POTTER PS10 Series Pressure Type Waterflow Switch Owner’s Manual
- June 9, 2024
- POTTER
Table of Contents
- Installation
- Wiring Instructions
- Wet System
- Dry System
- Dimensions
- Switch Clamping Plate Terminal
- Typical Sprinkler Applications
- Low Pressure Signal Connection
- Waterflow Signal Connection
- Local Bell For Waterflow Connection
- One Conduit Wiring
- Switch Operation
- Removing Knockouts
- Ordering Information
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
POTTER PS10 Series Pressure Type Waterflow Switch Owner's Manual
Installation
The Potter PS10 Series Pressure Actuated Switches are designed for the detection of a waterflow condition in automatic fire sprinkler systems of particular designs such as wet pipe systems with alarm check valves, dry pipe, preaction, or deluge valves. The PS10 is also suitable to provide a low pressure supervisory signal; adjustable between 0,27 and 1,03 BAR (4 and 15PSI).
- Apply Teflon tape to the threaded male connection on the device. (Do not use pipe dope)
- Device should be mounted in the upright position (threaded connection down).
- Tighten the device using a wrench on the flats on the device.
Wiring Instructions
- Remove the tamper resistant screw with the special key provided.
- Carefully place a screwdriver on the edge of the knockout and sharply apply a force sufficient to dislodge the knockout plug. See Fig 9
- Run wires through an approved conduit connector and affix the connector to the device.
- Connect the wires to the appropriate terminal connections for the service intended. See Figures 2,4,5, and 6. See Fig 7 for two switch, one conduit wiring.
Testing: The operation of the pressure alarm switch should be tested upon completion of installation and periodically thereafter in accordance with the applicable NFPA codes and standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently).
Wet System
METHOD 1: When using PS10 and control unit with retard – connect PS10 into alarm port piping on the input side of retard chamber and electrically connect PS10 to control unit that provides a retard to compensate for surges.
Insure that no unsupervised shut-off valves are present between the alarm
check valve and PS10.
METHOD 2: When using the PS10 for local bell application or with a control
that does not provide a retard feature – the PS10 must be installed on the
alarm outlet side of the retard chamber of the sprinkler system.
TESTING: Accomplished by opening the inspector’s end-of-line test valve. Allow
time to compensate for system or control retard. NOTE: Method 2 is not
applicable for remote station service use, if there is an unsupervised shut-
off valve between the alarm check valve and the PS10.
Wet System With Excess Pressure Connect PS10A into alarm port piping
extending from alarm check valve. Retard provisions are not required. Insure
that no unsupervised shut-off valves are present between the alarm check valve
and the PS10.
TESTING: Accomplished by opening the water by-pass test valve or the
inspector’s end-of-line test valve. When using end-of-line test, allow time
for excess pressure to bleed off.
Dry System
Connect PS10 into alarm port piping that extends from the intermediate chamber
of the alarm check valve. Install on the outlet side of the in-line check
valve of the alarm port piping. Insure that no unsupervised shut-off valves
are present between the alarm check valve and the PS10.
TESTING: Accomplished by opening the water by-pass test valve.
Note: The above tests may also activate any other circuit closer or water
motor gongs that are present on the system.
Dimensions
NOTE: To prevent leakage, apply Teflon tape sealant to male threads only.
⚠ Warning Use of pipe joint cement may result in obstruction of the aperture and loss of signal.
Switch Clamping Plate Terminal
⚠ Warning An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal.
Typical Sprinkler Applications
Low Pressure Signal Connection
Waterflow Signal Connection
Local Bell For Waterflow Connection
One Conduit Wiring
Break out thin section of divider to provide path for wires when wiring both switches from one conduit entrance.
Switch Operation
Fig. 8
Terminal C: Common
1: Closed when installed under normal system pressure.
2: Open when installed under normal system pressure. Closes on pressure drop.
Use for low pressure supervision.
Terminal
1: Open with no pressure supplied.
Closes upon detection of pressure. Use for waterflow indication.
2: Closed with no pressure applied.
Removing Knockouts
⚠ WARNING
- Installation must be performed by qualified personnel and in accordance with all national and local codes and ordinances.
- Shock hazard. Disconnect power source before servicing. Serious injury or death could result.
- Read all instructions carefully and understand them before starting installation. Save instructions for future use. Failure to read and understand instructions could result in improper operation of device resulting in serious injury or death.
- Risk of explosion. Not for use is hazardous locations. Serious injury or death could result.
⚠ CAUTION
- Do not tighten by grasping the switch enclosure. Use wrenching flats on the bushing only. Failure to install properly could damage the switch and cause improper operation resulting in damage to equipment and property.
- To seal threads, apply Teflon tape to male threads only. Using joint compounds or cement can obstruct the pressure port inlet and result in improper device operation and damage to equipment.
- Do not over tighten the device, standard piping practices apply.
Engineer/Architect Specifications Pressure Type Waterflow Switch
Pressure type waterflow switches; shall be a Model PS10 as manufactured by
Potter Electric Signal Company, St. Louis MO., and shall be installed on the
fire sprinkler system as shown and or specified herein.
Switches shall be provided with a ½” NPT male pressure connection and shall be connected to the alarm port outlet of; Wet Pipe Alarm Valves, Dry Pipe Valves, Pre-Action Valves, or Deluge Valves. The pressure switch shall be actuated when the alarm line pressure reaches 0,27 – 0,55 BAR (4 – 8 PSI).
Pressure type waterflow switches shall have a maximum service pressure rating
of 17,2 BAR (250 PSI) and shall be factory adjusted to operate on a pressure
increase of 0,27 – 0,55 BAR (4 – 8 PSI).
Pressure switch shall have one or two form C contacts, switch contact rating
10.1 Amps at 125/250 VAC, 2.0 Amps at 30 VDC.
Pressure type waterflow switches shall have two conduit entrances one for each
individual switch compartment to facilitate the use of dissimilar voltages for
each individual switch.
The cover of the pressure type waterflow switch shall be Zinc diecast with
rain lip and shall attach with one tamper resistant screw. The Pressure type
waterflow switch shall be suitable for indoor or outdoor service with a NEMA
4/IP66 rating.
The pressure type waterflow switch shall be UL Ulc and CSFM listed, FM and LPC approved and NYMEA accepted.
Ordering Information
PRINTED IN USA
References
- Fire Alarm Resources | Download fire alarm documents
- Potter Electric: Fire Alarms & Fire Sprinkler Systems
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>