Mircom FA-300 Series LCD Fire Alarm Control Panel User Manual

October 29, 2023
Mircom

Mircom-LOGO

Mircom FA-300 Series LCD Fire Alarm Control Panel

Mircom-FA-300-Series-LCD-Fire-Alarm-Control-Panel-
PRODUCT

Introduction

About this Manual

  • This user guide provides information on the main indicators and controls of the FA-300 Fire
  • Alarm Control Panel. Specifically, with this manual you will learn about:
  • What the LEDs on the main display indicate
  • What the buttons on the main display do
  • What certain common LCD screen messages mean
  • Refer to the Glossary on page 18 for an explanation of terms used in this manual.

Technical Support

  • For all technical support inquiries, please contact Mircom’s Technical Support Department between 8 A.M. and 5 P.M. (EDT) Monday through Friday, excluding holidays.
  • Local Phone: 905-695-3535
  • Toll-Free Phone: 1-888-449-3535
  • Local Fax: 905-660-4113
  • Toll-Free Fax: 1-888-660-4113
  • Email: techsupport@mircom.com

Main Display

Figure 1 shows the LCD display, LED indicators, and control button locations.

The main display panel on the fire alarm control board consists of:

  • Five LED indicators (located just below the LCD screen)
  • Five buttons (left edge of display)
  • 16 program buttons (right part of display)

LED indicators may be amber, red, or green, and may illuminate continuously (steady), or at one of two flash rates:

  • Fast flash (supervisory): 120 flashes per minute
  • Trouble flash: 20 flashes per minutes
The Buzzer and LED Indicators

Buzzer

  • The buzzer sounds if there is a fire alarm, a supervisory alarm, or a trouble in the fire alarm system. It turns off if the condition causing the buzzer to sound is cleared or if the BUZZER SILENCE button is pressed.

A.C. On LED

  • The green A.C. On LED illuminates steadily as long as the main power is above minimum level. The indicator turns off when the level falls below the minimum level and the panel switches to standby (battery) power.

Alarm LED

  • The red Alarm LED illuminates steadily when there is a fire alarm. This indicator will remain on until the system is reset.

Supervisory LED

  • The amber Supervisory LED illuminates at the fast flash rate when there is a supervisory alarm in the fire alarm system. For non-latching supervisory alarms, the SUPV LED will turn off when the condition causing the alarm goes away. For latching supervisory alarms, this LED remains on until the panel is reset.

Trouble LED

  • The Trouble LED flashes amber at the trouble flash rate when the panel detects any trouble condition. For non-latching trouble conditions, the Trouble LED turns off when the condition causing the alarm goes away. For latching trouble conditions, the LED remains on until the panel is reset.

CPU Fail LED

  • The CPU Fail LED flashes amber at the trouble flash rate to indicate a microprocessor failure on the main board.

Main Display Buttons

SYSTEM RESET

  • The SYSTEM RESET button resets the fire alarm control panel and all circuits.

SIGNAL SILENCE

  • Pressing the SIGNAL SILENCE button when the panel is in alarm deactivates any silenceable signal devices in the fire alarm system. Non-silenceable signal devices are unaffected. If you press the SIGNAL SILENCE button a second time, or if there is a subsequent alarm, the signals will re-sound. If the panel has been configured with a signal silence inhibit timer, this button will not work until the timer expires. This button also does not work if you have pressed the FIRE DRILL button.

FIRE DRILL

  • Pressing the FIRE DRILL button simulates a fire alarm by activating the fire alarm signals without transmitting an alarm to the central station. To cancel the fire drill, press the button again. If the fire alarm system goes into a real alarm while you are performing a fire drill, this button will not turn off the signals or operate any programmed relays.

LAMP TEST

  • Pressing and holding the LAMP TEST button causes all the front panel LEDs to illuminate. The screen displays the software version and the buzzer sounds. Use this button to test that the LCD display and all LEDs on the main display are working. If you hold the LAMP TEST button for more than ten seconds, the common trouble is activated.

BUZZER SILENCE

  • Pressing the BUZZER SILENCE button while the buzzer is sounding silences the buzzer. The buzzer will resound if there is a subsequent event. Pressing the button when the buzzer is not sounding has no effect.

The Up and Down Arrow Buttons

  • Use these buttons to scroll through any events listed on the screen. The up arrow moves to the next listed condition and the down arrow moves to the previously listed condition.

INFO

  • Press the INFO button while there is a message on the screen to view additional information.

ENTER, MENU, and CANCEL

  • The ENTER, MENU, and CANCEL buttons are used by technicians to program the fire alarm control panel

Disconnecting and Reconnecting a Circuit (Zone)

  • You can disconnect and reconnect detection and signal circuits (zones) from the panel using the bypass options in the menu.
  • To select the bypass options, you must be in the Command Menu. To enter the Command
  • Menu, press MENU.

To Disconnect (Bypass) a CircuitMircom-FA-300-Series-LCD-Fire-Alarm-
Control-Panel-FIG-11

  • If you have disconnected (bypassed) a circuit, a troubling message appears on the display and disappears when the circuit is reconnected

To Reconnect (Unbypass) a CircuitMircom-FA-300-Series-LCD-Fire-Alarm-
Control-Panel-FIG-12

Understanding On-screen Messages

  • The screen of the fire alarm control panel displays messages regarding system events.
  • System events display on the screen in a queue.
  • Events in this queue are listed on the screen in order of priority: alarms are of the highest priority, followed by supervisory, trouble, and monitor conditions. If the same type of event happens more than once (for example, two trouble conditions occur) they will be listed in the order of the most recent event to the least recent event. If an alarm, supervisory, or trouble condition occurs, their respective LED will flash.
  • Scroll through the events by using the arrow buttons. If you need more information about a displayed event, press
  • Note: For monitor events, the display shows the word BUILDING.

Example 1 (detection circuit)

  • Figure 3 indicates that event 1 of 9 is open trouble at the East Lobby Entrance. When  pressed, the screen shows that the process type is a verified alarm on Z-01 and the event occurred on Tuesday, April 4, 2003, at 18:01.Mircom-FA-300-Series-LCD-Fire-Alarm-Control-Panel-FIG-15

Example 2 (indicating circuit):

  • Figure 4 indicates that event 2 of 9 is a short trouble at the East Wing Lobby. When pressed, the screen shows that the process type is silenceable on NAC-1 and the event occurred on Tuesday, February 2, 2003, at 18:01.Mircom-FA-300-Series-LCD-Fire-Alarm-Control-Panel-FIG-16

Common Messages

  • Common system messages are outlined below.

AC Power Fail

  • The “AC Power Fail” message indicates that the power has dropped below the minimum level and the system is running on backup battery power. The trouble is removed when the power returns to the normal value.Mircom-FA-300-Series-LCD-Fire-Alarm-Control-Panel-FIG-17
Battery Trouble
  • The “Battery Trouble” message indicates that the battery voltage has dropped below the minimum value. The trouble is restored when the voltage returns to the normal value.Mircom-FA-300-Series-LCD-Fire-Alarm-Control-Panel-FIG-18
  • Note : The trouble code is a reference code for trained service personnel only.
Ground Fault
  • The “Ground Fault” message indicates that there is a short in the electrical connection between the metal chassis of the panel and the earth.Mircom-FA-300-Series-LCD-Fire-Alarm-Control-Panel-FIG-19

RAU num mismatch

  • The “RAU num mismatch” message can display for one of two reasons: either the main panel and annunciator failed to communicate with each other or an unconfigured remote annunciator is communicating with the main panel. In both cases, the following trouble message is displayed:Mircom-FA-300-Series-LCD-Fire-Alarm-Control-Panel-FIG-20
  • Note: The trouble code is a reference code for trained service personnel only.

4Wire Pwr. Supply

  • The “4Wire Pwr. Supply” message indicates that the panel has detected a short on a four-wire smoke supply the power is cut off and a troubling message is generated. Press System Reset to restore the power to the system. If the short is removed, the panel will return to normal; otherwise, the trouble message will stay.Mircom-FA-300-Series-LCD-Fire-Alarm-Control-Panel-FIG-21
Supervised Aux-supply
  • The “Aux. Power Supply” message indicates that the panel has detected a short on the auxiliary power supply (battery backup) and has cut it off. Press System Reset to restore the power to the system. If the short is removed, the panel will return to normal; otherwise, the trouble message will stayMircom-FA-300-Series-LCD-Fire-Alarm-Control-Panel-FIG-22
  • Note : The trouble code is a reference code for trained service personnel only.

City tie Polarity reversal – PR-300/Relay module

  • The “CtyTie/RM312 missing” message below indicates that the city tie, polarity reversal module or the relay module is not plugged in.Mircom-FA-300-Series-LCD-Fire-Alarm-Control-Panel-FIG-23
  • The “City Tie trouble” message below indicates that the panel detects an open on the city tie output.Mircom-FA-300-Series-LCD-Fire-Alarm-Control-Panel-FIG-24
  • Note: The trouble code is a reference code for trained service personnel only.

Glossary

Alarm Condition

  • Occurs when devices such as detectors, pull stations, or sprinklers are activated. In a single stage system, this condition activates all signaling devices throughout the building. In a two stage system, this condition activates an alert signal and the General Alarm timer.

Circuits

  • Refers to an actual electrical interface and is classified as initiating (detection), indicating (signal), or relay. The terms “circuit” and “zone” are often used interchangeably in the fire alarm industry.

Fast Flash Rate

  • An LED flashes at 120 flashes per minute to indicate a supervisory alarm.

Indicating Circuit

  • A circuit in a fire alarm system that is connected to audible or visual signaling devices.

Initiating Circuit

  • A circuit in a fire alarm system that is connected to detectors, pull stations, sprinklers, or water flow switches.

Latching Circuit

  • A circuit that, when activated, causes a condition on the panel that cannot be cleared until the panel is reset.

LED

  • The light-emitting diodes (LEDs) of the FA-300 are colored either amber, red, or green. When lit, LEDs provide information about the status of the panel.

Monitor Condition

  • Occurs when dampers open or close, when supply and return fans are running, etc.

Non-latching Circuit

  • A circuit that, when activated, causes a condition on the panel that is cleared once the circuit is deactivated. This term is used to describe supervisory and trouble circuits.

Non-Silenceable Circuit

  • A signal circuit that cannot be silenced by pressing the SIGNAL SILENCE button.

Relay Circuit

  • A circuit in a fire alarm system that connects relay devices (for example, fan damper relays).

Remote Annunciator

  • A device that visually indicates, either by LCD or LEDs, the floor or zone where the alarm originated.

Silenceable Circuit

  • A signal circuit that can be silenced by pressing the SIGNAL SILENCE button.

Supervisory Condition

  • Occurs when the system detects open circuits, short circuits, and grounds. A supervisory condition is one that would interfere with the operation of the fire alarm system.

Trouble Condition

  • Occurs when an abnormal condition such as a problem in the wiring, battery or power circuits exists in the fire alarm system.

Trouble Flash Rate

  • An LED flashes at 20 flashes per minute to indicate a trouble condition.

Walk Test

  • A test performed by a technician to ensure that each detection device is connected to the panel and working properly.

Zone

  • A fire alarm protected area that consists of at least one circuit. The terms “circuit” and “zone” are often used interchangeably in the fire alarm industry.
  • Mircom 2017
  • Printed in Canada
  • Subject to change without prior notice
  • www.mircomgroup.com
TECHNICAL SUPPORT
  • North America
  • Tel: (888) Mircom5
  • (888) 647-2665
  • International
  • Tel: (905) 647-2665
  • U.S.A
  • 4575 Witmer Industrial Estates
  • Niagara Falls, NY 14305
  • Tel: (888) 660-4655
  • (905) 660-4655
  • Fax: (905) 660-4113
  • CANADA – Main Office
  • 25 Interchange Way
  • Vaughan, ON L4K 5W3
  • Tel: (888) 660-4655
  • (905) 660-4655
  • Fax: (905) 660-4113
  • firealarmresources.com

Documents / Resources

| Mircom FA-300 Series LCD Fire Alarm Control Panel [pdf] User Manual
FA-300 Series LCD Fire Alarm Control Panel, FA-300 Series, LCD Fire Alarm Control Panel, Alarm Control Panel
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Mircom User Manuals

Related Manuals