Honeywell SDF505-ADH Addressable Duct Detector Housing Instructions

June 9, 2024
Honeywell

Honeywell logoHoneywell SD500-LED LED Driver Module logo
1 **SDF505-ADH Addressable Duct Detector Housing
InstructionsHoneywell SDF505-ADH Addressable Duct Detector
Housing
SD505-ADH Shown with Detector (Detector Sold Separately)**

Honeywell SDF505-ADH Addressable Duct Detector Housing - icon
1 Use with SD505-APS photoelectric and SD505-AIS ionization detectors

SDF505-ADH Addressable Duct Detector Housing

SD505-ADH
Analog Duct Detector Housing
The SD505-ADH analog addressable duct smoke detector detects smoke and products of combustion present in air moving through an HVAC air handling system. The SD505-ADH is a heavy duty metal housing with a pre-installed detector base, compatible with the SD505-APS Photoelectric smoke detector and the SD505-AIS Ionization Smoke Detector.
When smoke is detected in a duct, the unit communicates the condition to the fire alarm control panel. The panel can be programmed to turn fans, blowers, and other devices off or on.

Features

  • Two-wire connection to SLC LED alarm indication and communication on sensor head
  • Rugged steel backbox with clear plastic cover
  • Installation template included
  • Large terminal connection screws
  • Interchangeable “plug-in” photoelectric or ionization heads
  • UL listed, complies with NFPA 72 and 101
  • CSFM listed
  • MEA Approved 429-92-E, Vol 9
  • FM Approved

Specifications

Included Parts:| Metal housing with 7.5″ exhaust tube
SD505-4AB detector base
Installation template
4 mounting screws
---|---
Accessory model numbers:| SD505-APS Photoelectric Smoke Detector
SD505-AIS Ionization Smoke Detector
(parts not included with SD505-ADH)| SD500-ARM Relay Module
STS-2.5 Sampling tube for 6 to 2.5 duct width
STS-5.0 Sampling tube for 2.5 to 5.0 duct width
SDS-10.1 Sampling tube for 5.0 to 10.0 duct width
Current:| .55 mA (alarm and standby)
Air Velocity:| 500-4000 fpm (SD505-APS)
300-4000 fpm (SD505-AIS)
Sensitivity:| 1.1 (SD505-APS) % obs
0.8 (SD505-AIS) % obs
Ambient Temperature:| 32ºF to 100ºF
(0ºC to 37ºC)
Humidity:| 10 to 85% RH
Dimensions:| 10 H x 8.25 W x 2.25 D
Color:| Gray

Compatible Control Panels

IFP-1000
IFP-100

Dimensions

Honeywell SDF505-ADH Addressable Duct Detector Housing - fig
1

****7550 Meridian Circle, Maple Grove, MN 55369-4927
1-800-446-6444 or in Minnesota 763-493-6435
FAX: 763-493-6475 World Wide
Web: http://www.farenhyt.com
P/N 350217, 11/01
Copyright © 2001 Silent Knight
firealarmresources.com
Made in the U.S.A.