CERBERUS PYROTRONICS Lever Actuated Control Head Owner’s Manual

June 9, 2024
CERBERUS PYROTRONICS

Lever Actuated Control Head
Owner’s Manual

ENGINEER AND ARCHITECT SPECIFICATIONS

Model LAH Features:

  • Used for Manual Actuation of Cylinder
  • Comes Equipped with Safety Pull-Pin, to Prevent accidental Manual Discharge of FM-200TM Cylinder
  • Self-Venting
  • Solid Brass Construction
  • Stainless Steel Lever
  • Listed and FM Approved

Introduction

Model LAH, the Lever Actuated Head is equipped with an operating lever, for manual actuation of Ceberus Pyrotronics FM-200™ cylinders. The LAH is secured in a closed  position by a safety pull-pin. When the safety pull-pin is removed, the lever can be manually rotated to the open position. When the lever is in the open position, it allows for  the activating of the cylinder or valve on which it is installed.
The lever operated control head is self-venting to prevent accidental system discharge in the event of a slow buildup of pressure in a pilot line.
Ensure that the control head is in the “SET” position, with the safety pull- pin and seal wire intact. Next, remove the protection cap from the cylinder or stop valve actuation port. Using a suitable wrench, assemble the control head to the cylinder valve. Finally, tighten the swivel nut securely.

Ordering Information

Model No Description Part No.
LAH Lever Actuated Control Head 500-870652

Mounting Data

Cerberus Pyrotronics
8 Ridgedale Avenue
Cedar Knolls, NJ 07927
Tel:201-267-1300
FAX:201-397-7008
11/96 1M CPY-IG
Printed in U.S.A.
Cerberus Pyrotronics
50 East Pearce Street
Richmond Hill, Ontario
L4B, 1B7 CN
Tel:905-764-8384
FAX:905-731-9182
November 1996

Supersedes sheet dated 10/95