DIGITUS DN-170106 6 kVA Online UPS System Installation Guide
- June 9, 2024
- DIGITUS
Table of Contents
ONLINE UPS SYSTEM
6 kVA / 10 kVA
DN-170106 Rev. 2・DN-170107 Rev. 2
Quick Installation Guide
Safety
Important safety instructions – Save these instructions
There exists dangerous voltage and high temperature inside the UPS. During the
installation, operation and maintenance, please abide the local safety
instructions and relative laws, otherwise it will result in personnel injury
or equipment damage. Safety instructions in this manual act as a supplementary
for the local safety instructions. Our company will not assume the liability
that caused by disobeying local safety instructions.
1.1 Safety notes
-
Even no connection with utility power, 208/220/230/240VAC voltage may still exist at UPS outlet!
-
For the sake of human being safety, please well earth the UPS before starting it.
-
Don’t open or damage battery, for the liquid spilled from the battery is strongly poisonous and do harmful to body!
-
Please avoid short circuit between anode and cathode of battery, otherwise, it will cause spark or fire !
-
Don’t disassemble the UPS cover, or there may be an electric shock!
-
Check if there exists high voltage before touching the battery
-
Working environment and storage way will affect the lifetime and reliability of the UPS. Avoid the UPS from working under following environment for long time
• Area where the humidity and temperature is out of the specified range (temperature 0 to 40℃, relative humidity 5%-95%)
• Direct sunlight or location nearby heat
• Vibration Area with possibility to get the UPS crashed.
• Area with erosive gas, flammable gas, excessive dust, etc -
Keep ventilations in good conditions otherwise the components inside the UPS will be over-heated which may affect the life of the UPS.
1.2 Symbols used in this guide
WARNING!
Risk of electric shock
CAUTION!
Read this information to avoid equipment damage
Product Introduction
This series UPS is a kind of single phase in single phase out high frequency online UPS, it provides two capacities: The 6kVA and 10kVA. The products are modularized and adopt the N+X redundancy. It can flexibly increase the number of the UPS modules according to the load capacity which is convenient for flexible allocation and gradually investment.
Installation
3.1 Unpack checking
- Don’t lean the UPS when moving it out from the packaging
- Check the appearance to see if the UPS is damaged or not during the transportation, do not switch on the UPS if any damage found. Please contact the dealer right away.
- Check the accessories according to the packing list and contact the dealer in case of missing parts.
Package Content:
- 1 x UPS
- 1 x UPS User Guide
- 1 x UPS Quick Installation Guide
- 1 x Software download license
- 1 x USB cable
- 1 x RS232 cable
- 1 x Parallel cable
3.2 UPS Module Outlook
(1) EPO
(2) Parallel Port 1
(3) USB
(4) Input breaker
(5) Intelligent slot| (6) Battery Slot
(7) PDU
(8) COM (RS232)
(9) Parallel Port 2
(10) Terminal
---|---
3.3 LCD control panel
(1) INVERTER LED
(2) BATTERY LED
(3) BYPASS LED
(4) ALARM LED
(5) LCD display| (6) UP button
(7) DOWN button
(8) ESC /OFF button
(9) ENTER/ON button
---|---
3.4 Installation notes
-
Please place the UPS in a clean, stable environment, avoid the vibration, dust, humidity, flammable gas and liquid, corrosive objects. To avoid from high room temperature, a system of room extractor fans is recommended to be installed. Optional air filters are available if the UPS operates in a dusty environment.
-
The environment temperature around the UPS should keep in a range of 0°C ~40°C. If the environment temperature exceeds 40℃, the rated load capacity should be
reduced by 12% per 5°C. The max temperature can’t be higher than 50°C. -
If the UPS is dismantled under low temperature, it might be in a condensing condition.The UPS can’t be installed unless the internal and external of the equipment is fully dry. Otherwise, there will be in danger of electric shock.
-
Batteries should be mounted in an environment where the temperature is within the required specs. Temperature is a major factor in determining battery life and capacity. In a normal installation, the battery temperature is maintained between 15°C and 25°C. Keep batteries away from heat sources or main air ventilation area, etc.
WARNING!
Typical battery performance data are quoted for an operating temperature between 20°C and 25°C. Operating it above this range will reduce the battery life while operation below this range will reduce the battery capacity. -
Should the equipment not be installed immediately it must be stored in a room so as to protect it against excessive humidity and or heat sources.
CAUTION!
An unused battery must be recharged every 3months. Temporarily connecting the UPS to a suitable AC supply and activating it for the time required for recharging the batteries are required. -
The highest altitude that UPS may work normally with full load is 1500 meters.
The load capacity should be reduced when this UPS is installed in place whose altitude is higher than 1500 meters, shown as the following table:
(Load coefficient equals max load in high altitude place divided by nominal power of the UPS)
Altitude (m) | 1500 | 2000 | 2500 | 3000 | 3500 | 4000 | 4500 | 5000 |
---|---|---|---|---|---|---|---|---|
Load coefficient | 100% | 95% | 90% | 85% | 80% | 75% | 70% | 65% |
To get the UPS completely monitored by the software, you just simply connect RS232 or USB cable to each end of the computer and the UPS respectively.
3.5 External Protective Devices
For safety reasons, it is necessary to install, external circuit breaker at
the input A.C. supply and the battery. This chapter provides guidelines for
qualified installers that must have the knowledge of local wiring practices
for the equipment to be installed.
External Battery
The UPS and its associated batteries are protected against the effect of over-
current through a DC compatible thermo-magnetic circuit-breaker (or a set of
fuses) located close to the battery.
UPS Output
Any external distribution board used for load distribution shall be fitted
with protective devices that may avoid the risk of UPS overloaded.
Over-current
Protection device shall be installed at the distribution panel of the incoming
main supply. It may identify the power cables current capacity as well as the
overload capacity of the system.
CAUTION!
Select a thermo magnetic circuit-breaker with an IEC 60947-2 trip curve C
(normal) for 125% of the current as listed below.
3.6 Power Cables
The cable design shall comply with the voltages and currents provided in this
section, Kindly follow local wiring practices and take into consideration the
environmental conditions (temperature and physical support media).
WARNING!
Upon starting, please ensure that you are aware of the location and operation
of the external isolators which are connected to the UPS input/bypass supply
of the mains distribution panel. Check to see if these supplies are
electrically isolated, and post any necessary warning signs to prevent any
inadvertent operation.
Cable Dimension
UPS module | Cable Dimension |
---|
AC Input
(mm2)| AC Output
(mm2)| DC Input
(mm2)| Grounding
(mm2)
6kVA| 6| 6| 6| 6
10KVA| 10| 10| 10| 10
CAUTION!
Protective earth cable: Connect each cabinet to the main ground system.
For Grounding connection, follow the shortest route possible.
WARNING!
Failure to follow adequate earthing procedures may result in electromagnetic
interference or in hazards involving electric shock and fire.
3.7 Power cable connect
Once the equipment has been finally positioned and secured, connect the power
cables as described in the following procedure.
Verify the UPS is totally isolated from its external power source and also all
power isolators of the UPS are open. Check to see if they are electrically
isolated, and post any necessary warning signs to prevent their inadvertent
operation.
Choose appropriate power cable, and pay attention to the diameter of the
connection terminal of the cable that should be greater than or equal to that
of the connection poles.
WARNING!
If the load equipment is not ready to accept power on the arrival of the
commissioning engineer then ensure that the system output cables are safely
isolated at their ends.
CAUTION!
The earthing and neutral bonding arrangement must be in accordance with local
and national codes of practice.
3.8 Battery connection
The installation between UPS and EBPS shown as following
Note:
The BAT+ of the UPS connect poles is connected to the anode of the positive
battery, the BAT- is connected to the cathode of the positive battery and the
anode of the negative battery, the BAT- is connected to the cathode of the
negative battery.
Factory default setting for battery quantity is 20pcs and for battery capacity
is 9AH (charger current 1.35A). When connecting 16pcs or 18pcs batteries,
please re-set battery quantity and its capacity after UPS starts at AC mode.
When multiple battery boxes are connected in parallel, you only need to set
the battery capacity, and the number of batteries remains unchanged. Charger
current could be adjusted automatically according to battery capacity
selected. These corresponding settings are done though LCD.
Note:
1pcs UPS can connect max. 4pcs battery modules.
CAUTION!
Ensure correct polarity battery string series connection. i.e. inter-tier and
inter block connections are from (+) to (-)terminals. Don’t mix batteries with
different capacity or different brands, or even mix up new and old batteries,
either.
WARNING!
Ensure correct polarity of string end connections to the Battery Circuit
Breaker and from the Battery Circuit Breaker to the UPS terminals i.e. (+) to
(+) / (-) to (-) but disconnect one or more battery cell links in each tier.
Do not reconnect these links and do not close the battery circuit breaker
unless authorized by the commissioning engineer
3.9 Communication connection
Communication port
To allow for unattended UPS shutdown/start-up and status monitoring, connect
the communication cable one end to the USB/RS-232 port and the other to the
communication port of your PC. With the monitoring software installed, you can
schedule UPS shutdown/start-up and monitor UPS status through PC.
The UPS is equipped with intelligent slot perfect for either SNMP or Relay
card. When installing either SNMP or Relay card in the UPS, it will provide
advanced communication and monitoring options.
Note: USB port and RS-232 port can’t work at the same time.
Note: Using the provide USB cable is required.
3.10 Install software
For optimal computer system protection, install UPS monitoring software to
fully configure UPS shutdown. You may follow the Software License Card
instruction to install the monitoring software.
Note: The software product SN. can be only allowed for one PC
installation.
Operation
4.1 Turn on/off UPS
4.1.1 Connecting with Utility
CAUTION!
Make sure grounding is properly done!
- Set the Battery Breaker to the “ON” position according to the user’s manual.
- Switch on the UPS
WARNING!
Check to see if the load is safely connected with the output of the UPS. If
the load is not ready to receive power from the UPS, make sure that it is
safely isolated from the UPS output terminals
The internal fan of the UPS starts spinning, the UPS is performing
selfdiagnostics until buzzer beeps twice to show the UPS is normal. Then, the
UPS goes to bypass supply, Utility LED and Bypass LED turn Green, the inverter
is starting up now. When the inverter is checked “normal”, the UPS goes to
working mode and the load is supplied by
the inverter now. No matter the UPS is operated normally or not, the LCD
display will indicate current status. The top lines display the UPS
operational status and the bottom lines indicate alarm conditions when they
occur.
4.1.2 Black (Cold) start procedure
CAUTION!
Follow these procedures when the input AC Utility Failure, but battery is
normal
-
Turn on the battery switch.
The battery will feed the Auxiliary power board. -
Press and hold the ON key for more than two seconds to start the UPS.
When battery normal, rectifier starts operation, 30s later, inverter starts and operates, INV and output light up.
CAUTION!
Wait for approximately 30 seconds before you press the black start key.
4.1.3 Inverter Off
When the Utility is normal, press “ESC /OFF” button for approx. 1 sec until
beep sounds, the inverter LED will extinguish, the bypass LED on, then the UPS
turns to bypass supply.
When the UPS is on battery mode or without AC, press “ESC /OFF” button for
approx. 1 sec until beep sounds, the output of the UPS is off, fan stop
spinning. After 60 seconds, all the LED on the LCD display extinguish.
4.1.4 Disconnecting with Utility
CAUTION!
This procedure should be followed to completely shut down the UPS and the
LOAD. After all power switches, isolators and circuit breakers are opened,
there will be no output.
- After the inverter is off, turn the Utility and battery breakers to “OFF”, then the LCD display will extinguish completely and fan stops spinning in 60 seconds. If there are external battery packs connected, please also turn the battery breaker to “OFF”.
WARNING!
Wait for about 5 minutes for the internal D.C. bus bar capacitors to be
completely discharged.
4.3 LCD Display instruction
NOTICE! The display provides more functions than those described in this
manual.
There are 10 interfaces available in the LCD display:
ITEM | Interface Description | Content Displayed |
---|---|---|
1 | Input | Voltage & Frequency |
2 | Output | Voltage & Frequency |
3 | Bat. + | Voltage & Current |
4 | Bat. – | Voltage & Current |
5 | Temperature | PFC/ Internal temperature and ambient temperature |
6 | Load | Load |
7 | Bus voltage | Bus voltage ± |
8 | Software version | DSP version of inverter software |
9 | Model | Model |
- When the UPS is connecting with the Utility or Battery at cold start mode, it shows as drawing below:
-
Operational Status and mode
When the UPS at single mode, it shows “NOA” or “ECO” or “CF” or “GEN” or “SEF”, but If the UPS at parallel mode, it shows “PAL” instead -
Press “DOWN” button, the UPS goes to next page as shown below.
More detailed information on operation and device settings can be found in the corresponding user manual.
This is a Class A product. In home environment, this product may cause radio
interference.
In this case, the user may be required to take appropriate measures.
Hereby Assmann Electronic GmbH, declares that the Declaration of Conformity is part of the shipping content. If the Declaration of Conformity is missing, you can request it by post under the below mentioned manufacturer address.
www.assmann.com
Assmann Electronic GmbH
Auf dem Schüffel 3
58513 Lüdenscheid
Germany
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>