RAB XFMR200-480-277 Step-Down Autotransformer Instructions

June 9, 2024
RAB

RAB XFMR200-480-277 Step-Down Autotransformer

RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. Wed love to hear your comments. Please call thee Marketing Department at 888-RAB-1000 or email: marketing@rablighting.com

IMPORTANT

READ CAREFULLY BEFORE INSTALLING TRANSFORMER. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.
RAB transformer must be wired in accordance with the National Electrical Code and all applicable codes.Proper grounding is required for safety.
IS PRODUCT MUST BE INSTALLEDIN ACCORDANCE WITHTHE APPLICABLE INSTALLATION CODE BY A PERSON FAMILIARWITHTHE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED.

WARNINGS:

  • Risk of fire or electric shock. Transformer installation requires a qualified electrician. If not qualified, do not attempt installation.
  • The transformer shall be used within Recognized ratings as specified in “ELECTRICAL RATINGS
  • The transformer shall be mounted in the intended manner in an enclosure having adequate strength and thickness with acceptable spacings being provided.
  • The necessity of repeat Temperature Test shall be determined in the end use application.
  • The transformer employs a 105°C Class A insulation system.
  • Leakage current was not evaluated. The need of leakage current test is to be determined for each end product application.
  • The suitability of primary and secondary pins shall be determined in the end-product investigation.
  • The suitability of mounting means shall be determined in the end-product investigation.
  • The transformer is only suitable for factory installation.
  • The transformer has been evaluated at ambient temperature (Tmra) of 25°C.
  • Normal operating temperature range:-30°C- +45°C, Storage temperature range:-30°C-+80°C

ELECTRICAL SPECIFICATIONS

INPUT CHARA CTERISTICS OUTPUT CHARACTERISTICS
Input Voltage I nput Current at Max Load

Maximum Outp ut Current
480V| 0.46A| 2S0V| 200VA| 0.8A
347V| 0.6SA| 2S0V| 200VA| 0.8A

WYE 48OV OR GROUNDED DELTA POWER

WIRING DIAGRAM

Wiring Notes:

  • Wiring for 3-Phase Wye (or Star) 480V system, connect any two phase wires to autotransformer inputs (red and black wires).
  • Wiring for 3-Phase Delta 480V system with proper grounding, connect 480V and ground reference legs to autotransformer inputs (red and black wires).

Easy Answers

2023 RAB LIGHTING Inc.
Cranbury, New Jersey 08512 USA

rablighting.com
Visit our website for product info

Tech Help Line
Call our experts: 888 722-1000

e-mail
Answered promptly – sales@rablighting.com

Free Lighting Layouts
Answered online or by request

XFMR200-480-277 RAB WARRANTY: RABs warranty is subject to all terms and conditions found at rablighting.com/warranty.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals