Schneider Electric XCSLE XCSLF Safety Switch Instruction Manual
- June 9, 2024
- Schneider Electric
Table of Contents
Schneider Electric XCSLE XCSLF Safety Switch
Safety interlock switch (Original instruction)
These devices have been designed to be in compliance with the standards currently in effect: EN/IEC 60947-5-1, EN/ISO 13849-1, EN/IEC 62061, EN/IEC 60947-1, EN/ISO 14119, EN/IEC 60204. These devices can achieve up to category 4 PL=e or SIL 3 (if combined with an appropriate Control Safety Unit PL=e / SIL 3).
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Before servicing this device:
- Disconnect all power before servicing equipment.
- Place a “DO NOT TURN ON” label on all power disconnects.
- Lock all power disconnects in the open position.
- Install and close all covers before applying power or using this device.
Failure to follow these instructions will result in death or serious injury.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel
- Tapped entries for cable gland 1/2” NPT / ISO M20X1,5
- Shim provided with XCSZ01 enabling an XCKJ or XCSL5/7 with a ZCKY07 key to be replaced by an XCSLF with an XCSZ01 key without redrilling any mounting holes
WARNING
LOSS OF SAFETY FUNCTIONALITY
- All spare actuating keys must be stored in a safe place.
- Do not use a master key, modified or dummy actuating key.
- Actuating keys must be permanently mounted by soldering, riveting or non-retractable screws.
- Perform a periodic inspection and verify:
- secure mounting of components, including the head
- mechanical adjustment of XCSLE/LF switch with the XCSZ0* actuating key
- proper operation of the head and proper switching function
- correct sealing of cable entry
- wear: devices should not be used beyond the characteristics stated in catalogue
- do not modify the devices.
- The switch must be protected from environemental shocks.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Wiring diagram
M23 19-pin connectors
Examples
XCSLp with 2-LED module associated with the XPSUAF
Key inserted and locked : GN (green) LED on / Key not inserted : OG (orange) LED on
Head orientation
WARNING
IMPROPER INSTALLATION
- Do not use the safety limit switch as stopper or as centering device for moving guard.
- Use physical stop designed for that purpose.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Adjustment of actuating keys
Tightening torque, tightening capacity
Note: Connection support is made through a 1/2″ NPT and M20 fitting. If using metal conduit, use flexible metal conduit only. Maximum conduit tightening torque is: 23 Nm (17 Ft-lb) for XCSLE, 90 Nm (66 Ft-lb) for XCSLF.
Contact status
WARNING
IMPROPER COVER CLOSING
- Close and screw cover following tightening torque values.
- Lock with manual locking key.
- Remove manual locking key and store it in a safe place.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Servicing procedures
Maintenance
It is imperative to check the following points regularly
- the mechanical adjustment of product XCSLE / LF with the XCSZ 01/02/03/05 tongued key
- wear: the devices should not be used beyond the characteristics stated in catalogues
- make sure of the good electric switching
- it is forbidden to modify the devices.
Any and all liability shall be excluded in case of non compliance with the requirements of this notice.
Characteristics
OPERATION
Operation example of a safety switch XCSLE/LF: Locking when the solenoid is unpowered (Locking on de-energisation models) or locking when the solenoid is powered (Locking on energisation models
Differences when unlocked with power disconnected
Documents / Resources
|
Schneider Electric XCSLE XCSLF Safety
Switch
[pdf] Instruction Manual
XCSLE XCSLF Safety Switch, XCSLE XCSLF, Safety Switch, Switch
---|---