Mircom ALCN-792MISO/D Isolated Quad Loop Adder Module Owner’s Manual

October 29, 2023
Mircom

Mircom logo

Mircom ALCN-792MISO/D Isolated Quad Loop Adder Module

Description

The ALCN-792MISO Isolated Quad Loop Adder Module provides two addressable loops plus an additional two loops as part of the daughter board ALCN-792D which is mounted over the ALCN-792MISO. The quad loop adder module provides Signaling Line Circuits (SLC) to the Flex-Net Addressable Fire Alarm system consisting of 159 Sensors and 159 Addressable Modules per loop.

Each ALCN-792MISO Loop Controller Module has a dedicated Central Processor Unit (CPU) and will support two fully loaded SLC lines which will provide up to 318 addressable devices per SLC line, for a total of up to 636 addressable devices per ALCN-792MISO Quad Loop Controller module.

The ALCN-792MISO occupies one module space on any FleX-Net FX-2000N Series control panel chassis
The ALCN-792D daughter board provides two additional SLC lines for up to 318 addressable devices per SLC line, for a total of up to 1,272 addressable devices per combination ALCN-792MISO with ALCN-792D.

Mircom ALCN 792MISO D Isolated Quad Loop Adder Module
1

Features

  • Isolated
  • Dedicated Central Processor Unit (CPU) per module
  • Expands system capacity to 636 addressable devices on 2 loops, 159/159 per loop
  • With the addition of the ALCN-792D this expands module an additional 2 loops bringing module capacity to 1272 addressable devices.

Wiring Diagram

Mircom ALCN 792MISO D Isolated Quad Loop Adder Module
2 ALCN-792MISO with ALCN-792D Electrical Specifications

  • Power Limited: 24VDC, 400mA max, 10kHz frequency
    Max loop resistance: 40 ohms

  • Current Consumption: Standby: 200mA
    Alarm: 213 mA

  • Notes for ALCN-792MISO :
    All circuits are power limited and must use type FPL, FPLR, or FPLP power limited cable.
    Loop wiring: maximum loop resistance is 40 ohms total. These lines are power limited and fully supervised.

Refer to wiring instructions in the Network Fire Alarm Manual

Ordering Information

Model Description
ALCN-792MISO Isolated Quad Loop Adder Module
ALCN-792D Daughter Board

Canada
25 Interchange Way
Vaughan, Ontario L4K 5W3
Telephone: (905) 660-4655
Fax: (905) 660-4113
Web page: http://www.mircom.com

U.S.A.
4575 Witmer Industrial Estates
Niagara Falls, NY 14305
Toll Free: (888) 660-4655
Fax Toll Free: (888) 660-4113
Email: mail@mircom.com

firealarmresources.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Mircom User Manuals

Related Manuals