LED annunciator
FT2008-U1/FT2008-R1/FT2009-U1/FT2009-R1
Installation Instruction
FT2008-U1 LED Annunciator
- For Canadian applications, the “FT2008-U1”/“FT2008-R1”/“FT2009-U1”/“FT2009-R1” are deemed supplementary and can be used for display only. It must be housed in a ULC-S527 approved, locked, enclosure.
- Not approved for UL/ULC MNS applications.
Intended use
The FT2008/FT2009 LED annunciator enables the fire detection system to be
displayed and operated in a simplified way. The FT2008 provides 2×16 LEDs to
display alarm/trouble events. The FT2009 provides 2×32 LEDs to display
alarm/trouble events. Both devices are operated on the UFP line.
This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:
- This device may not cause harmful interference.
- This device must accept any interference received, including interference that may cause undesired operation.
Package contents
The following are included in the scope of delivery:
- FT2008-U1/FT2008-R1 or FT2009-U1/FT2009-R1
- Cable ties (2 pcs)
- EOL jumper connecter (1 pcs)
Safety instructions
Risk of injury to persons and damage to property
Please observe the following safety instructions:
- The devices are only intended for stationary installation in dry rooms.
- The devices may only be connected to the UFP line.
- If panel AUX power is not used, an UL listed/recognized for fire use, regulated, power limited 24V DC power supply is required.
- Static discharge precautions should be taken when handling the FT2008/FT2009.
Legend
- Stub for mounting cover (2 pcs.)
- Shield terminal
- Earth ground terminal
- Mounting holes (8 pcs.)
- Cable tie point
- Breakout openings for cables (2 pcs.)
- Holes for hanging front panel over stub (2 pcs.)
- Dip-switch
- Screws (2 pcs.)
- EOL jumper
- Connection terminals for UFP line and power supply
- Front panel earth ground connection
Mounting instruction
- Break out the required cable openings (6) on the backbox.
- Mark the drilling points for the 3 mounting holes (4), drill the holes and insert the anchors (not supplied); or use the pre drilled mounting holes for installation on a 2 gang, or 4” square standard electrical box.
- Pull the cables for the UFP and power supply, through the breakout openings (6) on the backbox.
- Screw the backbox tightly in place.
- Connect the cable to the terminal (11) in accordance with the connection diagram.
- Configure Dip-switch (8) and EOL jumper (10).
- Connect the green earth ground cable from front panel (12) to backbox (3).
- Hook the front panel with the holes (7) over the stubs (1) on the backbox.
- Press the front panel down over the backbox, screw (9) upwards and fix the front panel in place.
Dip-switch
8-digit Dip-switch is used for setting address and baud rate.
The first 1-4 digits are for setting address, the 7-8 digits are for setting
UFP communication baud rate. The 5-6 digits are reserved for future use.
Add. | Dip-switch |
---|---|
1 | 2 |
1 | On |
2 | Off |
3 | On |
4 | Off |
5 | On |
6 | Off |
7 | On |
8 | Off |
Baud Rate | Dip-switch |
--- | --- |
7 | 8 |
9600 bps | Off |
19200 bps | On |
38400 bps | Off |
57600 bps | On |
Technical data
| FT2008| FT2009
---|---|---
Weight| 2.646 lb| 3.748 lb
Dimensions (W x H x D) (In: inch)| 8.110×7.362
x1.949| 11.417×7.362 x1.949
Storage temperature| 14…140 °F
Operating temperature| 32…120.2 °F
Humidity| 93`)/c. rel.
Housing| IP30
Operating voltage| 24V DC Nominal
18.8…27.2V DC
Operating current| 25 mA| 25 mA
Activation current| 65 mA| 105 mA
Issued by
Siemens Industry, Inc.
Building Technology Division
8 Fernwood Road
Florham Park, NJ 08932
Tel. +1 973-593-2600
www.sbt.siemens.com/FIS
@2016 Siemens Industry, Inc.
Technical specifications and availability subject to change without notice.
Doc No. A6V10456397_enUS_c
Edition 2016-06-16