CERBERUS PYROTRONICS MXL Advanced Protection System Owner’s Manual
- June 9, 2024
- CERBERUS PYROTRONICS
Table of Contents
MXL Advanced Protection System Owner’s Manual
ENGINEER AND ARCHITECT SPECIFICATIONS
- FirePrint™ Application Specific Detection
- Capacity for over 2,000 Intelligent Input Devices
- Dynamic Supervision of Intelligent Devices
- Security Device Monitoring
- Sprinkler Supervision
- Intelligent/Analog Detection Circuits, Style 6 (Class A) or Style 4 (Class B)
- Detector Sensitivity Readout/ Printout per NFPA 72 Chapter 7
- Style D (Class A) or Style B (Class B) Conventional Initiating Circuits
- Style Z (Class A) or Style Y (Class B) Notification Appliance Circuits
- Degrade Mode Operation
- Distributed Processing
- 80 Character Backlit Alphanumeric Display
- Thermal Strip Printer
- Supervised Remote Printer
- 32 Character Custom Messages
- Multiple Command Stations
- Compare System Software
- Fully Field Programmable Via Laptop Computer
- Menu Driven Operator Commands
- Central & Distributed Architecture
- ChronoLINK 800 Event History Logging With On Line & Off Line Reports
- User Help Screens
- Multiple Levels of Password Protection
- EnviroLINK — Automatic Environmental Compensation for Smoke Detectors
- One Person Walk Test by Zone or System
- Alarm Verification by Device or Zone
- Logic Controlled Output Functions
- Time Base Controlled Output Functions
- Holiday Schedule
- City Tie/Lease Line
- Coded Outputs
- Supervised Serial Annunciator Driver/Input Interface
- Interactive VDT – Monochrome & Color
- Color Graphics Option
- Complies with NFPA 72
- NEC 760 Power Limited Circuits (UL 864 Compliant)
- 16 Gauge Steel Enclosure
- Listed 864, 1076, ULC Listed
- FM, CSFM, NYMEA, City of Chicago and U.S. Coast Guard Approved
- Pre-action Releasing (NFPA 13)
- FM Approved for Sprinkler & Deluge
- FM Approved for Intrinsically Safe Applications
- Halon & FM-200 Releasing Approval (NFPA 12A & NFPA 2001)
- Multi-Language Display
- Intelligent Interface to Building Management Systems
- Operates as an Interactive Peer with Other MXLs, MXL-IQs or MXLVs in a LifeLink Network
- CXL Command Center Monitoring
- Pre-Alarm Operation
- FireFinder Graphics
Description
The MXL is a microprocessor based advanced protection system. Its use of
unique multiprocessor “Network” design along with its ability to utilize both
analog and conventional detection devices make it the most flexible and
reliable system in the life safety field. The MXL is ideally suited for
commercial, institutional and industrial fire, security and control
applications. It complies with the requirements of NFPA 72. It is UL 864 and
1076 security listed as well as FM, ULC, CSFM, City of Chicago, U.S. Coast
Guard and NYMEA approved. It is also UL listed for releasing per NFPA 12A, 13
and 2001 for FM-200, Halon, Pre-Action Sprinkler and Deluge.
The basic MXL control unit consists of the following subassemblies: MMB-2 Main
Control Board; MPS-6, MPS12 with MMB-2 Power Supply; MKB-2 Annunciator and
Key-board; MME-3, MLE-6 or MSE-2 Enclosures.
Optional modules which can be installed with the MXL System include: MOM-2/4
Expansion Card Cage; ALD-2I Analog Loop Driver; CRM-4 Controllable Relay
Module; NIM-1R Network Interface Module; REP-1 Network Repeater Module; XLD-1
“X” Series Loop Driver; CSM-4 Controllable Signal Module; CZM-4 Conventional
Zone Module; PIM-1 Peripheral Interface Module; CMI-300 CXL Modem Interface
Module; MOD-16 Output Driver; MOI-7 Network Interface; MID-16 Input Module;
PSR-1 Remote Supply; MPS-12 DC Supply; MXL-VDT Interactive Video Display
Terminal; NET-4 Style 4 Network Interface; NET-7 Style 7 Network Interface;
MXL-G Color Graphics; MXL-GT Color Terminal; a full range of “I and IL” Series
intelligent detectors and devices (see data sheets).
MMB-2 Main Control Board
The function control of the MXL is contained on the MMB-2 Main Control Board.
The MMB-2 controls, operates and monitors input device identity, network
communications as well as operator commands that are entered through the MKB
annunicator/keyboard. All operations are supported by either the MPS-6 or the
MPS-12 power supply, eliminating the need for external power supplies. The
MMB-2 is a direct replacement of the MMB-1 therefore providing total backward
compatibility.
The MMB-2 provides 2 ALD (Analog Loop Driver) circuits. Each ALD loop can be
configured as Style 4 (Class B) or Style 6 (Class A) and can monitor and
control up to 60 Cerberus Pyrotronics analog input devices and 60 programmable
device relays. The MMB-2 is equipped with 2 programmable and codable Style Y
(Class B) or Style Z (Class A) notification appliance circuits. Each circuit
can activate up to 1.5 amps of Cerberus Pyrotronics audible and visual
notification appliances.
The MMB-2 includes a built-in battery charger and transfer circuit. The
charger is microprocessor controlled and incorporates a brownout circuit that
switches the system to standby batteries during the loss and reduction of the
primary source AC. Upon command, the system is capable of displaying the real
time, battery voltage, AC voltage and the charge current and other power data
on the MKB alphanumeric display. It also has a 1 amp, 24 VDC output that
powers the CZM-1 modules. The MMB-2 is designed with a built-in mounting
bracket.
The MMB-2 mounts directly to the MBR-MP mounting plate for mounting in either
the MME-3 or MME-6 backbox enclosure. The MMB-2 can also be mounted in the
MBR-2 or MBR-1 enclosures. MBR-1 requires additional mounting brackets.
The on-board 16 bit microprocessor along with nonvolatile EPROM and Flash
memory allow the system to be custom configured to meet a wide range of
customer requirements. The MMB-2 provides a port for connection to a laptop
computer allowing for off-line field programming. Complete system
configuration can be easily uploaded, downloaded, edited and changes verified
using AccuLINK™ custom programming software with integrated Compare™ system
software. Program options include but are not limited to EnviroLINK™, smoke
detector environmental compensation with two maintenance alert levels,
ChronoLINK™ history logging, output control by event, check and change time
based control, detector sensitivity, alarm verification by device or zone, 32
character custom alphanumeric messages, system operation passwords and NAC
coding.
MKB-2 Annunciator/Keypad
The MKB-2 mounts on a hinged frame in the MXL enclosure and provides an 80
character backlit LCD alphanumeric annunciator which continuously scrolls to
display information concerning system status along with 32 character user
defined device messages. When multiple events occur, the MKB-2 displays the
last event of the highest priority. Additional data can be viewed by
depressing the NEXT key. At any time, the display scroll can be stopped by
depressing the HOLD button. Switches are provided for acknowledging fire
alarms, supervisories, security conditions, and system troubles. An individual
switch is also provided for silencing the system notification appliance
circuits. A separate switch is used for resetting the control panel.
A 10 digit numeric keypad is supplied to allow entry of the user passwords, as
well as perform specific menu driven operation, programming and maintenance
functions. Another series of switches located on the MKB-2 allows user access
to the TSP-40 Thermal Strip Printer, when used. A set of user assignable
“Function” keys provide single button access to a variety of system commands.
These switches may be used to perform system operation such as “Drill,” manual
relay control, zone disconnect, etc.
Contained on the MKB-2 annunciator are system status indicator LED’s which can
function even if the main system microprocessor fails. They provide indication
of Main Power On, Fire Alarm, Security Condition, System Trouble,
Supervisories, System Audibles Active/Silenced and Partial System Disable.
The MKB-2 Annunciator communicates with the MMB-2 Main Control Board through
the system network link.
MPS-6 Power Supply
The MPS-6 is a fully supervised power supply which provides the system with
primary DC power. It is rated at 6.5 Amps and is unfiltered and unregulated.
It supplies the MXL Control Unit and its expansion modules with power required
for normal operation. The unit incorporates a resettable circuit breaker on
the primary input and includes a built in AC line filter for surge and noise
suppression. The MPS-6 mounts in the MXL enclosure backbox.
MOM-4 Network Option Module Card Cage
The MOM-4 Card Cage provides the MXL Main Unit or Remote Units with card slots
for option modules. Each MOM-4 supplies connection space for either two full
width option modules (ALD-2I, CZM-4, NIM-1R, XLD-1) or four half width option
modules (CSM-4, CRM-4, CMI-300, NET7, REP-1) or a combination of one full and
two half width modules.
ALD-2I Analog Loop Driver
The ALD-2I is an MXL Network option module which supplies two intelligent
analog circuits utilizing Cerberus Pyrotronics “I” and “IL” type intelligent
devices. It occupies two addresses on the Network and through the use of a
unique communication protocol, devices connected to the ALD-2I circuits are
dynamically supervised by the MXL control panel. Up to 60 programmable input
and output devices may be connected to each of its two circuits. Each circuit
may be wired as Style 4 or Style 6.
CSM-4 Controllable Signal Module
The Controllable Signal Module CSM-4 provides two fully supervised,
programmable notification appliance circuits.
The CSM-4 supplies two Class B (Style Y) or Class A (Style Z) type output
circuits for the supervision and control of listed audible or visual
notification appliances such as horns, bells, strobes, etc. Each circuit can
provide up to 1.5 amps (24 VDC) of current to power notification appliances.
The CSM-4 is also used for extinguishing agent releasing (FM-200, Halon, Pre-
Action Sprinkler and Deluge systems). Leased line and municipal tie
connections are also possible with the CSM-4.
CRM-4 Controllable Relay Module
The Controllable Relay Module CRM-4 is designed to provide auxiliary control
of building functions such as door holder release, elevator capture, smoke
control, lock release, etc.
The CRM-4 plugs into one half slot in the MOM-2/4 expansion card cage. It
provides four fully programmable relays. Each relay contains one set of SPDT
contacts rated at 2 amps 30 VDC/120 VAC resistive.
CMI-300 CXL/MXL Interface Module
The CMI-300 is an MXL option module which provides modem communication between
an MXL and an CXL system. The CMI-300 plugs into any available 1/2 slot on a
MOM-2/4 card cage. This interface board translates signals between the MXL
network and a CXL and fully supervises signals.
NET-4 Communication Module
The NET-4 is a plug-in type module used to provide communication between the
Cerberus Pyrotronics MXL and various other MXL Remote Modules. It is designed
to plug into an edge connector type slot on the PSR-1 Network Supply. The
NET-4 provides NFPA Style 4 type communication. This communication is RS-485
operating at 19.2K Baud. The communication is fully digital. ****
NET-7 Style 7 Network Interface Card
The NET-7 is a microprocessor controlled MXL network interface module which
allows the wiring of the MXL RS485 network in an NFPA Style 7 configuration.
The NET-7 plugs into a half slot of the MOM-2/4 card cage at the MXL command
center (MMB-1) and the PSR-1 or MOM-4 slot at the MXL remote units (MXLR,
MXLRV). The NET-7 provides two independent and fully supervised communication
paths allowing system operation through an open as well as short circuit. It
also isolates the power supplies at each remote unit providing the ability to
localize ground fault conditions. The communication operates at 19.2K Baud and
is digital.
PSR-1 Remote Power Supply
The PSR-1 is a microprocessor controlled remote power supply and battery
charger for use with the Cerberus Pyrotronics MXL. It operates in conjunction
with either an MPS-6 or MPS-12 to provide 6 or 12 Amps of power for use with
various MXL modules. When used with a NET-4 or NET-7 plug-in communication
module, the PSR-1 becomes a part of the MXL’s RS-485 Network. It acts as an
interface between remote option modules and the MXL.
PIM-1 Interface Module
The PIM-1 is an MXL option module which provides a bidirectional isolated
RS-232 port for connection to peripheral devices such as printers, CRT’s,
VDT’s and Color Graphics. The PIM-1 mounts in the MXL Enclosure. It connects
to the MMB-2 and provides a screw terminal block for connection of RS-232. A
number of supervised and non-supervised formats are available.
MOI-7 Output/Input Module
The MOI-7 is an MXL RS-485 Network module which provides a fully programmable
serial interface to the MOD16 output drivers, MID-16 input drivers. When used
with the MOD-16’s, it provides a serial annunciator or relay driver. When used
with MID-16, it provides programmable inputs.
Each MOI-7 can operate up to eight MOD-16’s and eight MID-16’s simultaneously.
Each MOD-16 output and MID16 input is independently programmable via the MXL
custom software.
MOD-16 Output Driver
The MOD-16 is an output driver module used in conjunction with the MOI-7 as a
part of the Cerberus Pyrotronics MXL System. Up to eight (8) MOD-16s can be
connected to an MOI-7 interface module. Each MOD-16 provides 16 open collector
current sinking outputs rated at 24 VDC, 50mA. MOD-16 outputs are programmable
through the MXL custom software.
MID-16 Programmable Input Driver
The MID-16 is an input module used in conjunction with the MOI-7 as a part of
the Cerberus Pyrotronics MXL System. Up to eight MID-16s can be connected to a
single MOI-7 along with eight MOD-16 output driver modules. Each MID-16
provides a non-supervised input which can monitor contact devices. Each
individual MID-16 input can be separately used as a part of the MXL custom
programming logic. These inputs can be individually set for either Alarm,
Supervisory, Trouble, Security or Status usage. They can also be configured to
provide supervision for lamps driven by MOD-16 outputs. Screw terminals and
connectors are provided on the MID-16 modules for interface to monitored
devices.
MME-3 MXL/V Standard Size Enclosure
The MME-3 enclosure set consists of a sheetmetal backbox and door with
keylock. The MME-3 can be used for either the MXL System, MXLV Voice Command
Console, MXLR Transponder, MXLRV Voice Transponder or Amplifier Equipment
(using the MSR-1 Rail Kit). To mount MXL/MXLV modules in the MME-3, the MBR-MP
removeable module mounting plate is required. Using the MBR-MP mounting plate
(1) MMB or (1) PSR-1 and up to 3 expansion cardcages (MOM or OMM) can be
mounted in the MME-3 enclosure. When used to mount MXL amplifiers (EL-410),
the MBR-MP is not required, instead up to (3) EL-410 amplifiers may be
installed in the MME-3 by using (3) MSR1 rail kits. When amplifiers are
mounted in any enclosure always install MDG-1 grills in the door for proper
ventilation.
MME-3 is designed for surface of semi-flush mounting and includes various
knockouts for wire and conduit entry. The door in the MME-3 set has two
cutouts for either clear lenses, blank plates or grills depending on the
application, and contains a key lock.
MBR-MP MME-3 and MLE-6 MXL Module Mounting Plate
The MBR-MP MXL/V Module Mounting Plate is required for use in both MME-3 and
MLE-6 enclosures to mount all MXL and MXLV equipment. MBR-MP is not necessary
if the MME-3 and MLE-6 enclosures are to be used only for mounting of
amplifiers (EL-410).
The MBR-MP is a removeable MXL/V module mouting plate that allows the
enclosure MME-3 or MLE-6 to be shipped to the job site for installation of
wiring and conduit, while the system hardware (electronics) is mounted to the
studs on the MBR-MP, pre-wired, programmed and tested prior to delivery and
installation at the job site. This allows for quicker, more efficient system
start ups with less chance of the sensitive electronics being damaged while
field wiring and conduit are connected to the system enclosure.
MBR-MP mounting plate bolts to either the MME-3 or MLE6 enclosures for easy
installation on the job site. The MBRMP also has handles to allow easy
transport and mounting. The MBR-MP contains mounting studs for (1) MMB or
PSR1, (1) PIM-1, (1) TBM-1, and up to (3) MOM or OMM cardcages or 2 cardcages
and (1) TSP-40 Printer (same mounting studs as the MBR-2 enclosures).
The MBR-MP is ordered and shipped seperately from the MME-3 and MLE-6
enclosures.
MLE-6 MXL/V Large Size Enclosure
The MLE-6 enclosure set consists of a sheetmetal backbox and door with two key
locks. The MLE-6 can be used for either the MXL system, MXLV Voice Command
Console, MXLR Transponder, MXLRV Voice Transponder or Amplifier Equipment
(using the MSR-1 rail kit). To mount MXL/V modules in the MLE-6, the MBR-MP
removeable module mounting plate is required with the MBR-3MP optionally
available for use. Using the MBR-MP mounting plate (1) MMB or PSR-1 and up to
(3) expansion cardcages (MOM or OMM) can be mounted in the MLE-6. If
additional cardcages are required, the MBR-3MP optional cardcage mounting
plate can also be installed in the MLE-6 below the MBR-MP. The MBR-3MP allows
mounting of an additional (3) MOM or OMM module expansion cardcages.
Various combinations of hardware can be installed in the MLE-6. If only
amplifiers are to be installed in the MLE-6, no MBR-MP or MBR-3MP plates are
required. Instead up to (5) EL-410 amplifiers can be installed by using (5)
MSR-1 rail kits. The MLE-6 can also be used to mount up to (3) MXL cardcages
and (2) amplifiers. This configuration would be typical of a remote voice
transponder cabinet. In this configuration (1) MBR-MP would be used in the
upper half of the MLE-6 to mount the MXL modules, while the lower half would
use (2) MSR-1 rail kits to mount up to (2) EL-410 amplifiers.
The MLE-6 is designed for surface or semi-flush mounting and includes various
knockouts for wire and conduit entry. The door supplied with the MLE-6 set has
(3) cutouts for either clear lenses, blank plates or grills, depending on the
application. The door also contains (2) key locks — keyed the same. Various
combinations of dead front mounting plates are possible with the MLE-6
enclosure. A typical MXLV installation would have (1) MKB-2 at the top, and
(2) MHD-3 dead front plates in the middle (for (14) VSM/VLM/ VFM modules per
plate) and (1) or (2) MHD-2 lower dead front plates.
MBR-3MP MLE-6 Optional Cardcage Mounting Plate
The MBR-3MP is an optional MXL/MXLV cardcage mounting plate for use
exclusively in the MLE-6 enclosure.
When installed in the MLE-6 backbox, the MBR-3MP adds the option of mounting
up to an additional (3) MOM or OMM expansion cardcages.
MDL-1 Clear Lens
The MDL-1 is a clear Plexiglas® lens which fits in either one of the two
openings in the MME-3 enclosure door or in one of the three openings in the
MLE-6 enclosure door. One lens is included in the MDL-1 package.
MDB-1 Sheet Metal Blank Plate
The MDB-1 is a sheet metal blank plate which fits in either one of the two
openings in the MME-3 enclosure door or in one of the three openings in the
MLE-6 enclosure door. One blank plate is in the MDB-1 package.
MHD-1 Upper or Middle Dead Front Panel
The MHD-1 is a hinged sheet metal panel which attaches to either the MME-3 or
the MLE-6 enclosure backbox. It fits in either the upper or the middle section
of the MME-3 backbox or the upper or either of the two middle sections of the
MLE-6 backbox. It has an opening with a cover plate for the TSP-40 printer
when used and attaches to the backboxes with screw fasteners. When in place
it covers and protects modules and wiring, providing dead front construction
in that area.
MHD-2 Lower Dead Front Panel
The MHD-2 is a hinged sheet metal panel which attaches to either the MME-3 or
the MLE-6 backboxes. It mounts in the lower section on the MME-3 and on the
lower two sections of the MLE-6 backbox. It has no openings and attaches to
the enclosures with screw fasteners. When in place, it covers and protects
modules and wiring, providing dead front construction in that area.
MHD-3 Middle Dead Front Plate for Mounting Switch/LED/Fan Control Modules
The MHD-3 is a hinged sheet metal panel that attaches to the MME-3 or MLE-6
backboxes. It fits in either the middle or the upper sections of these
enclosures. It has openings for two rows of VSM-1 Switch Modules, VLM-1 LED
Annunciator Modules, VFM-1 Fan Control Modules or VSB-1 Blank PLates. Each row
can mount up to (7) modules for a total of (14) modules per MHD-3. The MHD-3
attaches to the backboxes with screw fasteners. It is hinged for easy access
to the rear of the modules and inside of the enclosure.
MHD-4 Middle Dead Front Plate for the Switch/LED/ Fan control Modules with
Printer Cutout
The MHD-4 is a hinged sheet metal panel that attaches to the MME-3 or the
MLE-6 backboxes. It fits in the middle section of both enclosures. It has two
rows for mounting of VSM-1 Switch Modules, VLM-1 LED Annunciator Modules,
VFM-1 Fan Control Modules or VSB-1 Blank Modules. Each row has space to mount
(4) modules, for a total of (8) modules per MHD-4. The MHD-4 also has a cutout
to display the TSP-40 Internal Thermal Strip Printer. The MHD4 mounts to the
backboxes with screw fasteners. It is hinged for easy access to the rear of
the modules and inside of the enclosure. When in place, it covers and protects
modules and wiring, providing dead front construction in that area.
MSR-1 Rail Kit
The MSR-1 is a System 3 type rail kit which fits into either the MME-3 or the
MLE-6 enclosures. The MSR-1 comes with a U-bracket and a Z-bracket. It allows
modules such as the EL-410 amplifier, PS-35 Power Supply, BC-35 Battery
Charger, MOI-7 I/O Interface, MID-16, MOD-16, PS-5A, SYS3-MPFO for mounting
the D2300CP fiber optic interface modules or the CCU interface, or any other
System 3 type module required to be mounted in the MME-3 or the MLE-6
enclosures.
When used in the MME-3 enclosure (3) MSR-1 Rail Kits can be installed to mount
up to three rows for up to (3) EL-410 amplifiers. When used in the MLE-6, up
to (5) MSR-1 Rail Kit rows can be installed to allow mounting up to (5) EL-410
amplifiers. When the MLE-6 enclosure is used with the MBR-MP mounting plate to
install MXL or MXLV equipment, up to (2) MSR-1 Rail Kit rows can also be
installed in the MLE-6 for mounting of either (2) EL-410 amplifiers or some
complement of System 3 type mount modules.
MXL-VDT Interactive Video Display Terminal
The MXL-VDT is a 14” amber monitor with detachable keyboard. It provides an
interactive terminal for secondary display of MXL information, and operation
of MXL functions such as Acknowledge, Silence and Reset, as well as arming and
disarming devices. It also provides a means for generating system reports such
as listing smoke detector sensitivity settings and voltages, battery and power
supply voltages and current, and displaying the ChronoLINK event log. A
printer may be connected to the MXL-VDT.
MXL-G Color Graphics
MXL-G is a PC based color graphics display package designed for use with the
Cerberus Pyrotronics MXL system. It is used to monitor alarms, supervisories,
troubles and security violations as detected by the MXL. Up to 10 levels of
zoom screens can be associated with each device. It also acts as a fully
interactive operator terminal with disk based event logging. PC ordered
separately.
MXL-GT Color Interactive Terminal with History Reporting
MXL-GT is a PC based color terminal for use with the Cerberus Pyrotronics MXL
system. It consists of a serial interface module and software which allow a
standard PC to act as a fully interactive secondary operator terminal as well
as providing a comprehensive disk based event logging. PC ordered separately.
TSP-40 Thermal Strip Printer
The TSP-40 is a thermal strip printer designed for use with the Cerberus
Pyrotronics MXL system. It mounts in the MXL enclosure and its printout is
visible through a window in the locked enclosure door. Printouts are
automatically spooled on a take-up reel for easy record storage.
RCC-1 Remote Command Console
The RCC-1 is a remotely located MXL annunciator display module. The RCC-1
contains an 80 character LCD display and control keypad (MKB) and a PS-5N7
network interface. RCC-1s can be located anywhere that control or
annunciation is required. RCC-1 can be programmed for display only or can
provide display and system control. If a PIM-1 is added to the RCC-1, remote
printers, VDT, or graphics computers can be located throughout a facility.
MPS-12 Power Supply
The MPS-12 is a fully supervised power supply which provides the system with
preliminary DC power. It is rated at 12 amp. and is unfiltered and
unregulated. It supplies the PSR-1 and its expansion modules with power
required for normal operation. The unit incorporates a resettable circuit
breaker on the primary input and includes a built-in AC line filter for surge
and noise suppression. The MPS-12 mounts in the MXL enclosure backbox.
PIM-2 Parallel Printer Interface
The PIM-2 is an MXL or CXL parallel printer interface module. PIM-2 connects
to PIM-1 to allow MXL connection and supervision of any EDP UL listed printer.
PAL-1 UL Listed Parallel Printer
The PAL-1 is a UL listed supervised parallel system printer for MXL or CXL.
The PAL-1 connects to the PIM-2 and PIM1 to provide MXL with a UL listed
parallel printer that is supervised.
MSE-2 MXL Small Enclosure
The MSE-2 is a small MXL enclosure capable of housing an MMB-1 or PSR-1 and
MPS-6 or MPS-12. When expansion is required the MSE-2 provides for mounting of
either one (1) MOM-2 or OMM-2. MSE-2 is part of the MXL-SS and MXLV-SS
packages.
ICP Intelligent Control Point
The ICP is a field mounted output module capable of being programmed to be
either a remote bell or horn, speaker or telephone zone. The ICP communicates
with the MXL via the ALD loop.
LIM-1 Line Isolator Module
The LIM-1 is a short circuit isolator module for use on the MXL’s analog
loops. The LIM-1 is capable of providing Style 4 or Style 6 wiring of ALD
loops. Multiple short circuit isolators can be used on a single ALD loop to
prevent loss of protection in the event of a short circuit.
MOM-2 Network Option Module Card Cage
The MOM-2 provides the MXL main unit, remote units or MXL small enclosures
(MSE-2) with card slots for optional modules. Each MOM-2 provides space for
one full- width (ALD-2I, CZM-4, NIM-1R) or two half-width optional modules
(CSM-4, CRM-4, CMI-300, NET-7, REP-1).
PS-5N7 5 Volt Power Supply/Network Interface
The PS-5N7 is a 5V power supply and MXL local network interface module. The
PS-5N7 is an integral part of the RCC-1. The PS-5N7 can be used to provide a
Style 4 or Style 7 network interface for either a remote transponder for MXLV
with either TBM-2, ACM-1 and VSM-1/VLM-1/ VFM-1 or to drive OMM-1 and
associated MXLV cards.
FireFinder NCC-G — Network Color Graphics
FireFinder is a PC based color graphics display and control package designed
for use with the LifeLINK network and provides full control and annunciation
for a LifeLINK network of up to 63 MXL-IQ or MXL systems. The NCC-G is used
to monitor and control alarms, troubles, security, supervisory and all system
events from one of many MXL series systems. The NCC-G maintains an extensive
history log of all system events and has extensive report generation
capabilities. User programmable function buttons are programmable to allow
site specific control function configuration. Multiple NCC-Gs may be connected
to a LifeLINK network. PC ordered separately.
NIM-1R Network Interface Module
The NIM-1R is a full sized slot MXL module that allows the interconnection or
networking of up to 63 MXL systems.
The NIM-1R provides an RS-485 communication path in either Style 4 or Style 7
wiring configurations. The NIM-1R allows MXLs to have interpanel logic and
communicate in a peer to peer fashion. The NIM-1R can be programmed via CSGM
logic as an FSI (Foreign System Interface) to communicate with external
building control and annunciation systems.
CCU/M Alphanumeric Pager Interface
The CCU/M is a ancillary module that connects to the PIM1 to transmit MXL
status information in text message format to an alphanumeric pocket pager. The
CCU/M can be connected to an existing phone line and can dial out to a pager
using its onboard modem to transmit information via a paging service. The
CCU/M can also connect directly to an existing on-site paging system. Through
programming the CCU/M can send different types of events to different pagers.
Up to 8 different messages can be sent to pagers directly from the CCU/M.
Alarms, Troubles, Supervisory, Security, Arm/Disarm, Status Points, Audible
Status, and Reset can be directed to all or only certain alphanumeric pocket
pagers.
REP-1 Network Repeater Module
The REP-1 is a 1/2 slot MXL network module that provides the ability to
configure the MXL’s local or global networks in a star or daisy chain
configuration. The REP-1 provides two Style 4 or one Style 7 RS-485 network
circuits. Through the use of the REP-1, the MXL’s local network (MXL-MXLR) can
be expanded up to 64 nodes.
MMB-2
Electrical Specifications for Analog Loop Devices
-
Electrical Ratings:
Supervisory: 24VDC peak, 30mA max.
Alarm: 24 VDC peak, 30mA max. (60 devices in alarm) -
All wiring must be in accordance with Article 760 of NEC or local building codes.
-
Only Cerberus Pyrotronics devices may be used. (See
Table 1) A maximum of 60 devices in any combination may be connected to a single analog loop. -
No end of line device required.
-
Both circuits are power limited to NFPA 70/NEC. Each detector or group of detectors, requires a two wire circuit of minimum 18 AWG thermoplastic fixture wire enclosed in a conduit or minimum 18 AWG limited energy shielded cable without conduit, if permitted by local codes.
-
Total circuit resistance must not exceed 100 ohms.
Maximum capacitance:
0.4µF between + loop and – loop
0.8µF between + loop and chassis
0.8µF between – loop and chassis -
T-tapping is not allowed on Class A loops
MMB-2 AUX Power
- AUX power is available on TB5 terminals 9-12
- All wiring must be in accordance with Article 760 of NEC or local building codes.
- AUX power is power limited to NFPA 70/NEC 760.
- Electrical Ratings: 18-31 VDC, 1A max.
MMB-2 Notification Appliance Circuits (TB5, 1-4 and TB5, 5-8)
- These notification appliance circuits are for alarm notification appliances only (NFPA 72 Local). For Municipal tie (NFPA 72, Chapter 4 ) or Leased Line (NFPA 72 Chapter 4), use model CSM-4.
- All wiring must be in accordance with Article 760 of NEC or local building codes.
- Both notification appliance circuits are power limited to NFPA 70/NEC 760.
- Electrical Ratings: Supervisory 18-31 VDC, 12mA max Alarm 18-31 VDC, 1.5A max.
- End of Line Device: EOL 2.2K, 1/2W (P/N 140-820380)
- Line Resistance: Not to exceed 3 ohms max
MXL Compatible Analog/Intelligent Devices
Model | Description | Installation Instructions |
---|---|---|
CZM-1 | Conventional Zone Module | 315-090725 |
ILI-1/1H/1A/1AH | Intelligent Ion Detectors | 315-092724 |
ILP-1/IPLT-1 | Intelligent Photo Detectors | 315-092594 |
ILT-1 | Intelligent Heat Detectors | 315-093336 |
ILI-1B/1BH | Intelligent Ion High Vel. | 315-093234 |
ILP-2 | ipreePcirct Tpmetpcptiloicnation | 315-095028 |
MS1-10B/2013 | Intelligent Manual Station | 315-093329 |
MS-MI | littaetl!igi nent Metal Manual | 315-092169 |
TRI-B6/B6D/B6R | Intelligent Monitor Module (single/dual and with relay) |
315-093315
TRI-B6M| Intelligent Mini-Monitoring Module| 315-094547
ICP| Intelligent Control Point| 315-092471
LIM-1| Line Isolator Module| 315-092135
Cerberus Pyrotronics
8 Ridgedale Avenue
Cedar Knolls, NJ 07927
Tel:201-267-1300
FAX: 201-397-7008
Website: www.cerbpyro.com
4/97 10M CPY-IG
Printed in U.S.A.
Cerberus Pyrotronics
50 East Pearce Street
Richmond Hill, Ontario
L4B, 1B7 CN
Tel:905-764-8384
FAX:905-731-9182
April 1997
Supersedes sheet dated 1/95
firealarmresources.com