FN-LCD-N – LCD NETWORK ANNUNCIATOR
DESCRIPTION
The FN-LCD-N type LCD network annunciator is designed to be used with the
FireNET analog addressable system. It allows for remote access, monitoring &
control of the FireNET system throughout the building.
The FN-LCD-N is a true network annunciator that can access, monitor & control
any or all FireNET panels in the network. Each FN-LCD-N is completely
independent. The highly intuitive user interface and 320 character LCD display
of the FN-LCD-N is exactly the same as the FireNET panel. In addition to
routing any panel in the network to the FN-LCD-N, every event category within
each panel can also be individually routed, as well as routing of all remote
control functions (reset, alarm silence, re-sound alarm) from individual
panels. The FN-LCD-N supports the same RS485 expansion port as the FireNET
panel, allowing for FireNET expansion boards and accessories to be connected
to the network annunciator.
The FN-LCD-N also has (4) output relays for fire, supervisory, trouble &
auxiliary. The relays are programmable (except supervisory). Security is
established by the use of a password or firefighters enable key. Designed to
be aesthetically pleasing, the FN-LCD-N is available in charcoal grey or red
and can be surface or flush mounted using a standard trim ring kit.
Specifications subject to change without notice.
STANDARD FEATURES
- UL 864 9th edition Listed
- 320 character liquid crystal display (8 line x 40 character)
- LED indicators for Fire, Supervisory Alarm, PreAlarm, Fire Output Active, Power On, On Test, Panel Sounder Silenced, Delay Active, More Events, Point Bypassed, General Trouble, Power Trouble, System Trouble & NAC Trouble
- Dual RS485 ports for primary fire network
- RS485 slave bus for expansion – up to 31 FN-4127-IO boards or up to 15 FN-LCD-S serial annunciators and up to16 FN-4127-IO boards
- 2 built-in RS-232 interfaces for programming via a PC and serial printer interface
- 4 on board programmable Form C relays rated at 1 Amp at 30VDC (Fire, Supervisory, Trouble & Auxiliary)
- Same controls as the FireNET fire panel (Reset, Panel Sounder Silence, Lamp Test, Alarm Silence, Re-sound Alarm, Fire Drill, Programmable Function, More Events, More Fire Events, Enter & Exit)
- Local piezo sounder for event notification
- Supports user codes & firefighter key to enable access & controls
- Powered by FireNET Aux 24VDC or UL fire listed Aux. 24VDC supply
- Available in red or charcoal, and can be surface or flush mounted (using trim ring)
- True network annunciator, any or all panels can be routed to the FN-LCD-N. In addition, each event category can be individually routed to the FN-LCD-N
- Up to (64) FireNET panels & FN-LCD-N’s can be networked together in any combination
- 500mA of auxiliary power available rated at 24VDC
- Auto-learn feature
- Built-in help & alarm information screens
- Fire drill function
- Each FN-LCD-N is completely independent
- Supports up to (31) FN-4127-IO boards on RS485 expansion port
- The FN-LCD-N can be configured to remote reset, silence, resound, any or all panels on the network in any combination
SPECIFICATIONS
Input DC | 24VDC @ 270mA Max. ( + Aux. Power Load) |
---|---|
Aux. Output DC | 24VDC @ 500mA |
Dimensions | 14.5″ W x 10″ H x 3.3″ D |
Weight | 9.4 lbs |
Color | Red (optional charcoal) |
Material | ABS/steel enclosure |
Display | 8 line x 40 character LCD (320 characters total) |
Network | Dual RS485 ports (64 nodes max.) |
Relay Outputs | (4) Form C 1amp@30VDC |
PC Port | RS232 |
Printer Port | RS232 |
Expansion Port | RS485 (for optional expansion boards) |
ENGINEERING SPECIFICATION
The contractor shall furnish and install where indicated on the plans, the
network annunciator model FN-LCD-N.
The FN-LCD-N shall connect to the FireNET fire alarm control panel (FACP)
network. The network annunciator shall be capable of annunciating on its 320
character display and local buzzer, the condition of any FireNET FACP or
network annunciator on the network. Up to 64 FN-LCD-N network annunciators or
FireNET FACP’s may be connected together on the network. The FN-LCD-N shall be
UL listed, and have surface or flush mount capability.
WIRING DIAGRAM
Hochiki America Corporation
7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246
Fax: 714/522-2268
Technical Support: 800/845-6692 or
technicalsupport@hochiki.com
Find latest revision at www.hochiki.com
F0071 02/2007
Hochiki America Corporation FN-LCD-N
Specifications subject to change without notice.
firealarmresources.com
Documents / Resources
|
HOCHIKI FN-LCD-N LCD Network
Annunciator
[pdf] Owner's Manual
FN-LCD-N LCD Network Annunciator, FN-LCD-N, LCD Network Annunciator, Network
Annunciator, Annunciator
---|---
|
HOCHIKI FN-LCD-N LCD Network
Annunciator
[pdf] Instructions
FN-LCD-N LCD Network Annunciator, FN-LCD-N, LCD Network Annunciator, Network
Annunciator, Annunciator
References
- Fire Alarm Resources | Download fire alarm documents
- Hochiki | Fire Protection Equipment and Systems
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>