. Insert the loop line and external power wire through the floor repeater display.
  2. Mark the position for the 4 installation holes on flat wall (Fig. 2), drill the holes, put expansion bolts in and insert the screws leaving a small gap for hanging the display.
  3. Hang the floor repeater display over those screws through installation holes.
  4. Open the front panel (Fig. 4/5), tighten the screws and make sure the display is fixed firmly.
  5. Connect cables to terminals referring to the connection diagram (Fig. 3). Correctly set the internal 120Ω EOL resistor referring to the section “EOL Resistor”.
  6. Close the front panel.
    FSD connects to separate power supply, which needs to be UL Listed for Fire Safety Use and Power Limited.

Dimension (mm)

Technical data

Operating voltage 24 VDC nominal / 19…28 VDC
Operating current (quiescent) 60 mA
Activation current 70 mA
Operating temperature 0…+49 °C
Humidity ≤93% rel.
Communication protocol UFP (RS485-BUS)
Connection terminals 14-18 AWG
Color Black / Red
Operating location Indoor / dry

Details for ordering

Type Material No. Part No. Designation Weight
FSD901-U2 S54433-C102-A4 100935670 Desigo system display (black) 1.5 kg
FSD901-R2 S54433-C102-A3 101061934 Desigo system display (red) 1.5 kg
FSD901-U3 S54433-C102-A1 101061935 Cerberus system display (bl) 1.5 kg
FSD901-R3 S54433-C102-A2 100935673 Cerberus system display (red) 1.5 kg

Issued by
Siemens Industry, Inc.
Smart Infrastructure
8 Fernwood Road
Florham Park, NJ 08932
Tel. +1 973-593-2600
www.sbt.siemens.com/FIS
© Siemens Industry, Inc., 2019
Technical specifications and availability subject to change without notice
firealarmresources.com