Xitanium SR Bridge Built User Guide
Design-in Guide
Reliable SR technology for connected lighting applications
Introduction to this guide
Xitanium SR Bridge
Thank you for choosing the Philips Xitanium Sensor Ready Bridge (“SRB”). In
this guide you will find the information needed to integrate these devices
into a luminaire or lighting system.
This edition describes the Xitanium SR Bridge. We advise you to consult our
websites for the latest up-to-date information.
Applications
Philips Xitanium SR Bridge allows existing DALI drivers to become part of
wireless connected lighting systems for indoor lighting such as offices,
public buildings, industrial
applications and retail environments.
Information and support
Please consult your local Signify office or
visit:www.philips.com/oem
www.philips.com/multione
Design-in support
Dedicated design-in support from Signify is available on request. For this
service please contact your local Signify representative.
Document overview
In order to provide information in the best possible way, Signify’s philosophy
on product documentation is the following.
- Commercial leaflet contains product family information & system combinations
- Datasheet contains the product-specific specifications
- Design-in guide describes how the product must be used
- Driver certificates list up-to-date compliance with relevant product standards
All these documents can be found on the download page of our OEM website
www.philips.com/oem. If you require any further
information or support please contact your
local Signify representative.
Warnings and instructions
Safety warnings:
- Avoid touching live parts!
- Do not use the SR Bridge with damaged housing and/or connectors!
- Do not service the SR Bridge when the mains voltage is connected; this includes connecting or disconnecting wires and cables.
Safety warnings and installation instructions
- Do not use damaged products.
- Do not short SR Bridge output wires.
- SR Bridge output wire is a live mains part when switched on.
- The luminaire manufacturer is responsible for his own luminaire design and has to comply with all relevant safety standards.
- The Xitanium SR Bridges are suitable for built-in Class I and Class II and independent Class I and Class II applications; they must not be exposed to the elements such as snow, water and ice or to any other chemical agent which can be expected to have an adverse effect on the driver (e.g. Corrosive environments). It is the responsibility of both luminaire manufacturer and installer to prevent exposure.
- Do not service the SR Bridge and connected driver(s) when the mains voltage is connected, this includes connecting or disconnecting loads.
- SR Bridge and connected driver(s) must be installed in accordance with national and local electrical codes.
- Please provide adequate earth and/or equipotential connections whenever possible or applicable.
- In case the SR Bridge is used in the independent application the SR Bridge must be protected against ingress of and exposure to including but not limited to water, oil, fat, acids or any other chemical agent – be it in the gaseous, vapor, liquid or solid form- which can be expected to have an adverse effect on the SR Bridge (e.g. use in wet /corrosive / dusty environments). It is the responsibility of both luminaire manufacturer and installer to prevent ingress and exposure. Common sense needs to be used in order to define the proper ingress protection of the SR Bridge for the intended application.
- Independent application: for thermal reasons the SR Bridge must be mounted in such a way that distance between the SR Bridge and adjacent objects (excluding the mounting surface) is at least 20mm, see the illustration on the left. Do not exceed the maximum specified ambient temperature (ta) as specified for the SR Bridge.
Introduction to the Xitanium SR Bridge
Xitanium SR Bridge
The Xitanium SR Bridge is designed to connect existing or new DALI indoor
lighting systems to SR (wireless) connected systems, or to switch ON/OFF any
driver via a line-switch. Applications include offices, public buildings,
industrial applications and retail environments. With Xitanium SR
functionality, flexibility in luminaire design is assured and with the SR
interface it is simpler than ever to connect to SR certified sensors.
Xitanium SR Bridge versions
The Xitanium SR Bridge described in this guide is available in 2 versions; a
built-in and an independent version. Detailed specifications can be found in
the Xitanium SR Bridge datasheets which can be downloaded at
www.philips.com/oem.
Programmable Interface
The Xitanium SR Bridge is programmable. Seveal features and parameters can be
set via the SR Interface or SimpleSet using the Philips MultiOne Configurator
software and tool.
SimpleSet
Philips SimpleSet NFC wireless programming technology allows luminaire
manufacturers to quickly and easily program the Xitanium SR Bridge in any
stage during the manufacturing process, without a connection to mains power,
offering great flexibility. For more information on MultiOne or SimpleSet,
please visit www.philips.com/multione or
contact your local Philips representative.
SR Bridge driver connection
A typical application for the Xitanium SR Bridge is to connect the SR Bridge
to one or more Philips Xitanium DALI drivers and a SR Certified sensor,e.g.
Philips EasyAir.
Up to twenty DALI drivers can be controlled by a single Bridge via its DALI
interface.
Alternatively, multiple drivers – which must not be Dali -can be connected to
the relay port of the SR-bridge for on/off switching of their mains support.
A single EasyAir sensor connected to multiple SR Bridges
If one sensor is connected to multiple SR-bridges, not more than four SR
Bridges must have their SR PSUs enabled. To minimize unnecessary losses, it is
recommended to turn on only two SR Bridge SR PSUs. Each SR PSU can supply 52
mA supply current. More details about EasyAir can be found in the Design-in
Guide for the EasyAir sensors at
www.philips.com/oem.
Features of the Xitanium SR Bridge
Mains input range
The AC input voltage ranges for performance and operational safety can be
found in the SR Bridge datasheet. DC input voltage operation is not supported.
Switched output using zero crossing detection
The output of the Xitanium SR Bridge can be switched on/off using its internal
relay. Switching is based on advanced zero crossing technology to reduce
inrush current. This allows for higher loads to be switched on/off by the SR
Bridge (up to 400W max).
Note: The internal SR Bridge relay can be bypassed by connecting drivers
to permanent mains voltage and using DALI on/off commands instead to turn
on/off the driver output.
Note: For DALI identification, the SET POWER ON LEVEL command will result
in momentary blinking of the light. This blinking cannot be avoided.
Programmable Interface
The Xitanium SR Bridge is programmable. A number of features and parameters
can be set via either MultiOne Configurator or SimpleSet. Items that can be
programmed can be found in the section Controllability.
SR (Sensor Ready) interface
The Xitanium SR Bridge features a digital interface (SR interface) to enable
direct connection to any suitable SR Certified sensor. Communication is based
on DALI 2 protocol
Energy metering
The Xitanium SR Bridge has built in energy and power measurement capability.
Given its limited accuracy, this information cannot be used for billing
purposes. Energy readings show the total consumed energy of all drivers
connected to the bridge but not the consumption of individual drivers.
Driver Diagnostics
A threshold can be set for the power consumption of the connected load (ON/OFF
load on line switch port) at which a lamp failure error is flagged. Default,
this feature is disabled.
Multiple DALI drivers on a single SR Bridge
Up to twenty DALI drivers can be connected to a single SR bridge via its DALI
interface. Please refer to the datasheet for more details.
SR bus power supply unit (SR PSU)
The SR Bridge has an internal power supply which can be used to power the
connected sensor via the SR bus.
SR Bridge wiring diagrams
DALI connection
- Up to twenty DALI drivers can be controlled by a single Bridge via its DALI interface. The total electrical load connected to the SR bridge must not exceed 400VA.
- Supports full sensor control including on/off, dimming, color tuning and scene setting
Wiring diagram DALI connection
Connection at internal relay port
- Multiple drivers with up to 400VA electrical load can be connected.
- Via the relay mains supply of the drivers is fully switched off/on; no standby power of the drivers is kept on.
- The relay can also be configured to always stay closed.
- Not suitable for dimming features, e.g. for daylight regulation or background level at shared occupancy.
SR (Sensor Ready) interface
Sensor Ready Interface
The Xitanium SR Bridge features a digital SR interface to enable direct
connection to any suitable SR Certified sensor. The simple two-wire SR
interface supports these key functions:
- Switchable built-in SR PSU to provide power to the connected sensor
- Two-way digital communication between the SR Bridge and sensor, using DALI 2 protocol
- Standard DALI dimming, on/off and control functions
- Power and energy reporting, utilizing the power monitoring integrated in the SR Bridge
- Diagnostic information
SR PSU:
The SR Bridge has the ability to supply the SR bus with a built-in SR PSU that
can be turned on/off. By factory default the SR PSU is turned on and ready to
be used with an external sensor. The SR PSU should in principle be turned off
if used in SR networks with multiple SR Bridges to avoid that wrong polarity
can lead to very high currents on the SR bus.
The SR PSU can be turned on/off with the MultiOne configuration software. The
SR PSU is capable of delivering a minimum current of 52mA (ISR) to the SR bus
and the
connected device(s) and will never supply more than 60mA (ISR_MAX). The SR bus
voltage will be between 12V and 20V depending on the connected sensor load and
the
amount of SR PSUs connected in parallel. See the figure on the left for the
typical VI curve for one SR PSU. When the SR PSU is switched off the SR Bridge
will extract a maximum of 2mA from the SR bus.
Sensors
Most SR certified sensors intended to be used in an SR system will be powered
from the SR bus. When communication is present on the SR bus, the bus gets
pulled down by the data packages. This reduces the average current available
for the sensor. When communicating the average available current can drop with
50%. This should be taken into account when designing the sensor. The
extracted peak current (ISR_ EXTRACTED) should be limited by the sensor.
Rules for building an SR system:
- Respect SR bus polarity when more than one SR PSU is connected in parallel.The total maximum SR bus current(ISR_MAX_TOTAL) must be ≤ 250mA. This current can be determined by adding ISR_MAX of all SR PSUs. As a consequence a maximum of four SR PSUs can be connected in parallel.
- The total current delivered to the SR bus (ISRDELIVERED) can be determined by adding ISR of all SR PSUs. The total current extracted from the SR bus (ISR EXTRACTED) can be determined by adding up consuming devices like SR drivers with switched off SR supply, other DALI gear and control devices.
- To guarantee good communication, a margin of 8mA is needed to drive the SR bus itself (ISR_MARGIN).
- The following rule should be respected: ISR_EXTRACTED + ISR_MARGIN ≤ ISR_DELIVERED.
Caution:
- When the above rules are not taken into account, communication cannot be guaranteed and damage to components may occur.
Typical examples:
1: One SR Bridge is connected to a sensor. The SR PSU of this Bridge is
switched on. The specification of the sensor states that the extracted peak
current is 40mA.
Will this SR system have good communication?
- One SR supply is involved, so BUS polarity is irrelevant.
- ISR_MAX_TOTAL = 60mA. This is ≤ 250mA
- ISR_DELIVERED = 52mA
- ISR_EXTRACTED = 40mA
- ISR_MARGIN = 8mA
- 40 + 8mA ≤ 52mA
Conclusion: this system will function properly.
2: Is it allowed to add an SR Bridge with switchedoff SR PSU to this SR system?
- Yes, an SR Bridge with switched-off SR PSU extracts 2 mA from the SR bus.
- ISR_EXTRACTED = 40 + 2 = 42mA.
- 42 + 8 mA ≤ 52mA
Conclusion: this system will function properly.
3: Can this SR supply in example 2 also be switched on?
- Yes, but polarity of both SR PSUs must be observed.
- ISR_TOTAL = 2 * 60 = 120mA. This is ≤ 250mA.
Conclusion: this system will function properly.
Digital communication:
Dimming is possible through the standard digital interface based on DALI 2
protocol. Dimming range is 1%-100%. Dimming curves can be either logarithmic
or linear (see the figures on the left).
- Note that the output current at 1% and 100% level is determined by the connected driver.
- The SR Bridge has built-in energy measurement capability and can report energy and actual power consumption. Accuracy of power measurement is higher of following two values: 0.5W or +/-4 % measured input power. This feature stores parameters in the non- volatile memory bank provision specified in the DALI 2 standard and the SR Certified specification.
- The SR Bridge also supports many diagnostic features/parameters which can be accessed via the SR interface.
Although the SR interface supports DALI commands, it is not a DALI interface as such since the interface is polarity-sensitive and its cable lenght is limited to 15m. We do not advise use of the SR bus in wired DALI networks.
Other considerations for the SR interface
- Length of cabling, using 0.75mm wires: the maximum2 SR bus cable length wiring must not exceed 15m.
- The SR control interface is SELV-classified.
Basic SR Bridge use case
The basic use case for the SR Bridge is to connect one or more Xitanium DALI
drivers and a SR Certified sensor to the SR Bridge. The maximum load that the
SR Bridge relay can switch is 400W while its DALI interface can control max.
twenty DALI drivers.
SR Bridge fault detection use case
The SR Bridge is measuring the power/energy consumption of the connected loads
constantly. For ON/OFF loads on line switch port the fault detection feature
can be used to monitor the connected loads and determine whether one (or more)
of the loads have failed. The SR Bridge has the capability to set an (alarm)
message flag based on a trigger point that the load has been reduced. The
fault detection accuracy depends on the trigger point. Default, this feature
is disabled. It can be enabled via MultiOne by setting a suitable threshold
power.
If several luminaires are connected to the SR-bridge via DALI the SR-bridge
reports a lamp failure if one or more lamps fail, or a gear failure if one or
more of the drivers fail. It is not shown however how many of the connected
devices fail.
Mechanical Design-in
Sizes
The Xitanium SR Bridge is available in two different versions: Built-in and
Independent. See the pictures on the left. The SRB-built-in version is for
mounting inside a luminaire. The SRB-independent version has strain reliefs
for input and output cabling and can be placed outside the luminaire. The
specific dimensions can be found in the
SR Bridge datasheet.
Mounting screw dimensions should be based on the specified fixing hole
diameter in the SR Bridge datasheet. Oversized and undersized screws should
not be used in order to prevent damage to the mounting feet or loose mounting.
Please allow for sufficient free space around the SimpleSet antenna if the SR
Bridge is to be configured after mounting in the luminaire. The minimum
recommended space is depending on the type of SimpleSet configuration tool.
Using the tool as shown on the left (LCN9620), the minimum distance is 19mm
(+/-1mm).
Thermal Design-In
Introduction
The following section covers the critical thermal management point to
facilitate design-in. Taking thermal considerations into account will ensure
optimal performance and lifetime of the system. The maximum case temperature
(tcmax) of the SR Bridge should not be exceeded. It is mandatory to keep the
SR Bridge tcmax within specification to meet SR Bridge lifetime and failure
rate specifications. Please refer to the product datasheet for specific
values.
Case Temperature Point (tc) point
To achieve optimal lifetime and reliability, it is critical that the
temperature of the components in the SR Bridge remains within its rating.
During design, all precautions are taken to ensure that the internal
components are at the lowest possible temperatures.
Initial thermal analysis is performed via IR scans at room temperature to
identify the hottest components of the SR Bridge. Subsequently, detailed
temperature measurements of the critical components are performed under
various input/output conditions at worst case operating temperatures. The
temperature measurements are then correlated to acase point tcon the SR Bridge
as shown in the figure on the left. The tc temperature is a proxy for the
temperatures of the critical internal SR Bridge components.
The location of the tc point is identified on the product type plate and is
marked by a * or O symbol.
The specified ta min-max and tc max values of the SR Bridge must not be
exceeded.
Note: In order to ensure accurate tctest results, the case temperature
should not vary by more than 1°C for a period of at least 30 minutes after a
stable temperature has been
achieved. The tc point should not be obstructed when mounted in the
luminaire/enclosure, neither must its temperature be artificially lowered as a
means to use the SR Bridge above the maximum specified ambient temperature ta.
Electrical Design-In
Inrush current
Inrush current refers to the brief high input current that flows into a load
during the moment of connection to mains; see the figure on the left.
Typically, the amplitude is much greater than the steady-state input current.
The SR Bridge is using advanced zero crossing technology by turning on the
load only when the sinusoidal mains voltage is near its zero crossing point.
This reduces the inrush current of the connected load flowing through the SR
Bridge and its relay to a minimum. The SR Bridge itself has its own inrush
current when connected to mains voltage. Details can be found in the
datasheet. What does inrush current do? A high inrush current can cause
miniature circuit breakers (MCB) or melting fuses to open (nuisance tripping)
or relay contacts to become overloaded if not designed to handle this current
(accelerated wearout). Thus it will limit how many drivers can be connected to
an MCB, melting fuse or relay. In case of the SR Bridge, the max. amount of
drivers which can be switched is defined by the internal relay.
Surge immunity
The Xitanium SR Bridge has limited built-in surge immunity. Please refer to
the datasheet for the applicable differential-mode and common-mode immunity
levels.
In case higher immunity levels are required it is recommended to use an
external Surge Protection Device (SPD).
Electromagnetic compatibility (EMC)
The Xitanium SR Bridge meets EMC requirements per CISPR 15. These tests are
conducted with a reference setup. To maintain good EMC performance at the
luminaire level, the input, output and control wires should be kept separated
as much as possible and the FE terminal must be connected to the luminaire
housing and/or Protective Earth. Mains wires should not be routed directly
over or next to either side of the SR Bridge housing.
Electrical insulation
Please refer to the datasheet for a detailed insulation overview. The Xitanium
SR Bridge meets IEC61347-1 for electrical safety. The SR interface is
classified as SELV while the DALI interface is classified as FELV.
Controllability
How to configure the Xitanium SR Bridge features is explained in the Philips MultiOne User Manual guide; see the Help function of MultiOne or download it from www.philips.com/multione. In this section the SR Bridge features will be explained in more detail.
Load Fault Indicator Threshold (LFIT)
Factory default setting: 15W
This diagnostic feature enables the threshold setting in Watt below which a
lamp failure error will be flagged. Recommend value for the lamp failure power
level is total load power x 0.9.
With the latest version of SR-bridges fault detection can be enabled/disabled
by MultiOne.
Luminaire information
Each Xitanium SR Bridge can be assigned a unique number (GTIN1/EAN13) with an
additional 42-character line for more unique information as part of asset
management
Minimum dim level
Factory default setting: enabled at 1%
This feature enables the setting of the dimming level in % below which the
light cannot be dimmed. This feature can be enabled/disabled.
Relay Switched Output (RSO)
Factory default setting: switches with SR commands. The internal relay can be
configured such that it either remains always open (Ls terminal not live) or
is switching the load on and off in correspondence with the incoming SR on/off
commands.
SR PSU
Factory default setting: enabled
The Xitanium SR Bridge is equipped with an integrated Power Supply Unit (PSU)
to power a sensor via the SR communication bus. This PSU can be disabled if
power is not needed. The PSU must be disabled if more than four SR PSUs are
connected in parallel in order to prevent SR bus current exceeding 250mA.
Miscellaneous
In addition, the consumed energy of the switched load can be read out. A
diagnostic tab is included as well for (field) service purposes. A test tab
allows the testing of the SR Bridge.
Compliance and approval
Xitanium SR Bridge compliances and approvals can be found in the published
Declarations of Conformity (DoC) and ENEC/CB certificates as published on
www.philips.com/oem. For further questions
please contact your local Signify sales representative.
System Disposal
We recommend that the Xitanium Bridge and its components are disposed of in an
appropriate way at the end of their (economic) lifetime. The SR Bridgess are
in effect normal pieces of electronic equipment containing components that are
currently not considered to be harmful to the environment. We therefore
recommend that these parts are disposed of as normal electronic waste, in
accordance with local regulations.
Disclaimer
Note that the information provided in this document is subject to change at any time without prior notice. This document is not an official testing certificate and cannot be used or construed as a document authorizing or otherwise supporting an official release of a luminaire. The user of this document remains at all times liable and responsible for any and all required testing and approbation prior to the manufacture and sale of any luminaire. The recommendations and other advice contained in this document, are provided solely for informational purposes for internal evaluation by the user of this document. Signify does not make and hereby expressly disclaims any warranties or assurances whatsoever as to the accuracy, completeness, reliability, content and/or quality of any recommendations and other advice contained in this document, whether express or implied including, without limitation, any warranties of satisfactory quality, fitness for a particular purpose or non- infringement. Signify has not investigated, and is under no obligation or duty to investigate, whether the recommendations and other advice contained in this document are, or may be, in conflict with existing patents or any other intellectual property rights. The recommendations and other advice contained herein are provided by Signify on an “as is” basis, at the user’s sole risk and expense. Specifically mentioned products, materials and/or tools from third parties are only indicative and reference to these products, materials and/or tools does not necessarily mean they are endorsed by Signify. Signify gives no warranties regarding these and assumes no legal liability or responsibility for any loss or damage resulting from the use of the information thereto given here. Philips and the Philips Shield Emblem are registered trademarks of Koninklijke Philips N.V. All other trademarks are owned by Signify Holding or their respective owners.
©2022 Signify Holding B.V. All rights reserved.
Note that the information provided in this document is subject to change.
Date of release: December, 2022