Model| Voltage| Frequency| CCT| Wattage| PF| Lumen| Beam Angle| Dimension| Working temperature| Weight
---|---|---|---|---|---|---|---|---|---|---
ZU210.12| 100–277 V| 50/60 Hz| 4 000 K| 100 W| ≥0.9| 17 000 lm| 120°| ø 265 × 163 mm| -35~+50°C| 2.15 kg
ZU210.6| 100–277 V| 50/60 Hz| 4 000 K| 100 W| ≥0.9| 17 000 lm| 60°| ø 265 × 163 mm| -35~+50°C| 2.15 kg
ZU210.9| 100–277 V| 50/60 Hz| 4 000 K| 100 W| ≥0.9| 17 000 lm| 90°| ø 265 × 163 mm| -35~+50°C| 2.15 kg
ZU215.12| 100–277 V| 50/60 Hz| 4 000 K| 150 W| ≥0.9| 25 500 lm| 120°| ø 300 × 173 mm| -35~+50°C| 2.65 kg
ZU215.6| 100–277 V| 50/60 Hz| 4 000 K| 150 W| ≥0.9| 25 500 lm| 60°| ø 300 × 173 mm| -35~+50°C| 2.65 kg
ZU215.9| 100–277 V| 50/60 Hz| 4 000 K| 150 W| ≥0.9| 25 500 lm| 90°| ø 300 × 173 mm| -35~+50°C| 2.65 kg
ZU220.12| 100–277 V| 50/60 Hz| 4 000 K| 200 W| ≥0.9| 34 000 lm| 120°| ø 340 × 178 mm| -35~+50°C| 3.25 kg
ZU220.6| 100–277 V| 50/60 Hz| 4 000 K| 200 W| ≥0.9| 34 000 lm| 60°| ø 340 × 178 mm| -35~+50°C| 3.25 kg
ZU220.9| 100–277 V| 50/60 Hz| 4 000 K| 200 W| ≥0.9| 34 000 lm| 90°| ø 340 × 178 mm| -35~+50°C| 3.25 kg

Mounting

  • Method A: Loop
    Install the loop with gasket to luminaire well in the specified position.
    Hang the luminaire well into the hook.
    Wiring 1 to power supply cable: Brown-L; Blue-N; Green-G;
    Wire 2 to dimmer: Purple – Dim+, Grey – Dim-.

  • Method B: Bracket

1. Remove four screws holding the driver.
2. Insert the bracket between the driver and the body of the luminaire.
3. Screw the screws back to their original location.
4. Install 2 pcs M8 expanding bolts on the mounting surface as per the hole position on our luminaire.
5. Loose the auxiliary screws on two sides of the bracket.  

Rotate the luminaire to desirable degree and tighten auxiliary screws again.

6. Wiring 1 to power supply cable: Brown-L; Blue-N; Green-  

G; Wiring 2 for dimming: Purple – Dim+, Grey – Dim-
Installation height 2.5 m.

  1.         *  **L** – brown – live wire
    *  **G** – green&yellow – earth wire (ground)
    *  **N** – blue – neutral wire
    *  **Dim** \+ – purple – Dimming +
    *  **Dim-** – grey – Dimming –

Dimming can be realised in two ways via convertors ZU9001 and ZU9002: 0–10 V, DALI.

Installation of Converters

ZU9001 is an isolated signal converter which allows to use 0–10 V dimming.
ZU9002 is an isolated signal converter, transforming the DALI signal to 0–10 V output. It conforms to the DALI protocol IEC62386-101/101/207.

  1. Turn the cover to left and lift outwards to take it down.
  2. Insert the connector of the controller into the interface and rotate the controller device clockwise direction.
    Rotate in any angle until the controller device falls inside. Then continue to rotate in clockwise direction until it cannot be rotated.

ATTENTION!!! Do not under any circumstances connect mains voltage to conductors intended to control dimming. Risk of destroying the light fitting.

Maintenance instructions

Before maintenance, switch off the lamp and wait until itis cooled.
Clean it with a soft moistened cloth.
Never submerge the lamp in water or other liquids. During maintenance, observe general rules for occupational safety, and be very careful.

WARNING

  • If the external flexible cable or cord of this luminaire is damaged, it shall be exclusively replaced by the manu-facturer or his service agent or a similar qualified person in order to avoid a hazard.
  • The light source contained in this luminaire shall only be replaced by the manufacturer or his service agent or a similar qualified person.
  • Terminal block not included. Installation may require advice from a qualified person.
  • Terminal block for connection of power supply: 3 terminals screw-type or screw-less type, rated for cross-section range including 1.0 mm2 and voltage min 230 V. For installation with connecting dimming control wires additional 2 terminals are required.
  • Maintain a minimum distance of 1 m between the Highbay light fitting and the object or surface you are illuminating.
  • If you are installing the Highbay light fitting under roofing, maintain a minimum distance of 0.2 m between the up-per side of the light fitting and the bottom of the roofing.
  • When using the Highbay light fitting on a flammable surface, observe the above instructions.
  • The Highbay light fitting may only be connected to electrical mains with installation and protection that is in line with valid regulations and standards.
  • Before interfering with the Highbay light fitting or per-forming maintenance and repair, the light fitting must be disconnected from the mains. This must only be done by a knowledgeable/experienced person within the meaning of valid regulations on qualification for such activities.
  • Do not use the Highbay light fitting without the protec-tive glass.
  • Protection against dangerous contact voltage is ensured through connection to a neutral conductor.
  • The exterior flexible cable for the light fitting cannot be replaced; if the cable is damaged, the light fitting must be disposed of.
  • The light source of the light fitting is not replaceable; after the end of the light fitting‘s service life, the entire light fitting must be replaced.
  • The light fitting does not come with a terminal box. Instal-lation may require the assistance of a qualified person.
  • Caution, risk of electric shock.

Do not dispose with domestic waste. Use special collection points for sorted waste. Contact local authorities for in-formation about collection points. If the electronic devices would be disposed in landfill, dangerous substances may reach groundwater and subsequently food chain, where it could affect human health.
EMOS spol. s r.o. declares that the ZU210.12, ZU210.9, ZU210.6, ZU215.12, ZU215.9, ZU215.6, ZU220.12, ZU220.9, ZU220.6 is in compliance with the essential requirements and other relevant provisions of Directive. The device can be freely operated in the EU. The Declaration of Conformity can be found at http://www.emos.eu/download.

This product contains a light source of energy efficiency class C

Do not throw electric appliances into unsorted municipal waste, use collection points of sorted waste! Dangerous sub-stances from electric appliances deposited in landfills can leak into underground waters, reach the foodchain and damage your health and well-being. For actual information about collection points, contact the local authorities.

tel: +386 8 205 17 21
e-mail: [email protected]

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

EMOS User Manuals

Related Manuals