Mircom MIX-3000 Series Alpha Smoke and Heat Detectors Instruction Manual

June 9, 2024
Mircom

Mircom MIX-3000 Series Alpha Smoke and Heat Detectors

General

These instructions apply to the MIX-2000 standard base and the MIX-2001 E-Z Fit base and MIX-3300, MIX-3000, MIX-3100, MIX-3200 detectors.

Installation

These products must be installed in accordance with the applicable NFPA standards, local codes and jurisdictional authorities. Failure to follow these instructions may result in failure of the detectors to report an alarm condition. Mircom is not responsible for detectors which are improperly installed, maintained and tested.
Before installing these products check the continuity, polarity and insulation resistance of all wiring. Check that sitting is in accordance with the fire system drawings and conforms to all applicable local codes such as NFPA 72.
Use 3″ octagonal box for direct connection to the base. 4″ octagonal and 4″ square boxes may be used with proper UL listed mounting brackets. When mounting on a wall, install 4″ to 12″ from the ceiling. Use 3M Weatherban 606 Non-Flammable sealing compound (or equivalent) to seal field wiring conduit opening in the electrical box, this will reduce the stack effect. Secure the base to the electrical box with appropriate screws. Do not overtighten the screws. The raised
mark on the side of the base indicates the direction of the detector LED when fitted. Connect the shield, if required, to the SHIELD terminal on the base. For information on how to set the address of each device correctly refer to the section ‘Address Setting’ overleaf.

Wiring

CAUTION: Do not use looped wire under terminals L1 and L2. Break wire run to provide supervision of connections. Terminals L1 and L2 are polarity insensitive.

Mircom MIX-3000 Series Alpha Smoke and Heat Detector-
fig2

The above instructions cover the following base models:

MIX-2000 Standard base
MIX-2001 6″ E-Z Fit base

Address Setting

Refer to the table below for the complete list of address settings. Select the desired address and remove the pips indicated in black. Remove pips with a small screwdriver.
Select the desired address and remove the pips indicated in black. Remove pips with a small screwdriver.

Mircom MIX-3000 Series Alpha Smoke and Heat Detector-
fig3

Technical Data

Detector model no. MIX-3300 MIX-3000 MIX-3100 MIX-3200
Detector type Heat Ionization Photoelectric Multisensor
Working voltage 17–28V dc 17–28V dc 17–28V dc 17–28V dc
Modulation voltage 5–9V 5–9V 5–9V 5–9V
Maximum alarm current 3.4mA 3.5mA 3.4mA 3.5mA
Surge current 1.0mA 0.5mA 1.0mA 1.0mA
Supervisory current 500µA 500µA 400µA 500µA
Heat element rating Mode 1 129°F (54°C)

Mode 5 212°F (100°C)

| N/A| N/A| Mode 5 135°F (57°C)
Test method| •Hair dryer| •Home safe- guard Sensitivity test

•No Climb

•Gemini 501

| •Home safeguard

Sensitivity test

•No Climb

•Gemini 501

| •Home safeguard

Sensitivity test

•No Climb

•Gemini 501

•Hair dryer (heat sen- sor only)

Installation temperature| Minimum 32°F (0°C)

Maximum at

least 20°F (11°C) below rating

| Minimum 32°F (0°C)

Maximum 100°F (38°C)

| Minimum 32°F (0°C)

Maximum 100°F (38°C)

| Mode 1-4 Minimum 32°F (0°C)

Maximum 100°F (38°C) Mode 5 Minimum 32°F Maximum at least 20°F (11°C) below rating

Compatibility Information

These smoke and heat detectors have been approved by Underwriters Laboratories Inc. For details of compatible control panels, please contact Mircom.

Canada
25 Interchange Way, Vaughan, Ontario, L4K 5W3
Tel: 905-660-4655, Fax: 905-660-4113

USA
4575 Witmer Industrial Estates Niagara Falls, NY 14305
Tel Toll Free: 888-660-4655, Fax Toll Free: 888-660-4113
Website: www.mircom.com

firealarmresources.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Mircom User Manuals

Related Manuals